14
Device Description
WAGO-I/O-SYSTEM 750
753-501 2DO 24V DC 0,5A
Manual
Version 1.2.0
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
The field voltage and the system voltage are electrically isolated from each other.
Using in safety related applications!
When using the I/O module ( 753-501 ) in safety-related applications, the
instructions and connection examples in Section “Using Interference-Free
Variants of I/O Modules in Safety Related Applications” are to be observed!
Any configuration of the output modules is possible when designing the fieldbus
node. Grouping of module types is not necessary.
The I/O module 753-501 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.