Process Image 45
753-1630 SMI Master Module 230 V AC
Manual
Version 1.2.0 FW/HW Version 02/01
The following responses to the SMI commands are possible via the process
image.
Table 22: Response to Request Commands
Response
Code
Designation
Description
0x0000
RES_ACK
Acknowledge was received from the
SMI master module
0x0001
RES_ERROR_NACK
Not Acknowledge was received from the
SMI master module
0x0002
RES_ERROR_LENGT
H
SMI master module has identified and
reported a length error
0x0003
RES_ERROR_TIMEOU
T
No response received
0x0004
RES_ERROR_ECHO
Echo of the SMI circuit was incorrect
0x0005
RES_ERROR_CHECKS
UM
SMI master module has identified a
checksum error
Pos: 85 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1