WAGO-I/O-SYSTEM 750
Use in Hazardous Environments
45
750-539 4DO 24V DC VALVE Ex i
Manual
Version 1.0.1
7.2.1
Special Conditions for Safe Use
(TÜV 14 ATEX 148929 X)
1.
The modules of the WAGO-I/O-SYSTEM 750-*** have to been erected in
such a way, that corresponding to EN 60079-15 a degree of protection of at
least IP 54 according to EN 60529 is achieved.
2.
Measures have to been taken, external to the modules, to provide a transient
protection that ensures that the rated voltage, connected to the power supply
terminals, is not exceeded by more than 40 %.
3.
The connecting and disconnecting of the non-intrinsically safe circuits is
only permitted if no explosive atmosphere exists. This although applies for
the all switches, interfaces (Fieldbus, Ethernet, Serial) and the SD-card.
4.
The ambient temperature range is: 0 °C ≤ T
amb
≤ +60 °C
The ambient temperature range for modules with suffix extension /025-****
is: -20 °C ≤ T
amb
≤ +60 °C