765-4203/0100-0000
Planning
Product manual | Version: 1.0.0
45
4PORT IOL-A FLD EC DC 24V 2.0A
Figure 6: Power Supply Group with 765-4203/0100-0000 – Connection Example 2
To do so, we consider port X01 of the 765-4203/0100-0000 module:
This has a load of 5.2 A = 2 A + 2 A + 0.5 A + 0.5 A + 0.2 A on pin 1. This exceeds the
maximum load capacity of 4 A and it thus not permitted.
If the currents on X01 and X02 of the 765-1701/0200-0000 IO-Link Hub were increased,
the overload protection would constantly activate and could threaten destruction of the
765-4203/0100-0000 IO-Link Master on its port X01.
6.3 Settings Options
6.3.1 Module Parameters
Indexes 0x2000 to 0x2003
Parameters with indexes 0x2000 to 0x2003 configure the module.
Table 39: Module Parameters
Index Subindex
Parametername
Value Range
Default Description
0x2000.00
Force mode set-
ting
0: Force mode enable
0
The “Forcing” operating mode may be
used.
1: Force mode disable
The “Forcing” operating mode must
not be used.
0x2001.00
PD layout configu-
ration
0: port-based
0
Order of the process data of the digi-
tal inputs and digital outputs:
Bit 0 = port X01 pin 4, bit 1 = port X01
pin 2,
bit 2 = port X02 pin 4, bit 3 = port X02
pin 2, ...
1: pin-based
Order of the process data of the digi-
tal inputs and digital outputs:
Bit 0 = port X01 pin 4, Bit 1 = port X02
pin 4,
bit 2 = port X03 pin 4, bit 3 = port X04
pin 4,
...
bit 8 = port X01 pin 2, bit 9 = port X02
pin 2, ...