![WAGO 750-532 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/wago/750-532/750-532_manual_3224520007.webp)
750-532 [4 DO DC 24 V 0,5 A, High-Side Switching, Diagnostics]
•
7
View
WAGO-I/O-SYSTEM 750
I/O Modules
2 I/O Modules
2.1 Digital Output Modules
2.1.1 750-532 [4 DO DC 24 V 0,5 A, High-Side Switching, Diagnostics]
4 Channel Digital Output Module DC 24 V 0,5 A,
2-conductor, short-circuit-protected; high-side switching, diagnostics
2.1.1.1 View
A1 A2
13 14
750-532
A3 A4
A5 A6
A7 A8
DO 1
DO 3
0 V
DO 4
Datenkontakte
Leistungskontakte
0 V
DO 2
Status
Diagnose
DO 1 … DO 4
Fig. 2.1.1-1: 4 Channel Digital Output Module 750-532
g053200e
2.1.1.2 Description
The connected load is switched via the digital output from the control system.
These output modules can recognize a short circuit to ground, a line break and
an overload in either channel.
The module has four output channels. Four 2-conductor actuators may be
directly connected to the module.
The actuators can be connected using connection DO 1 or DO 2, DO 3, DO 4
and 0 V.
The connection of 3-conductor actuators to this module requires a field side
connection module (750-603 or 750-614) for 24 V supply.
Note
For the connection of inductive loads a protected circuit, e. g. a recovery
diode, has to be switched parallel to this load.
The output channels are electrically short-circuit-protected and high-side
switching. Which means that the status of the output channels is "high" if the
output channels switch to the 24 V supply voltage for the field side.