5.5.3
Installing the External Antennal
To mount the external antenna to the EnOcean Gateway, proceed as follows:
1.
To open the EnOcean Gateway, disengage the enclosure cover by turning
gently to the right.
2.
Screw the external antenna to the SMA socket on the printed circuit board;
see also Section “Connections.”
3.
Attach the external antenna cable to the strain relief.
4.
Parameterize the EnOcean gateway for the connection of an external
antenna using the DIP switches, see Section “Operating elements.”
5.
Set the enclosure cover with the printed circuit board onto the enclosure
bottom of the EnOcean Gateway and close it by turning gently to the left.
6.
Position the external antenna to a suitable point and adjust it.
5.5.4
Typical Range
The following maximum ranges apply to typical conditions:
•
Visual connection: 30 m in passageways; 100 m in halls
•
Gypsum board, wood: 30 m through maximum 5 walls
•
Brick walls, porous concrete: 20 m through maximum 3 walls
•
Reinforced concrete walls/ceilings: 10 m through maximum 1 ceiling