WAGO I/O SYSTEM 750 XTR
Device Description
23
750-601/040-000 Power Supply 24 VDC Fuse XTR
Manual
Version 2.0.0
3.6
Technical Data
3.6.1
Device Data
Table 8: Technical Data
– Device
Width
12 mm
Height (from upper edge of DIN-rail)
62.6 mm
Depth
100 mm
Weight
46.3 g
Degree of protection
IP20
3.6.2
Supply
Table 9: Technical Data
– Supply
Current consumption,
system voltage
max.
5 mA
Power Supply via CAGE CLAMP
®
connectors
under laboratory conditions
for ambient operating temperature
−40 °C … +55 °C
for ambient operating temperature
+55 °C … +70 °C
24 VDC (power supply via SELV/PELV
power supply unit)
18 V … 31,2 V (17,4 V … 31,2 V)
1)
18 V … 28,8 V (17,4 V … 28,8 V)
1)
18 V … 26,4 V (17,4 V … 26,4 V)
1)
Voltage via power jumper contacts
24 VDC
Current
max.
via power jumper contacts
6.3 A
Rated surge voltage
1 kV
Fuse
5 x 20 mm; T 6.3 A (not included)
Notice: Use UL-recognized fuses only!
1)
including residual ripple of 15%
3.6.3
Connection Type
Table 10: Technical Data
– Field Wiring
Wire connection
CAGE CLAMP
®
Cross section
0.25
mm² … 2.5 mm² / AWG 24 … 14
Stripped lengths
8 mm
… 9 mm / 0.33 in
Table 11: Technical Data
– Power Jumper Contacts
Power jumper contacts
Spring contact, self-cleaning, hard gold
plated