765-4203/0100-0000

Functions

30

Product manual | Version: 1.0.0
4PORT IOL-A FLD EC DC 24V 2.0A

Simulating Inputs

To simulate input data, you can set alternative values that are used for the input instead
of the actual process data values. This allows you to test how the system (i.e., the mod-
ule and a connected controller) responds to specific inputs.

With digital inputs, you can simulate pin 2 and pin 4.

For IO-Link, you can simulate port 16 data bytes.

Simultaneous Access

A device-internal mechanism prevents simultaneous access by multiple instances. This
ensures that only one single instance at a time ever has write access.

“Forcing” Operating Mode Must Be Enabled in the Parameterization

The “Forcing” operating mode can be switched off by the higher-level controller. This is
done with the “Force mode setting” parameter – see 

8

 

Module Parameters [

}

 45]

. To

enable forcing, the “Force mode setting” parameter value must be set to 0 (“Enable force
mode”). This is the default setting in the device description file provided with the device.

5.3 Monitoring Functions

The 765 Series modules have extensive internal sensors for measuring:
• Temperatures
• Currents
• Voltages

The measurements are performed for the module and for pin 1, pin 2 and pin 4 of each
port. The measured values can be displayed in the WAGO I/O Field Webserver or the
WAGO I/O Field app. Alternatively, an OPC UA client can read out the measured values
and display them.

In the module, the measured values are compared to limiting values. An alarm or event is
generated if a value falls above or below a limiting value (e.g., a temperature limiting
value). The module can send this alarm/event
• EtherCAT

®

: Send emergency telegram to the controller, or the controller can read the

diagnostic history object (Index 0x10F3),

• to the OPC UA client upon: OPC UA: event.

The OPC UA client application can use the measured values, for example to implement
load management. You can find information on load management in 

8

 

Design Power

Supply [

}

 38]

.

5.4 Overload protection

The module has built-in overload protection and periodically measures the current, volt-
age and temperature.

If the output current, supply voltage or temperature exceeds the maximum value, the
module switches off a pin/port

Содержание 765-4203/0100-0000

Страница 1: ...Product manual Version 1 0 0 WAGO I O System Field 4 Port IO Link Master Class A EtherCAT 24 V DC 2 0 A 4 M12 Connection 765 4203 0100 0000...

Страница 2: ...as been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreci ate any information or suggestions for improving the documen...

Страница 3: ...14 4 2 Connections 15 4 2 1 Power supply 15 4 2 2 Communication Interfaces 16 4 2 2 1 IO Link Master 16 4 2 3 Network Connections 16 4 2 3 1 ETHERNET Interfaces 16 4 3 Circuit Diagram 17 4 4 Technica...

Страница 4: ...upply Examples 42 6 3 Settings Options 45 6 3 1 Module Parameters 45 7 Transport and Storage 50 8 Installation and Removal 51 8 1 Installation 51 8 1 1 Tools Required for Installation 51 8 1 2 Before...

Страница 5: ...zing the Module via the WAGO I O Field Webserver 73 10 3 1 4 1 Configure Ports 73 10 3 1 4 2 Accessing a Connected IO Link Device 77 10 3 1 4 3 Configuring IP Parameters 80 10 3 1 4 4 Storing Maintena...

Страница 6: ...9 Emergency Error Codes 106 11 2 1 10 Events Triggered by the IO Link Master 108 11 2 1 11 Events Triggered by the IO Link Device 109 11 2 2 Diagnostic Data of the Modules 110 12 Service 111 12 1 Res...

Страница 7: ...l data and approvals certificates for a product Instruction leaflet Is included with each product Contains initial information on safe handling of the product All documentation is available at www wag...

Страница 8: ...o special instructions Modifications to the hardware or software have been made by the user or third parties that are not described in this documentation and that has contributed to the fault Individu...

