background image

86 

Value Script FW 2.20 (Standard) 

WAGO-TO-PASS® 761 

 

 

761-112 Telecontrol Module Compact, Web 

 

Manual 

 

Version 2.0.0  

  

10.2 

Value Script FW 2.31 (Extended) 

  

Due to extended functionalities, the value script has been extended to include a 
version designation ("01.01") as well as supply voltage, output values and GPS 
information. Furthermore the identity may also be up to 16 characters long. 

Table 35: Data format for value script FW 2.31 (extended) 

Index 

Variable 

Contents 

Format 

ID 

Identity 

Identity[16];Serial number[5] 

SV 

Value script version 

Version number[5] (currently “01.01”) 

PA 

Parameter 

Cycle time[4];Provider[5];Alarm counter[2] 

TI 

Date, time 

YY/MM/DD,hh:mm:ss; 

D1 

Digital input 1 

Value[1];Alarm[1] 

D2 

Digital input 2 

Value[1];Alarm[1] 

D3 

Digital input 3 

Value[1];Alarm[1] 

D4 

Digital input 4 

Value[1];Alarm[1] 

D5 

Digital input 5 

Value[1];Alarm[1] 

D6 

Digital input 6 

Value[1];Alarm[1] 

10 

D7 

Digital input 7 

Value[1];Alarm[1] 

11 

D8 

Digital input 8 

Value[1];Alarm[1] 

12 

A1 

Analog input 1 

Value[6];Unit[5];Alarm[1] 

13 

A2 

Analog input 2 

Value[6];Unit[5];Alarm[1] 

14 

A3 

Analog input 3 

Value[6];Unit[5];Alarm[1] 

15 

A4 

Analog input 4 

Value[6];Unit[5];Alarm[1] 

16 

A5 

Analog input 5 

Value[6];Unit[5];Alarm[1] 

17 

A6 

Analog input 6 

Value[6];Unit[5];Alarm[1] 

18 

A7 

Analog input 7 

Value[6];Unit[5];Alarm[1] 

19 

A8 

Analog input 8 

Value[6];Unit[5];Alarm[1] 

20 

Supply voltage 

Value[6];Unit[5];Alarm[1] 

21 

DO 

Digital outputs 

4 x Value[1] 

22 

AO 

Analog outputs 

2 x (Value[5];Unit[5];) 

23* 

US 

Unstructured string 

Data[40] 

24** 

PO 

GPS position 

String data[75] 

25** 

GI 

GPS information 

Deviation[5];8 x Flag[1]; 

26*** 

MA 

MODBUS alarm 

Value[2];Status[2];Alarm[1] 

27*** 

MV 

MODBUS variables 

64 x Value[4] 

This variable is sent only if a connection test is performed via the serial 
interface (SMS test). 

** 

This variable is sent only if the GPS functionality is available in the 

TO-

PASS

®

 telecontrol module.  

 ***  These variables are sent only if MODBUS is switched on. 

 

 

 

Alarm marker for the multiplex function 

When the multiplex function is used, the alarm markers for D1 to D4 are all '1' for 
a multiplex alarm. 

Содержание 761-112

Страница 1: ...Manual WAGO TO PASS 761 Telecontrol Module Compact Web 761 112 Telecontrol module for fault detection indication monitoring and remote control Version 2 0 0...

Страница 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fu...

Страница 3: ...n Source GPL 11 2 4 Block Rounding for GPRS Connections 11 2 5 Safety Advice Precautions 12 3 Device Description 15 3 1 Scope of Delivery 15 3 2 Use 15 3 3 View 17 3 4 Connectors 18 3 4 1 Antenna 18 3...

Страница 4: ...6 7 Configuring Inputs and Outputs 48 6 8 Digital Inputs 48 6 9 Multiplex Input 52 6 10 Multiplex Settings 53 6 10 1 1 Multiplex Alarm Text 54 6 10 2 Digital Outputs 55 6 11 Configuring Error Detector...

Страница 5: ...ample of Value Script FW 2 31 Extended 88 10 2 1 1 Value Script FW 2 33 Counter Inputs 89 10 2 1 2 Example of Value Script FW 2 33 Counter Inputs 91 10 2 2 Logger Script 92 10 2 2 1 Logger Script Stan...

Страница 6: ...ions are included if applicable 1 1 Validity of this Documentation This documentation is only applicable to the telecontrol module 761 112 Telecontrol Module Compact Web 1 2 Copyright This Manual incl...

Страница 7: ...tes a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not avoid...

Страница 8: ...s Documentation WAGO TO PASS 761 761 112 Telecontrol Module Compact Web Manual Version 2 0 0 Additional Information Refers to additional information which is not an integral part of this documentation...

Страница 9: ...ta files are marked in italic type e g C Programme WAGO I O CHECK Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from a me...

Страница 10: ...utomation The specialists must be familiar with the current norms and guidelines for the devices and automated environments All changes to the controller should always be carried out by qualified pers...

Страница 11: ...n Source GPL The TO PASS Compact telecontrol module firmware contains Open Source software under GPL According to Section 3b of GPL we offer you the source code You can obtain the source code with lic...

Страница 12: ...tion repair or maintenance work Installation only in appropriate housings cabinets or in electrical operation rooms TO PASS telecontrol modules are exposed operating equipment They may only be assembl...

Страница 13: ...nly qualified staff can install and maintain the TO PASS remote module and its antenna The transmitted must be off when working on or nearer to the antenna than specified below HF Exposition The exter...

Страница 14: ...an enclosure being resistant to the above mentioned materials Clean tools and materials are imperative for handling devices modules Cleaning only with permitted materials Clean soiled contacts using o...

Страница 15: ...e connection of signals from plants transmission preparation of values for the operator TO PASS telecontrol modules 761 112 may be used as fault indicator remote data request system permanent on line...

Страница 16: ...ion Standard Extended Extended Parameterizable Time request script Not implemented Not implemented Not implemented Implemented Counter inputs Not supported Not supported Not supported Supported Delay...

Страница 17: ...761 112 Telecontrol Module Compact Web Manual Version 2 0 0 3 3 View Figure 1 Front view Position Description 1 SIM Card insert 2 Antenna connection 3 Statusindication 4 PC interface 5 Connecting term...

Страница 18: ...ors 3 4 1 Antenna The screw connector SMA socket for the GSM antenna is located at the top of the housing Figure 2 Antenna connection Observe the maximum length of the antenna cable The total length o...

Страница 19: ...e LPS requirements per DIN EN 60950 1 Table 4 Terminal assignment for operating voltage Figure 3 Terminal assignment for operating voltage Connection Short name Designation 1 2 Uv Operating voltage DC...

Страница 20: ...nstructively no direct conduction connection between the cabinet frame or machine parts and the carrier rail Here the earth ground must be set up via an electrical conductor accordingly valid national...

Страница 21: ...achieve this connect the shield over a large surface area e g WAGO shield connecting system This is especially recommended for large scale systems where equalizing current or high impulse type current...

Страница 22: ...AGO Shield Connecting System The WAGO shield connecting system consists of shield clamping saddles busbars and various mounting carriers to enable a wide variety of setups For more information on this...

Страница 23: ...digital inputs Figure 5 Terminal assignment for digital inputs Connection Short name Designation 5 DI1 Digital input 1 6 DI2 Digital input 2 7 DI3 Digital input 3 8 DI4 Digital input 4 9 Not assigned...

Страница 24: ...nputs Table 7 Counter input pin assignments Figure 6 Counter input pin assignments Connection Short name Explanation 5 DI1 Counter input 1 configurable 6 DI2 Counter input 2 configurable 7 DI3 Counter...

Страница 25: ...voltages Only SELV PELV voltages shall be connected to the device terminals Table 8 Terminal assignment for digital outputs Figure 7 Terminal assignment for digital outputs Connection Short name Desig...

Страница 26: ...n Description 1 Not assigned 2 TXD 3 RXD 4 Not assigned 5 GND 6 Not assigned 7 Not assigned 8 Not assigned 9 Not assigned Table 10 PC interface cable assignment WAGO TO PASS PC D Sub 9 Pin Description...

Страница 27: ...is activated Initialization takes approx 40 s after system start up if everything is OK SMS GPRS processing Antenna is not connected the modem is searching for a network Poor GSM network the modem is...

Страница 28: ...4 sol Stripped length 9 mm 10 mm 3 6 2 Supply Table 13 Technical Data Supply Operating voltage 10 V 30 VDC Nominal voltage operation with mains power 24 VDC Nominal voltage operation using battery 12...

Страница 29: ...Number of inputs 4 Input type Type 3 acc to IEC 61131 2 Input voltage 0 V 30 V DC Signal voltage 0 0 V 5 V DC Signal voltage 1 7 V 30 V DC Input current max at 30 V DC 2 9 mA 3 6 6 Counter Inputs Tab...

Страница 30: ...per Article 3 2 RoHS Device complies with European RoHS directive FCC Verification per FCC 15b Approval Canada Approval Croatia Approval Mexico Approval Turkey 3 8 Standards and Guidelines 761 112 tel...

Страница 31: ...ambient temperature of 20 C to 70 C In the event of higher or lower temperatures proper cooling or heating arrangements must be provided Please contact WAGO Kontakttechnik GmbH Co K G for assistance T...

Страница 32: ...g the TO PASS telecontrol module from the DIN rail Figure 11 Removing the TO PASS telecontrol module from the DIN rail 1 Press the undersurface against the lower DIN rail edge until the TO PASS teleco...

Страница 33: ...connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals Terminate both solid and ferruled conductors without actuation by simply pushing them...

Страница 34: ...il The shield connection of the TO PASS telecontrol module shield terminal 38 must be connected to the DIN rail The DIN rail must have a low impedance ground see section Connections Ground 5 2 1 Digit...

Страница 35: ...PELV voltages Only SELV PELV voltages shall be connected to the device terminals Connect shielding Shielded cables are recommended for the counter inputs When using shielded cables the shield must be...

Страница 36: ...761 112 Telecontrol Module Compact Web Manual Version 2 0 0 5 2 3 Digital Outputs Only connect SELV PELV voltages Only SELV PELV voltages shall be connected to the device terminals Figure 14 Connectio...

Страница 37: ...using a double click 5 Select the CD drive in which you have placed the CD with the operating software 6 Start the WAGO TO PASS_SETUP 2 17 EXE program or a newer version in the main directory on the...

Страница 38: ...O PASS telecontrol module it must first be configured with the telephone number 1 Every TO PASS telecontrol module requires an SIM card for proper operation You can obtain an SIM card from any mobile...

Страница 39: ...IN button so that the TO PASS telecontrol module does not use the PIN code Also deactivate the PIN on the SIM card To do this insert the SIM card into a cell phone and under menu item Security select...

Страница 40: ...og ISDN Select the type of connection for communicating with the TO PASS telecontrol module RS 232 Direct connection via RS 232 cable GSM Dial up using GSM modem on the PC Analog Dial up using analog...

Страница 41: ...OM1 COMx Here select the serial interface where the communication cable is connected with a RS 232 connection Language English German French Select the langauge for the TO PASS operator interface here...

Страница 42: ...have set the type of connection for communicating with the TO PASS telecontrol module you are then able to read out the parameters of the connected module Select the menu option Edit Read Parameters T...

Страница 43: ...be configured from the project tree under it select the Identity option On the right side you will find the selection field for the function the display field for the name the input field for the tel...

Страница 44: ...nd enter the PIN number in the field provided Roaming Roaming is always activated in TO PASS telecontrol modules To select a favorite carrier click the Allow button and enter the 5 digit carrier ID in...

Страница 45: ...s are sent by the TO PASS telecontrol module as SMS however they can also be sent as an e mail fax or voice mail as defined in configuration The TO PASS telecontrol module can also transmit messages t...

Страница 46: ...address e g for a T Mobile SIM card 8000 receiver provider net Transmission as fax Follow the instructions from the provider for transmissions as fax messages For T Mobile or Vodafone for example ent...

Страница 47: ...r transmitting the data of the logger APN access In this field enter the APN access point Access Point Name for the SIM card provider e g T Mobile internet t mobile Vodafone web vodafone de The specif...

Страница 48: ...nputs Digital inputs 1 4 can be configured as counter inputs starting from Firmware Version FW 2 33 The counters count up or down from the given starting and end value With upward counting exceeding o...

Страница 49: ...the visualization system This function is available starting with Firmware Version FW 2 33 Starting value In this field enter the starting value for the counter This field is only active when the inp...

Страница 50: ...plications with GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the message when the digital input has been set or when the count...

Страница 51: ...th GPRS transmission Analog value Use these buttons to select up to four analog values which can also be transmitted with the deactivation message when the digital input has been reset or when the cou...

Страница 52: ...owing applies in this case DI1 20 1 DI2 21 2 DI3 22 4 and DI4 23 8 Thus for example if DI1 and DI3 are set then the binary number is 5 If only DI4 is set then the binary number is 8 In the multiplex t...

Страница 53: ...able Addresses Multiplex operation Click the button Use to enable disable multiplex operation for digital inputs DI1 DI4 If a status combination of digital inputs DI1 DI4 is fulfilled in multiplex ope...

Страница 54: ...ultiplex Input entry The input fields for the alarm texts pertaining to the 16 statuses are provided on the right side Figure 21 Configuring multiplex operation alarm texts Table 24 Configuring multip...

Страница 55: ...nects the DC voltage available at terminal 37 to the corresponding output Deactivation text In this field enter the deactivation text for the output When the TO PASS telecontrol module receives this t...

Страница 56: ...lation packet size Please note the information given on calculation packet size in the Section Important Information Rounding of Blocks for GPRS Links 6 11 1 Alarm Messages for Digital Inputs If on or...

Страница 57: ...elecontrol module waits for an acknowledgement after transmitting an alarm SMS Acknowledgement is in the form of an SMS containing the configured response text or a simple call by the recipient to the...

Страница 58: ...ct the TO PASS telecontrol module from the project tree using the identifier Select the entry Repeat times under the option Special Functions The input fields for the Web interval the Web outputs and...

Страница 59: ...function is available starting with Firmware Version FW 2 33 Switching input In this field select a digital input to be used for switching of the transmission interval between Web interval Off status...

Страница 60: ...imes of day Time adjustment must be performed for limited SMS transmission to check the day of the week and the active time The first SMS is transmitted when the starting value for the active time on...

Страница 61: ...nt Table 28 Setting the time adjustment Settings Time adjustment The TO PASS telecontrol module sends an SMS to itself and receives the current time from the provider transmitted by this SMS when the...

Страница 62: ...have adapted all parameters for the TO PASS telecontrol module to your requirements you have to write the parameters to the connected module Select the menu option Edit Write Parameters The software...

Страница 63: ...ol Module Compact Web Manual Version 2 0 0 6 13 1 Operation 6 14 Remote Query of Process Values The TO PASS telecontrol module offers two options for remote inquiry of the process values available Que...

Страница 64: ...ays the alarms that are still possible per hour The alarm counter only transmitted when enabled Alarm counter parameter in the Identifier dialog 0 If at least one digital input is configured as a coun...

Страница 65: ...Explanation 0 Digital input not configured as a counter e ZW Counter is active Counter value d ZW Counter is not active Counter value o ZW Counter overflow Counter vlaue r ZW Counter has been reset C...

Страница 66: ...lay the process values with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mo...

Страница 67: ...lues of the inputs and outputs The process values displayed are valid if the on line display is green Figure 26 Visualization of the process values Process values pertaining to inputs are displayed in...

Страница 68: ...process values click the Counter button possible only when inputs have been configured as counters The process values displayed are valid when the on line indicator is highlighted in green Figure 27...

Страница 69: ...ol Module Compact Web Manual Version 2 0 0 7 1 2 Telecontrol TO PASS telecontrol modules offer the option of influencing a process remotely with the help of their analog and digital outputs There are...

Страница 70: ...command with an SMS containing the identifier and the transmitted text Example Table 32 Example of parameters for Set DO Parameter Setting Activation text DOUT1 1 Deactivation text DOUT1 0 Turn off ti...

Страница 71: ...ble 33 Control commands for counters Control command Function Cx x 1 4 Select counter 1 4 E Activate counter D Deactivate counter R Reset counter n e g 500 Set counter value Control commands must be c...

Страница 72: ...lay the process values with the TO PASS operator program select the menu item Visualization Process values The program establishes a link to the TO PASS telecontrol modules selected Please note the mo...

Страница 73: ...ess values displayed are valid if the on line display is green Figure 28 Visualization of the process values Process values pertaining to inputs are displayed in the upper portion of the window and th...

Страница 74: ...ator is highlighted in green Figure 29 Counter process values The counter statuses are shown at the top of the window while the counter values the starting and end values and the limits are shown at t...

Страница 75: ...receive an acknowledgement SMS containing the identifier the response text and the alarm text Acknowledgement by phone call is based on the card being used Some data cards do not allow voice links me...

Страница 76: ...modules specifically to the respective ready state This takes place with simple changeover via SMS To do this just send an SMS with the text Standby1 to the TO PASS telecontrol modules The TO PASS te...

Страница 77: ...splayed Figure 30 Test inputs and outputs The process values of the inputs are displayed in the upper area and the process values of the outputs are displayed in the lower area By pressing the buttons...

Страница 78: ...nd values and the limits are shown at the bottom To start a counter click the button Activate To stop a counter click the button Deactivate To restore the counter to its starting value click the butto...

Страница 79: ...direct serial link to the TO PASS telecontrol module To test the connection select the menu option Edit Test SMS GPRS The following window is displayed Figure 32 Testing the connection Select the addr...

Страница 80: ...required The modem test may only be performed with a direct serial link to the TO PASS telecontrol module To test the mode select the menu item Modem Test The following window is displayed Figure 33...

Страница 81: ...rovider for APN access user name and password see also Section Parameter setting Addresses Under Special Functions select Repetition Time and set the WEB Interval for the cyclic transmission to the We...

Страница 82: ...he character 9 2 1 Example HTTP Request The HTTP request consists of both header and data string which are separated by an empty line CR LF Carriage Return Line Feed To improve readability line breaks...

Страница 83: ...ensions In the data set descriptions the maximum number of characters is indicated in square brackets Starting from Firmware Version 02 33 08 you can select the script version to be applied to data tr...

Страница 84: ...A1 Analog input 1 Value 6 Unit 5 Alarm 1 12 A2 Analog input 2 Value 6 Unit 5 Alarm 1 13 A3 Analog input 3 Value 6 Unit 5 Alarm 1 14 A4 Analog input 4 Value 6 Unit 5 Alarm 1 15 A5 Analog input 5 Value...

Страница 85: ...To improve readability line breaks have been inserted ID TO PASS 12345 PA 0000 home 99 TI 11 05 05 14 34 21 D1 1 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00...

Страница 86: ...1 Alarm 1 11 D8 Digital input 8 Value 1 Alarm 1 12 A1 Analog input 1 Value 6 Unit 5 Alarm 1 13 A2 Analog input 2 Value 6 Unit 5 Alarm 1 14 A3 Analog input 3 Value 6 Unit 5 Alarm 1 15 A4 Analog input 4...

Страница 87: ...viation is not enabled 1 Position deviation is enabled Flag 3 0 GPS receiver is turned off 1 GPS receiver is turned on Flag 4 0 No valid position available 1 Valid position available Flag 5 0 Static m...

Страница 88: ...been inserted ID TO PASS Ext 12345 SV 01 01 PA 0000 home 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5 00 0...

Страница 89: ...DO 0000 AO 000 0 04 00 mA C1 0 0 0 C2 r 20F5800 0 C3 r 0 0 C4 0 0 0 SQ 21 US Hello MA 00 00 0 MV 0026 0000 002E 0064 0026 0000 0054 0064 HT 1 value always 1 the device time has not been set TI entry i...

Страница 90: ...1 First value reached transgressed 2 Second value reached transgressed If both values are reached simultaneously only status 2 is transmitted SQ Signal quality or modem connection without formatting T...

Страница 91: ...000 home 99 TI 11 05 05 12 19 51 D1 0 0 D2 0 0 D3 0 0 D4 0 0 D5 0 0 D6 0 0 D7 0 0 D8 0 0 A1 00 00 mA 0 A2 00 00 mA 0 A3 00 00 mA 0 A4 00 00 mA 0 A5 00 00 mA 0 A6 00 00 mA 0 A7 00 00 mA 0 A8 00 00 mA 0...

Страница 92: ...econtrol Module Compact Web Manual Version 2 0 0 10 2 2 Logger Script Data transmission to the logger script is activated via cyclical transmission repetitions Web interval Data packet information con...

Страница 93: ...ta Set Byte 0 1 2 3 4 5 6 Bit 76543210765432107654321076543210765432107654321076543210 Cont PNNNNNNNSJJJJJMMMMDDDDDhhhhhmmmmmmssssssDIN AIN1 Byte 7 8 9 10 11 12 13 Bit 76543210765432107654321076543210...

Страница 94: ...ine breaks have been inserted ID TO PASS 12345 PA 0005 home 99 TI 11 05 05 14 36 11 LO 092D4AD100000000000000000000 562D4AD123000000000000000000 3F2D4AD12A000000000000000000 562D4AD1370000000000000000...

Страница 95: ...7 LPD2 2 GPS message 81 see LPDx variable data format table 8 LIO3 3 I O message 74 see LIOx variable data format table 9 LPD3 3 GPS message 81 see LPDx variable data format table 10 LIO4 4 I O messag...

Страница 96: ...put Value 3 10 7 analog input Value 3 11 8 analog input Value 3 12 Supply voltage Value 3 13 Digital output image Image 1 14 1 analog output Value 3 15 2 analog output Value 3 10 2 4 1 1 Data Format f...

Страница 97: ...000 000 000 000 000 B89 0 000 000 LPD3 C0 11 05 05 06 34 25 276 C41 2600 N 216 1621 E 0C 4D34 3 26A F 21 11 7 0 LIO4 001C 56 11 05 05 08 34 36 00 000 000 000 000 000 000 000 000 B83 0 000 000 LPD4 C0...

Страница 98: ...44 0x2C 2C Altitude in m 51 5 51 5 10 515 0x203 203 Position accuracy 2 2 Direction 309 35 309 x 60 35 18575 0x488F 488F Speed in km h 3 7 3 7 10 37 0x25 25 Speed in knots 2 0 2 0 10 20 0x14 14 Number...

Страница 99: ...ue 2nd input hexadecimal Value 8 4 Counter status 3rd input Status 1 5 Counter value 3rd input hexadecimal Value 8 6 Counter status 4th input Status 1 7 Counter value 4th input hexadecimal Value 8 The...

Страница 100: ...09 16 00 003 32E 7D5 7D9 7DA 7D8 7D6 7D5 AD0 0 000 32D LCD1 0 0 r 54600 r 0 0 0 LIO2 0001 11 00 01 01 00 09 52 00 CE3 32E 7D5 7D8 7DA 7D7 7D6 7D4 ACE 0 D04 32D LCD2 0 0 e 54600 d 0 0 0 LIO3 0002 78 0...

Страница 101: ...l Version 2 0 0 10 2 4 3 Time Request Script FW 2 33 If time adjustment is to take place via the Internet a time request script is transmitted on system start in order to adjust the time when a reply...

Страница 102: ...02 33 08 setpoint settings for digital and analog outputs and for changing the counters can be transmitted as replies Table 47 Setpoint settings Variable Contents Format AO1 1 analog output Normalized...

Страница 103: ...rver Apache CR LF Content length 31 CR LF Keep alive timeout 15 max 100 CR LF Connection Keep Alive CR LF Content type text html CR LF CR LF Values stored 08 09 19 13 22 23 The header depends on both...

Страница 104: ...ng example switching contact at counter input DI1 35 Figure 14 Connection example for a relay at DO1 output 36 Figure 15 General settings 40 Figure 16 Configuring the identity 43 Figure 17 Configuring...

Страница 105: ...ts 49 Table 23 Configuring multiplex operation settings 53 Table 24 Configuring multiplex operation alarm texts 54 Table 25 Configuring the digital outputs 55 Table 26 Configuring the acknowledgement...

Страница 106: ...106 List of Tables WAGO TO PASS 761 761 112 Telecontrol Module Compact Web Manual Version 2 0 0...

Страница 107: ...WAGO TO PASS 761 107 761 112 Telecontrol Module Compact Web Manual Version 2 0 0...

Страница 108: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastra e 27 D 32423 Minden Phone 49 5 71 8 87 0 Fax 49 5 71 8 87 1 69 E Mail info wago com Internet http www wago com...

Отзывы: