Figure 2: WRF06 Master and Configuration Module
One instance of the
FbWRF06
function block is required for each room operating
unit to be addressed. The Modbus
®
address of the required slave is set at the
“
bSlaveNo
” input. “1” for Modbus
®
slave one.
The data of the room operating unit to be addressed is read via this function block
and the input values of the unit can be changed from the controller.
Among other things, the data read includes the current temperature, room
occupancy and set points. The possible inputs in the room operating unit include
the information saved in the input register of the device.
Note
Input and output values
More information about the input and output registers is available in the
register description of Thermokon.