Страница 9: ...e result This symbol identifies the result of an action Lists Lists first level Lists second level Figures Figures in this documentation are for better understanding and may differ from the actual pro...

Страница 10: ...ghts regarding patent utility model or design registration Third party trademarks are referred to in the product documentation The and TM symbols are omitted hereinafter The trademarks are listed in t...

Страница 11: ...ut into operation by qualified electrical special ists per EN 50110 1 2 and IEC 60364 Comply with the laws standards guidelines local regulations and accepted technol ogy standards and practices appli...

Страница 12: ...gloves and attach protective covers and or touch proof protection 2 5 Indirect Safety Only use a dry or cloth or a clothed dampened with water to clean the product Do not use cleaning agents e g abras...

Страница 13: ...and configuration using the WAGO I O Field app and a mobile device WAGO I O Field Webserver integrated Webserver accessible via Ethernet over EtherCAT EoE with the following functions configuration pa...

Страница 14: ...Product manual Version 1 0 0 4PORT IOL A FLD EC DC 24V 2 0A 4 Properties 4 1 View Figure 1 View Table 3 Legend for View Figure Function Position Custom Name Description ETHERNET 2 X21 ETHERNET interf...

Страница 15: ...supply LED 24 VDC 12 2L X32 2L supply voltage LED 24 VDC IO Link Class A 8 X01 X04 IO Link port ports X01 X04 M12 A coded 9 1 3 5 7 IO Link port LEDs for ports X01 X04 channel B pin 2 7 0 2 4 6 IO Lin...

Страница 16: ...Examples 42 There you will find information on the maximum permitted current consumption 4 2 2 Communication Interfaces 4 2 2 1 IO Link Master Table 5 IO Link class A IO Link Class A Pin Signal Descri...

Страница 17: ...ue Item Number 0765 4203 0100 0000 Product function 4 Port IO Link Master Class A Product name short 4 PORT IOL A FLD EC 24 VDC 2 0 A Product name long 4 Port IO Link Master Class A EtherCAT 24 V DC 2...

Страница 18: ...detection of changes However it should be noted that the transfer and pro cessing of the process data in the device and in the controller also take time and reduce the maximum in put signal change Rec...

Страница 19: ...e and overvolt age Voltage drop through high side path Less than 200 mV Maximum capacitive load 1000 F parallel to 24 0 1 Hz 470 F parallel to 12 0 1 Hz 220 F parallel to 6 0 1 Hz Maximum inductive lo...

Страница 20: ...he common reference point 4 4 6 Environmental Conditions Table 13 Environmental Conditions Property Value Surrounding air temperature operation 25 C 70 C Surrounding air temperature storage 40 C 80 C...

Страница 21: ...nostic functions http www wago com UA DigitalConnector http www wago com UA Diagnostics Server profile Micro Embedded Device Protocol OPC UA TCP User access Anonymous read access only Username passwor...

Страница 22: ...OPC UA The following figure shows the maximum permissible current I that can flow into the product as a function of the surrounding air temperature T 5 10 15 20 20 T C 25 30 35 40 45 50 55 60 65 70 I...

Страница 23: ...r with the follow ing specifications Operating frequency 2402 2480 MHz Maximum RF output power 20 mW RED Certificate number R20 0936 01 TEC Slimline FCC FCC ID 2AKUE SLIMLINE ISED Certificate number 2...

Страница 24: ...g output process data One object 0x160x for each port with the IO Link output data or the value of the digital output Object 0x1610 for transferring the digital outputs of all ports pin 2 in each case...

Страница 25: ...sed in slot IO Link Port X04 and can be 1 2 4 8 16 or 32 bytes 0x6030 02 1 byte Input byte 1 0x6030 20 1 byte Input byte 31 Objects 0x1A0x with port operating mode Digital input The following table de...

Страница 26: ...A 7 Port X04 pin 2 DI B or DO B Byte 2 0 7 0 Table 23 Input Process Data pin based assignment Byte Bit Input Process Data Byte 1 0 Port X01 pin 4 DI A or DO A 1 Port X02 pin 4 DI A or DO A 2 Port X03...

Страница 27: ...ital output The assignment is as follows Object 0x1600 is assigned to port X01 Object 0x1601 is assigned to port X02 Object 0x1602 is assigned to port X03 Object 0x1603 is assigned to port X04 Objects...

Страница 28: ...te PD C Q pin 4 Port X01 pin 4 functions as digital output Object 0x1600 contains object 0x7000 01 and transfers the outputs data to the digital output connected to port X01 pin 4 Bit 0 0 output off B...

Страница 29: ...hod is helpful for commissioning systems and troubleshooting The Forcing function can be accessed through the following tools WAGO I O Field Webserver WAGO I O Field app on mobile devices Systems like...

Страница 30: ...with the device 5 3 Monitoring Functions The 765 Series modules have extensive internal sensors for measuring Temperatures Currents Voltages The measurements are performed for the module and for pin...

Страница 31: ...module Using a Web browser the user can view the Web pages and dis play and modify parameters WAGO I O Field App The WAGO I O Field app is an app for mobile devices that can communicate with a 765 mod...

Страница 32: ...you have changed parameters of the port configuration via the WAGO I O Field Web server the WAGO I O Field app the WAGO IO Link Configurator or the OPC UA Client please note that these changes are in...

Страница 33: ...mation include Display current measured values for the ports temperature voltage current and state on pins 1 2 and 4 Display information about the connected IO Link module Display the status informati...

Страница 34: ...on Set up and manage users 8 Logging Users on and off and Managing Them 87 Sign in Sign out Log users on and off 5 5 4 WAGO I O Field app The WAGO I O Field app is an app for maintenance diagnostics o...

Страница 35: ...to modules with integrated IO Link master ports The functional scope described can vary depending on the module type Note Read the online help You can find Product specific information on the WAGO App...

Страница 36: ...es current voltage temperature Events overcurrent overload and overtemperature Read status information Read process data Read statistics minimum maximum current per pin minimum maximum voltage per pin...

Страница 37: ...tem Do not connect control components and control networks to an open network such as the Internet or an office network WAGO recommends protecting control components and control networks against unaut...

Страница 38: ...The module has integrated protective functions see 8 Overload protection 30 to prevent damage in overload situations such as overcurrent or short circuit However it is important not to rely on these...

Страница 39: ...es to the total current in a supply cable If this upper limit is ex ceeded there is a risk of destruction of or damage to the module To avoid this protect each supply line with a fuse or circuit break...

Страница 40: ...individual pins of the ports The following upper limits apply to the currents on the pins of the individual ports Table 35 Upper Limits for Current on the Individual Pins of the Connections Pin Norma...

Страница 41: ...currents in supply cables 1 and 2 must be followed at all times Table 38 Rules for Supply Cables 1 and 2 Current Supply Cable 1 Supply Line 2 Total current for the supply cable rule 1 IX31_1L 16 A IX3...

Страница 42: ...the calculated total currents of the two supply cables are measured by the chip used in the 765 Series products and thus can be recorded by a monitoring application These val ues can be accessed via t...

Страница 43: ...are thus permissible Example of a Power Supply Group via PWR OUT If you connect another device to the PWR OUT X32 power supply output this forms a supply group The maximum permissible current feedthro...

Страница 44: ...port X02 one digital input output with max current demand of 1 A on pin 1 On port X03 one digital input output with max current demand of 0 5 A on pin 1 On port X04 one digital input output with max...

Страница 45: ...3 Settings Options 6 3 1 Module Parameters Indexes 0x2000 to 0x2003 Parameters with indexes 0x2000 to 0x2003 configure the module Table 39 Module Parameters Index Subindex Parametername Value Range De...

Страница 46: ...ce and in connection with the WAGO I O Field app 0x2003 02 BT timeout 6 59 s 30 Switch off time of the Bluetooth inter face if not used a new Bluetooth connection can be established by an optical sign...

Страница 47: ...n or der for a signal change to be de tected 150 15 ms filter time 200 20 ms filter time 0x2100 24 0x2110 24 Port X01 X02 Configuration IOL input length 0 32 0 Length of the input data Set automatical...

Страница 48: ...ware Please do not change 0x8000 25 0x8010 25 IO Link port X01 X02 Process Data Out put Length 0 223 0 Length of the output data Set automatically by the configuration software Please do not change 0x...

Страница 49: ...ge Time Basis Bits 6 7 Factor Bits 0 5 Port Cycle Time Formula Examples 32 3 2 ms 48 4 8 ms 64 127 0 4 ms 01 0 63 6 4 ms 0 4 ms factor 68 8 0 s 93 18 0 ms 100 20 8 ms 128 191 1 6 ms 10 0 63 32 ms 1 6...

Страница 50: ...l protection during transport and storage Store the product in suitable packaging preferably the original packaging Only transport the product in suitable containers packaging Make sure the product co...

Страница 51: ...ainst weather exposure no di rect sunlight no salt water or spray Note that the module should not be installed in the immediate vicinity of objects or de vices that can get hot For a high level of mod...

Страница 52: ...rom each other and to give them a large surface to dissipate heat to the surrounding air 8 1 6 Installation You can install the product directly on your equipment with screws Mount the product on a fl...

Страница 53: ...ion allow it to cool before touching it or use gloves Prepare for removal as follows 1 If the product is contaminated clean it before removal It is especially important to clean contaminated screw cla...

Страница 54: ...nstructions to reduce interference Lay network cables e g fieldbus cables in their own cable ducts Do not lay network cables parallel to power supply cables through which high power flows When install...

Страница 55: ...r supply to connection X32 The following procedure is especially advantageous Install the power supply for the module electronics independently of the power supply for the actuators Provide independen...

Страница 56: ...ICE Damage to electronics For passthrough of the supply voltage the following should be noted The maximum total current permitted on 1L is 16 A The maximum total current permitted on 2L is 16 A The te...

Страница 57: ...lculated approximately with the following formula RL l K A where RL Cable resistance I Cable length K Specific cable resistance of the conductor material usually copper according to manufacturer s spe...

Страница 58: ...which you have mounted the module 2 Connect the port of the EtherCAT master to X21 IN of the EtherCAT slave using an ETHERNET cable 3 Tighten the pluggable connector using the knurled head screw Conn...

Страница 59: ...upply contacts see Rule 3 in 8 Design Power Supply 38 section Rule 3 Ports X01 X02 etc The following figure shows the potential routing of the two load circuits within the module If a port is operated...

Страница 60: ...4 3 1L 1L DIO B C Q 1L 1 2 4 3 1L 1L DIO B C Q 1L 1 2 4 3 1L 1L DIO B C Q 1L FE PWR IN PWR OUT 4 1 3 2 2L 1L FE 2L 1L 4 1 3 2 2L 1L FE 2L 1L Ethernet Ethernet Figure 10 Schematic Circuit Diagram of t...

Страница 61: ...red port configuration IO Link master and pin 2 as a digital output Connection of a digital input at channel A Required port configuration pin 4 as digital input and pin 2 disabled Connection of two d...

Страница 62: ...anual Version 1 0 0 4PORT IOL A FLD EC DC 24V 2 0A Connection Option Description Connection of a digital output on channel A and a digital input on channel B Required port configuration pin 4 as a dig...

Страница 63: ...ting the IP address for the Module for the EtherCAT Master You can set the IP address for the module in the configuration software of the EtherCAT master e g TwinCAT To do so create a configuration pr...

Страница 64: ...port of the 765 mod ule corresponds to a slot For each IO Link port X01 X02 specify what is connected to it IO Link device and how much process data it transmits Digital Input Digital Output whether n...

Страница 65: ...tting Parameters You can set the parameters for the module in the configuration software of the EtherCAT master The existing parameters contain the basic settings for the module which you can adapt to...

Страница 66: ...evice information Product data and WAGO contact information Device version Information on the product version Hardware name and version number Software name and version number Website version number M...

Страница 67: ...the Information Status Configuration IOL and Process data tabs The Configuration tab also offers the option of making port settings You can access the port information as follows 1 From the main menu...

Страница 68: ...rmation tab shows the following current measured values for each of pin 1 pin 2 and pin 4 of the selected port Temperature of the pin measured in C Voltage on the pin measured in volts Current flowing...

Страница 69: ...er of profile IDs in the profile characteristic index 0x000D of the connected product Vendor name Detailed name of the manufacturer vendor of the connected device up to 64 characters Vendor text Addit...

Страница 70: ...operating mode What is the true input output data length of the connected product in bytes What is the manufacturer ID or product ID of the product connected to the IO Link port Proceed as follows to...

Страница 71: ...9 Meaning of the Individual Bits Bits of Port Quality Info Description Bit 0 0 input process data valid 1 input process data invalid Bit 1 0 output process data valid 1 output process data invalid Bit...

Страница 72: ...is value is the device ID of the connected product 10 3 1 3 12 Displaying Process Data You can view the process data associated with a specific port on the Process Data tab Proceed as follows to view...

Страница 73: ...0 8 Forcing IO Link ports 91 10 3 1 4 1 Configure Ports Figure 17 Port XX Menu Item Configuration Tab The Configuration tab is used to display and modify the following port settings for the se lected...

Страница 74: ...e expected cycle time 10 Click the Apply button Your changes now take effect Configuring the Operating Mode for Pin 4 of the Port You can select the port operating mode for pin 4 of the selected IO Li...

Страница 75: ...digital output The signal is permanently set to logic 1 for testing pur poses only Configuring the Device Check for Validation and Backup Note In the IOL Autostart operating mode see above this drop d...

Страница 76: ...during Validation and Backup Selection Option Inspection Level Backup Level Description No device check NO_CHECK Disable No device check is performed Type compatible de vice V1 0 TYPE_COMP Disable Dev...

Страница 77: ...specification Required Rights Changes to settings require operator or admin rights If you do not have these the tab is grayed out and the displayed values cannot be edited Access to IO Link Device To...

Страница 78: ...sult Figure 19 Ports X01 X08 Read Access to IO Link at Index 43 and Subindex 0 Unsuccessful Read Failed If the operation was not successful an error message appears in the history with error codes fro...

Страница 79: ...med If the operation was successful the text Write ok and the result appear in the history The entries in the history then have the following structure Time Index Subindex Write ok Result If the opera...

Страница 80: ...therCAT master configures the module s IP address Therefore with EtherCAT modules no manual IP address configuration is necessary 10 3 1 4 4 Storing Maintenance Information On the Maintenance Informat...

Страница 81: ...Printable ASCII string max 32 characters Uniform label string in the system for the location where the device is in stalled I M1 TAG_LOCATION Installation Date ASCII time indication max 32 characters...

Страница 82: ...32 characters Date time of the next ser vice e g firmware update To make changes to the maintenance information 1 From the Webserver main menu left select the Settings menu item The Device Configurati...

Страница 83: ...ick the Select file button A file selection dialog opens 4 Select the firmware container file FWUPDATE ZIP from this dialog The name of the selected firmware container file appears in the File field 5...

Страница 84: ...me Reset Application Pa rameters Application specific data port configuration and parameters remanent parame ters Reset All All Settings To reset the module to the factory settings proceed as follows...

Страница 85: ...are used Current version of the Bluetooth hardware used Chip identifier of the Bluetooth chip used Interface identifier of Bluetooth interface module Individual DM code of the product can be scanned b...

Страница 86: ...h Bluetooth if the product has an approval for the specific country or region To enable the Bluetooth interface you must have the WAGO I O Field app installed on the smartphone or tablet Proceed as fo...

Страница 87: ...oceed as follows to switch LED forcing externally controlled LED mode on Slide the LED forcing switch to the right LED forcing switches on The LED on the Bluetooth interface can now be externally cont...

Страница 88: ...out menu item changes back to Sign in Guest User Access By default the Webserver recognizes the user guest without a password this was set up for initial access or guest access Initial Login as Admin...

Страница 89: ...can be created in the second row Proceed as follows 1 In the Username field enter the username to use for the user Users that are al ready in use are not allowed here 2 In the Password field enter the...

Страница 90: ...ebserver you must be logged in there with operator or administrator rights To perform forcing pro ceed as follows 1 From the Webserver main menu left select the DIO Forcing menu item 2 Check the Forci...

Страница 91: ...forcing functionality through a forcing medium e g the WAGO I O Field Webserver it is locked for all other users of the module They cannot access the forcing functionality until the user that is acti...

Страница 92: ...it proceed as follows 1 Check the force box for the port in question 2 For this port you can enter 16 byte substitute values in hexadecimal format in the set value hexadecimal input fields of the colu...

Страница 93: ...The manual is available in the download area for the WAGO IO Link Configurator soft ware at www wago com item number 0765 4203 0100 0000 10 3 3 WAGO I O Field app 10 3 3 1 Parameterizing a Module wit...

Страница 94: ...ion node The path to this node is Root Object DeviceSet device name Table 61 Identify Devices Node Name Node Class Access Description Manufacturer Variable Read Device manufacturer ManufacturerUri Var...

Страница 95: ...teresis unit 0 1 C If the temperature exceeds the limiting value the temperature must fall back below the limiting value by the hysteresis to revoke the diagnosis UnderTemperature Variable Read 25 C L...

Страница 96: ...le Read Average voltage in supply cable 1 unit mV MeanVoltageL2 Variable Read Average voltage in supply cable 2 unit mV The OPC UA server provides nodes with measured values for each port and each ind...

Страница 97: ...n the MaxCur rentPin1 node The path to this node is Root Object DeviceSet device name IOLinkMaster PortXX Statistics Current Temperature Voltage The following table lists port specific statistical inf...

Страница 98: ...8 Product manual Version 1 0 0 4PORT IOL A FLD EC DC 24V 2 0A Node Name Node Class Access Description MinVoltagePin1 MinVoltagePin2 MinVoltagePin4 Variable Read Minimum voltage on pin 1 pin 2 or pin 4...

Страница 99: ...LED indicates the status of the system product Table 69 System Status LED Color State Description SYS system status Duo LED yellow green Green On System status OK Yellow On Firmware update is active O...

Страница 100: ...A host watchdog timeout has occurred Possible cause 2 Synchronization error the module switches automatically to Safe Operational Red Double flash Process data watchdog timeout A process data watchdo...

Страница 101: ...port X03 and 6 port X04 indicate the status of the IO Link Master or digital input output channel A LEDs 1 port X01 3 port X02 5 port X03 and 7 port X04 indicate the status of the digital input output...

Страница 102: ...an contain at most the number of diagnostic messages specified in subindex 1 Maximum Messages These can be retrieved starting with subindex 6 Subindex 0 indicates the highest subindex under which a di...

Страница 103: ...e too high Acknowledgment Mode Read 0 No diagnostic messages have been acknowledged so far Read 0 Subindex of last acknowledged diagnostic message 6 69 Writing 0 All acknowledged diagnostic messages a...

Страница 104: ...0 Error messages are stored in the diagnostic message queue 1 Error messages are not stored in the diagnostic message queue Bit 4 Mode selection for reaction to diagnostic history buffer overflow 0 O...

Страница 105: ...lated from this by read ing the current time stamp object 0x10F8 and calculating the age of the message Bits 5 7 Reserved Bits 8 15 Number of parameters in this diagnostic message Text ID UINT16 Text...

Страница 106: ...its 4 5 Type 0 reserved 1 notification 2 warning 3 error Bit 3 Source 0 device remote 1 master port Bits 0 2 Instance 0 unknown 1 3 reserved 4 application 5 7 reserved 11 2 1 9 Emergency Error Codes T...

Страница 107: ...oltage 0xFF01 Overvoltage Overvoltage in supply line 1L The supply line has exceeded the limiting value for the maximum voltage Check supply voltage 0xFF02 Overtempera ture Overtemperature The device...

Страница 108: ...d provides information on how to remedy faults Table 84 IO Link Master Events IO Link Event Code Description Remedy 0x17FF Process data error Check submodule configuration 0x1800 No device access loss...

Страница 109: ...onnected IO Link Device 0x1000 General malfunction IO Link device reports unknown error 0x4000 Temperature error Eliminate overload 0x4210 Device overheating Eliminate heat source 0x4220 Device underc...

Страница 110: ...ules Index Sub in dex Name Explanation Type Flag s Default 0xA000 Diagnostic Data Diagnostic Data of IO Link Port 1 RECORD 0 Highest supported subindex Highest supported subindex UINT8 RO 1 IO Link St...

Страница 111: ...WAGO I O Field Webserver 8 Resetsetting the Module to the Factory Settings 83 12 2 Updating Firmware The device s firmware can be updated Use the WAGO I O Field Webserver for this pur pose You need th...

Страница 112: ...ly disposal benefits health protects the environ ment from harmful substances in electrical and electronic equipment and enables sus tainable and efficient use of resources Observe national and local...

Страница 113: ...les These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate rad...

Страница 114: ...le in the IP67 housing serves the acquisition and output of data via sensors and actuators for the industrial control technology The integrated Blue tooth interface of the product allows the parameter...

Страница 115: ...droidTM is a trademark of Google LLC Apple the Apple logo iPhone iPad and iPod touch are registered trademarks of Apple Inc registered in the USA and other countries App Store is a service mark of App...

Страница 116: ...UA is a registered trademark of the OPC Foundation PROFIBUS is a registered trademark of the PROFIBUS Nutzerorganisation e V PNO PROFINET is a registered trademark of the PROFIBUS Nutzerorganisation...

Страница 117: ...ignment of the Digital Input 25 Table 21 Object 0x1A10 Assignment of the Digital Inputs 26 Table 22 Input Process Data port based assignment 26 Table 23 Input Process Data pin based assignment 26 Tabl...

Страница 118: ...Down Menu Selecting the Operating Mode for Pin 4 of the Selected IO Link Port 74 Table 53 IQ Behavior Drop Down Menu Configuration of Pin 2 I Q for IO Link Class A De vices 75 Table 54 Possible Value...

Страница 119: ...79 Flags for Controlling the Sending and Saving of Diagnostic Messages 104 Table 80 Structure of a Diagnostic Message in Subindexes 6 to 69 105 Table 81 Event Qualifier 106 Table 82 Emergency Error C...

Страница 120: ...13 Information Tab Port XX Menu Item 68 Figure 14 Information Tab Port XX Menu Item 69 Figure 15 Port XX Menu Item Status Tab 70 Figure 16 Port XX Menu Item Process Data Tab 72 Figure 17 Port XX Menu...

Страница 121: ...765 4203 0100 0000 List of Figures Product manual Version 1 0 0 121 4PORT IOL A FLD EC DC 24V 2 0A...

Страница 122: ...s catalogs videos and other WAGO media are subject to copyright Distribution or modification of the contents of these pages and videos is prohibited Furthermore the content may neither be copied nor m...

Отзывы: