22   WAGO Operating Instructions 4PU/4PS/2PU CT 

 

 
 
 
 
 
 

6.7.6 Modbus

®

 ID

 

4PU and 4PS 

2PU CT 

The Modbus

®

 ID can be set  from 1 to 247; the 

default Modbus

®

 ID is set to 1. 

 

 

 

6.7.7 

Modbus®

-Baudrate

 

4PU and 4PS 

2PU CT 

The default Modbus

®

 baud rate is 9600 Bd. This 

can be changed to the following values: 
115,200 / 56,700 / 38,400 / 19,200 / 9600 / 4800 
/ 2400 / 1200 / 600 / 300 Bd. 

 

 

 

6.7.8 Modbus

®

 Parity

 

4PU and 4PS 

2PU CT 

The default Modbus

®

 parity is even. This can be 

changed to the following values: 
None / Odd / Even 

 

 

 

6.7.9 M-Bus-ID

 

4PU and 4PS 

2PU CT 

The M-Bus ID can be freely set from 0 to 250; M-
Bus ID 0 is configured by default. 

 

 

 

 

 

Содержание 879-3000 4PU

Страница 1: ...Operating Instructions Version 082022V1 6 2022 distributed by WAGO All rights reserved WAGO Energy Meters MID with Push in CAGE CLAMP and Lever 879 3020 4PS 879 3000 4PU 879 3040 2PU CT...

Страница 2: ...MID relevant 17 6 3 Display Part 3 non MID relevant 17 6 4 Process Diagram 4PU 4PS 2PU CT 18 6 5 Settings 19 6 6 Bluetooth 19 6 7 Settings via Buttons 20 6 7 1 Password 20 6 7 2 Tariff 20 6 7 3 S0 Pu...

Страница 3: ...nly Access must be limited to authorized qualified staff having the appropriate key or tool Proper Handling Requirements for the trouble free safe operation of the product are proper transport storage...

Страница 4: ...Further details are given in the contractual agreements Please send your suggestions for modifications to modified or new hardware or software configurations directly to WAGO GmbH Co KG Never break an...

Страница 5: ...possible that this meter has a defect or failure for which we apologize Under normal conditions your product should provide you with years of trouble free service If there is a problem with the energy...

Страница 6: ...6 WAGO Operating Instructions 4PU 4PS 2PU CT 3 Certificates 3 1 MID Declaration of Conformity 4PU and 4PS...

Страница 7: ...WAGO Operating Instructions 4PU 4PS 2PU CT 7 3 2 CE Declaration of Conformity 4PU und 4PS...

Страница 8: ...8 WAGO Operating Instructions 4PU 4PS 2PU CT 3 3 MID Declaration of Conformity 2PU CT...

Страница 9: ...WAGO Operating Instructions 4PU 4PS 2PU CT 9 3 4 CE Declaration of Conformity 2PU CT...

Страница 10: ...during operation 75 Humidity during storage 95 International storage EN50470 1 3 Accuracy class B 1 accuracy Protection against Dust and water IP51 front side IP20 connection Protection class II Ambi...

Страница 11: ...rotocol BLE 4 2 Frequency range Bluetooth 4 0 2402 2480 MHz 40 CH 4 5 M Bus Communication Specifications Bus type 2 wire M Bus Baud rate 300 600 1200 2400 standard 4800 and 9600 Parity Even even uncha...

Страница 12: ...Fine stranded conductors 0 2 4 mm 24 12 AWG Fine stranded conductors with ferrule and plastic collar 0 25 2 5 mm Push in technology can be used for solid conductors fine stranded conductors and fine...

Страница 13: ...utput Phase L2 IN L3 Input Phase L3 OUT L3 Output Phase L3 N External bridge on terminal point IN L2 4 S0 output 1 5 Ground for S0 6 S0 output 2 7 Modbus A 8 Ground for Modbus B M Bus 9 M Bus 10 11 Ta...

Страница 14: ...L2 IN L3 Input Phase L3 OUT L3 Output Phase L3 N External bridge on terminal point IN L2 4 S0 output 1 5 Ground for S0 6 S0 output 2 7 Modbus A 8 Ground for Modbus B M Bus 9 M Bus 10 11 Tariff 230 VA...

Страница 15: ...Output CT3 U1 U2 U3 Voltage L1 L2 L3 N External bridge on terminal block IN U2 4 S0 output 1 5 Ground for S0 6 S0 output 2 7 Modbus A 8 Ground for Modbus B M Bus 9 M Bus 10 11 Tariff 230 VAC 2PU CT 3...

Страница 16: ...ient for the operator Both the fuse and circuit breaker must meet the specifications of the building s electrical design and all local codes An external fuse or thermal shutdown used as an overcurrent...

Страница 17: ...in Tariff 4 Reverse direction 2 8 1 Negative Active Energy in Tariff 1 2 8 2 Negative Active Energy in Tariff 2 2 8 3 Negative Active Energy in Tariff 3 2 8 4 Negative Active Energy in Tariff 4 The ta...

Страница 18: ...18 WAGO Operating Instructions 4PU 4PS 2PU CT 6 4 Process Diagram 4PU 4PS 2PU CT...

Страница 19: ...S 2PU CT If the arrows point to the Bluetooth icon press the middle button The Bluetooth interface of the meter is now enabled and ready for communication with the WAGO Energy Meter Configurator app T...

Страница 20: ...ring the correct password the settings menu appears 6 7 1 Password 4PU and 4PS 2PU CT The settings via the buttons are protected by a password This password is also relevant for the settings via Bluet...

Страница 21: ...O System 750 we recommend using the 4 channel digital input module Item No 750 409 The meters have a pulse value of 1 000 pulses kWh by default The value setting can be changed to the following values...

Страница 22: ...CT The default Modbus baud rate is 9600 Bd This can be changed to the following values 115 200 56 700 38 400 19 200 9600 4800 2400 1200 600 300 Bd 6 7 8 Modbus Parity 4PU and 4PS 2PU CT The default Mo...

Страница 23: ...The meter is equipped with a blue backlight If desired this can be switched to permanently on permanently off or on when a button is pressed 6 7 12 Power down Counter 4PU and 4PS 2PU CT The power down...

Страница 24: ...erse Active Energy Tariff 2 21 7 0 Forward Active Power L1 2 8 3 Reverse Active Energy Tariff 3 41 7 0 Forward Active Power L2 2 8 4 Reverse Active Energy Tariff 4 61 7 0 Forward Active Power L3 React...

Страница 25: ...gy L3 7 8 0 Inductive Reverse Reactive Energy Q3 Total 2 8 0 Reverse Active Energy 7 8 1 Inductive Reverse Reactive Energy Q3 T1 22 8 0 Reverse Active Energy L1 7 8 2 Inductive Reverse Reactive Energy...

Страница 26: ...e three CT HISTORY REGISTERS So CT HISTORY 01 0005 5 A 02 0100 5 A and 03 1100 5 A In the first image entry into the submenu is confirmed with OK in the menu In the following figures the entries CT HI...

Страница 27: ...tting 4 CT3 300 5A CT4 400 5A 4 444kWh Hist CT4 4 444kWh fixed and unchangeable then continuous with the new CT ratio to the next CT setting 5 CT4 400 5A CT5 500 5A 5 555kWh Hist CT4 5 555kWh fixed an...

Страница 28: ...s flashing No pulse output The pulse output is not supplied with DC voltage The pulse output is not correctly connected Use a voltmeter to check whether the external voltage source Ui is 5 27 VDC Chec...

Страница 29: ...AC at terminal blocks 10 and 11 the meter switches to Tariff 2 and writes the measured values to the register provided for T2 A1 2 Switching Tariffs to T3 and T4 Tariffs 3 and 4 can be enabled directl...

Страница 30: ...ory settings for the M Bus are as follows Baud rate 2400 8 data bits Parity Even 1 stop bit The secondary address 253 FD is preset to the last 8 digits of the serial number You will also find this pri...

Страница 31: ...7 123456789 Wh Activeenergy exportT3 84 30 83 3C 15 CD 5B 07 123456789 Wh Activeenergy exportT4 84 80 10 83 3C 15 CD 5B 07 123456789 Wh Total kWh resettable 04 83 FC 10 15 CD 5B 07 123456789 Wh Reacti...

Страница 32: ...Code 68 07 07 68 53 01 51 09 FD 3A 05 E5 Combinations Code 05 01 02 03 04 and 05 S0 Rate 68 0A 0A 68 53 01 51 0C FD 3A 00 00 01 00 E5 S0 Rate 100 10 000 2 000 1 000 100 10 1 0 1 0 01 Resettable regist...

Страница 33: ...to even odd and none Data and stop bits cannot be changed If you connect the meter via a serial converter RS 485 for test purposes please note that due to the incomplete implementation of the Modbus...

Страница 34: ...3 import export 4 import export 5 import export 10 4010 LCD rolling time 03 1 sec HEX 4011 Parity 03 1 Signed 1 even 2 none 3 odd 4012 L1 current direction 03 1 ASCII F import R export 4013 L2 curren...

Страница 35: ...ive power 03 2 kW Float ABCD 5014 L1 active power 03 2 kW Float ABCD 5016 L2 active power 03 2 kW Float ABCD 5018 L3 active power 03 2 kW Float ABCD 501A Total reactive power 03 2 kvar Float ABCD 501C...

Страница 36: ...01C T2 Active energy export 03 2 kWh Float ABCD 601E L1 Active energy export 03 2 kWh Float ABCD 6020 L2 Active energy export 03 2 kWh Float ABCD 6022 L3 Active energy export 03 2 kWh Float ABCD 6024...

Страница 37: ...2 kvarh Float ABCD 6065 Import inductive reactive energy in Q1 T1 03 2 kvarh Float ABCD 6067 Import inductive reactive energy in Q1 T2 03 2 kvarh Float ABCD 6069 Import inductive reactive energy in Q1...

Страница 38: ...e 06 1 Signed Command 01 06 400F 0004 new code 4 F R 1 import only 2 export only 3 import export 4 import export 5 import export 10 4010 LCD rolling time 06 1 Seconds HEX Command 01 06 4010 0025 new t...

Страница 39: ...bH Copyright WAGO GmbH Co KG All rights reserved The content and structure of the WAGO websites catalogs videos and other WAGO media are subject to copyright Distribution or modification of the conten...

Отзывы: