750-559(/xxx-xxx) [4 AO DC 0-10 V] • 11
Process Image
WAGO-I/O-SYSTEM 750
I/O Modules
More Information
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)
or in the internet under:
!
Documentation
!
WAGO-I/O-SYSTEM 750
!
System Description
2.1.1.7 Process
Image
The analog output module 750-559 transmits 16-bit data and 8 status bits per
channel.
The digitalized output value is transmitted in a data word (16 bits) as output
byte 0 (low) and output byte 1 (high) via the process image of the coupler/
controller.
This value is represented with a 12 bit resolution on bit B3 ... B14.
The three least significant bits (B0 ... B2) are not parsed.
Some fieldbus systems can process the status information using by means of a
status byte.
As the returned status byte of this output module is always zero, it will not be
parsed.
2.1.1.7.1 Standard
Format
For the standard module 750-559, the numerical values ranging from 0x0000
to 0x7FFF are scaled on the output current ranging from 0 V to 10 V.
Process values of module 750-559
numerical value
Output
value
binary
status
byte
0 V - 10 V
output value
hex.
dec.
hex.
0.00 '0000.0000.0000.0000'
0x0000
0
0x00
1.25 '0001.0000.0000.0000'
0x1000
4096
0x00
2.50 '0010.0000.0000.0000'
0x2000
8192
0x00
3.75 '0011.0000.0000.0000'
0x3000
12288
0x00
5.00 '0100.0000.0000.0000'
0x4000
16384
0x00
6.25 '0101.0000.0000.0000'
0x5000
20480
0x00
7.50 '0110.0000.0000.0000'
0x6000
24576
0x00
8.75 '0111.0000.0000.0000'
0x7000
28672
0x00
10.00 '0111.1111.1111.1111'
0x7FFF
32767
0x00