background image

9970-0966

s07870000_00000007 V1.5.0 © 2018

WAGO Kontakttechnik GmbH & Co. KG

Hansastr. 27

D-32423 Minden

www.wago.com

En

Operating and Assembly instructions

Safety related! Note and keep!

Subject to design changes

Support:  Phone:  +49 (0) 571/887 - 44555  /  Fax:  +49 (0) 571/887 - 844555 

 

Mail: [email protected]

Power Supply Eco

DC power supply

787-2742 / 787-2744

1  Safety Information

Do not work when devices are energized!

High voltage can cause electric shock or burns. 

Switch off all power to the device prior to performing any installation, repair or 

 

maintenance work.

Live parts are likely to be touched!

The party setting up the device is responsible for providing appropriate touch guards. 

 

The installation regulations must be observed for each individual application.

Hot surface!

The surface of the housing can become hot during operation. Under high ambient 

temperatures, there is a danger of burns when the device is touched. If the device was 

operated at high ambient temperatures, allow it to cool off before touching it!

Select conductor cross sections as required for current load!

In the event of a fault, the output current of a power supply can be up to 1.5 × I

OUT

.

Only use conductor cross sections designed for this current load.

i

Observe complete product documentation!

The complete product documentation consists of this document and the device 

 

manual. You will find this manual on the Internet at www.wago.com/

<OrderNumber>

.

In addition, please observe the information provided on the device’s housing.

Please especially observe the following:

•  The device described in these instructions shall only be installed by a qualified electrician 

according to both EN 50110­1/­2 and IEC 60364.

•  Before startup, check the device for any damage that may have occurred during shipping. 

 

The device shall not be put into operation in the event of mechanical damage.

•  Observe the applicable laws, standards and regulations.

•  Observe the current, accepted technology standards and practices at the time of installation.

•  Only install this device in dry indoor rooms.

•  Do not install the devices on or in the vicinity of easily flammable materials.

•  Only use this device in a controlled enviroment.

•  The device is an open system. The device must be installed in a suitable electrical and fire 

enclosure. This enclosure must:

-  guarantee that the max. permissible pollution degree is not exceeded

­  offer adequate protection against direct or accidental contact,

­  guarantee mechanical stability over the entire operating temperature range

•  Ensure proper handling to protect device during shipping and handling. Particularly during 

transport and handling, ensure that no parts are bent and that electrical spacing remains  

constant.

•  Keep sufficient distance from adjacent components to avoid interfering with the cooling!

•  The operator must provide a mains isolator in the device supply line. The 

OFF

 position must 

be clearly marked on this isolator. The isolator must be located near the device where it can be 

operated.

This product may only be used as described in this note and in the complete instructions. Use 

other than this may represent a risk to safe, intended use and will nullify the warranty or guarantee. 

WAGO Kontakttechnik GmbH & Co. KG is not liable for damage resulting from non­intended or 

 

improper use.

2  Technical Data

Table 1: Device

787-2742

787-2744

Dimensions (mm) W × H × D

(depth from upper­edge of DIN 35 rail)

80 × 130 × 170

140 × 130 × 170

Weight

1.7 kg

2.6 kg

Table 2: Electrical Data

787-2742

787-2744

IN

Y 400 … 480 V 3~;

 

1.3 … 1.1 A; 50 … 60 Hz

Y 400 … 480 V 3~;

 

1.9 … 1.6 A; 50 … 60 Hz

OUT

24 V   SELV; 20 A

24 V   SELV; 40 A

Table 3: Wiring – Terminal Assignment

787-2742

787-2744

Input terminal

2606 Series

2606 Series

Output terminal

2606 Series

2616 Series

DC OK contact

2091 Series

2091 Series

Table 4: Wiring – Dimensions

Cross section

2606 Series

 

2616 Series

 

 

2091 Series

0.5 … 10 mm² / AWG 20 … 08 

1)

 

2)

 

0.5 … 6 mm² / AWG 20 … 10 

2) 3) 4)

0.75 … 16 mm² / AWG 18 … 06 

1)

 

0.75 … 25 mm² / AWG 18 … 04 

2)

 

0.75 … 16 mm² / AWG 18 … 06 

2) 3) 4)

0.2 … 2.5 mm² / AWG 24 … 12 

1) 2)

0.2 … 2.5 mm² / AWG 24 … 12 

2) 3)

0.5 … 2.5 mm² / AWG 22 … 12 

2) 4)

Strip length

2606 Series

2616 Series

2091 Series

11 … 13 mm / 0.43 … 0.51 in

18 … 20 mm / 0.71 … 0.79 in

9 … 10 mm / 0.35 … 0.39 in

Use conductors rated to

≥ +75 °C (surrounding air temperature, operation: ≤ +60 °C)

≥ +90 °C (surrounding air temperature, operation: > +60 °C)

1)

 solid   

2)

 fine­stranded   

3)

 with insulated ferrule   

4)

 with uninsulated ferrule

Table 5: Ambient Conditions

Protection Class

I

Degree of protection

IP20

Overvoltage categorie

II

Pollution degree

2

Branch circuit breaker 

*

16 A (for USA/Kanada only: 15 A)

Surrounding air temperature, operation

−20 … +70 °C; Derating: −2 % / K > +45 °C

Surrounding air temperature, storage

−40 … +85 °C

Rel. humidity

10 … 95 % (non­condensing)

Elevation above sea level

Max. 2000 m

* The branch circuit breaker can be used for activation during installation. In this case, the branch circuit breaker must meet all the 

requirements on this isolator device.  

If an additional switch is used, it must have the same electrical load capacity as the branch circuit breaker..

Table 6: Mounting

Mounting position:  

Nominal position (see “Mounting”)

Distances 

*

Top

Bottom

Left

Right

Passive adjacent devices

50 mm

50 mm

10 mm

10 mm

Active adjacent devices

50 mm

50 mm

20 mm

20 mm

*

 Upon request, other spacing also approved for special operating conditions.

3  View

Table 7: View (Example: 787­2742)

g

b

i

h

f

e

d

c

a

Pos. Assignment

a

Front side

b

787­2742: 2606 Series output (+ + − − −)

787­2744: 2616 Series output (+ + − − −)

c

Potentiometer for setting the output  

voltage between 24 … 28 VDC

d

DC OK indicator

LED green: Output voltage > 22 VDC

e

Overload indicator

LED red: Output current > 105 %

f

DC OK contact 

picoMAX

®

 3.5 (13 14 13)

g

Type plate

h

2606 Series input (L1 L2 L3 

3

)

i

Mount/removal latch on a DIN­rail

4  Mounting

Install the device in the nominal position exclusively to ensure proper heat dissipation (see also 

“View”):

•  Front side (a) front

•  Ventilation openings top and bottom

Other mounting positions should only be used at one‘s own risk.

Avoid electrostatic discharge!

The devices are equipped with electronic components that you may destroy by 

electrostatic discharge when you touch. Please observe the safety precautions against 

electrostatic discharge in accordance with EN 61340­5­1/­3

Pay attention while 

 

handling the devices to good grounding of the environment (persons, job and packing).

4.1  DIN 35 Rail

B

A

C

D

Figure 1: Mounting 

Figure 2: Removal

4.1.1  Installation to the DIN Rail

Install the device by snapping it into the DIN rail according to EN 60715 (see Figure “Mounting”):

1.  Place the device with its DIN rail guide on the top edge of the DIN rail.

2.  Press the device onto the DIN­rail [A] while simultaneously pulling on the latch (i) [B] until it 

locks into place.

3.  To ensure secure fastening on the DIN rail, fit end clips on either side of the device (e.g., Order 

No. 

249-117

).

4.1.2  Removal from the DIN Rail

1.  To remove (see Figure “Removal”), pull down the latch (i) [C]. 

 

Use a screwdriver or an operating tool for this.

2.  Tilt the device forward [D] and detach it from the DIN rail.

5  Wiring

Wiring is based on the contact type:

•  Input contacts (h) and output contacts (b):

 

Use the respective operating lever to open the clamping unit (toolless)

•  DC OK contact (f):

 

Use the respective push­button and an operating tool or screwdriver to open the clamping 

unit.

All terminals use push­in technology for toolless wiring by plugging them in directly. Please note:

•  Fine­stranded conductors must have a ferrule (insulated or uninsulated). Corresponding 

 

conductor sizes are found in the “Wiring – Dimensions” table.

•  You can plug solid conductors in directly even without a ferrule. 

 

The following restrictions apply to the information in the “Wiring – Dimensions” table:
­  Input and output terminals:

 

No restrictions in conductor size

­  DC OK contact:

 

Conductor size > 0.25 mm²/AWG 23

L1

L2

L3

DC+

DC+

DC -

DC -

DC -

DC O.K

13      14      13

Отзывы: