34 List of Figures
WAGO I/O System 750
750-940 EnOcean RS-485 Gateway; 868 MHz
Manual
Version 1.3.0, valid from FW/HW Version 01/01
4.2.1
Register Layout
Table
20
: Register Layout
Reg.
No.
Byte
No.
Write
Access
Default
Value
Description
0
0
Yes
1
Modbus address
Value range = 1 ... 247
1
1
2
Yes
0
Reset device
Value range: 1 (reset)
3
2
4
Yes
0
Reset ESP3 report buffer.
Value range: 1 (reset)
5
3
6
No
0
Status: Number of received and buffered ESP3
reports.
7
4
8
No
0
Status: Number of bytes for the next ESP3 report in
the
Process input data
.
9
5
10
No
0
Process input data
Received ESP3 report.
Max. length: 50 bytes.
11
…
…
…
…
…
29
58
No
0
59
30
60
Yes
0
Process output data
ESP3 report to be sent.
Max. length: 50 bytes.
61
…
…
…
…
…
54
108
Yes
0
109
55
110
No
0
String length of the following basic device information
in bytes.
111
56
112
No
–
Basic device information
In ACSII format.
Max. length: 80 bytes.
Example:
“
WAGO Kontakttechnik GmbH & Co. KG 2850-3151
001/001/000 001.003.00
”
113
…
…
…
…
…
95
190
No
–
191