2AO FLD IOL CONV 0-10V
5
Functions
5.1 Operating Modes
5.1.1 IO-Link Mode
IO-Link is a communication system for connecting intelligent sensors and actuators to au-
tomation systems. IO-Link is governed by the IEC 61131-9 standard.
The product has an IO-Link communication interface that requires an IO-Link-capable
module (IO-Link master) for interoperation.
The IO-Link interface allows direct access to the process data and diagnostic data and al-
lows product parameters to be set during operation.
For more information about IO-Link and all the necessary information about the required
IO-Link hardware and software, see www.wago.com/<item number>.
IO Device Description (IODD)
The IODD (Input Output Device Description) required for configuration can be down-
loaded from the IO-Link community’s website:
ü
5.2 Parameter Description
Parameters are set through the ISDU mechanism (ISDU = Indexed Service Data Units)
described in the IO-Link specification. This allows read and write access to the ISDU ob-
jects.
The product is parameterized via an IO-Link tool (e.g., WAGO IO-Link Configurator),
The terms “index” and “subindex” used in the following tables refer to Indexed Service
Data Units (ISDUs).
The following parameters are available.
You can find product diagnostic parameters in
8
.
5.2.1 Default Command
Table 7: Default Command – General
Index
2
Access rights
Write-only
Table 8: Default Command
Name
Description
Subindex Data
Type
Length
Factory
Setting
Value Range
Default com-
mand
-
0
UIntegerT 8 bits
-
(130) Restore factory de-
fault
(240) IO-Link 1.1 system
test command 240, event
8DFE appears