2787-2147
Notes on Operation
Product manual | Version: 1.0.0
55
Power Supply Pro 2
• I
ECB
: trip current of the electronic circuit breaker
• t
ECB
: trip delay of the electronic circuit breaker
You can find more information on the individual values in section
8
10.6.1 “Constant Current” Mode
In this mode, the load current on the output is limited if the nominal output current is ex-
ceeded by a significant amount. The load current is limited to about 110 % of the nominal
output current. This occurs for 20 seconds.
If the overload lasts longer, a 15-second pause occurs, during which the output voltage is
switched off. The output voltage is then switched back on. If the overload is still present,
the process starts again.
This mode is set by default.
I
OUT
/ I
N
t
20s
15s
15s
>110%
100%
20s
Figure 36: “Constant Current” Mode
10.6.2 “Constant Current with Latching Shutdown” Mode
In this mode, the load current on the output is limited if the nominal output current is ex-
ceeded by a significant amount. The load current is limited to about 110 % of the nominal
output current. This occurs for 20 seconds.
If the overload lasts longer, the output is switched off. To switch the output back on, man-
ual intervention is necessary. The following options are available for this:
• Communication interface
• Buttons
• Digital input