WAGO 750-532 Скачать руководство пользователя страница 10

10 

 • 

750-532 [4 DO DC 24 V 0,5 A, High-Side Switching, Diagnostics] 

 Technical 

Data

 

  

WAGO-I/O-SYSTEM 

750 

  

I/O 

Modules 

2.1.1.5 Technical 

Data 

Module specific Data 

Number of outputs 

Current consumption (internal)

max.

 10 

mA 

Voltage via power jumper contacts 

DC 24 V (-25 % ... +30%) 

Type of load 

resistive, inductive, lamps 

Switching rate 

max.

 

2 kHz  

Reverse voltage protection 

Yes 

Output current 

0,5 A, short-circuit-protected 

Short-circuit limitation 

typ. Pwm

 6 

Diagnostics 

open circuit, overload and short circuit 

Open-circuit detection 
in the switched off status 

< 0.9 mA 

typ. 

at 24 V 

(> 2.0 mA -> no open circuit operation) 

Energy dissipation W

max.

 

(unique switching off) 

0.125 J 
L

max. 

 2 W

max.

 /I² 

Isolation 

500 V (System/Field) 

Current consumption 

typ.

(field side) 

13 mA (per module) + load 

Internal bit width 

4 Bit Out, 4 Bit In (Diag) 

Dimensions (mm) W x H x L 

12 x 64* x 100 
* from upper edge of 35 DIN rail 

Weight 

ca. 50 g 

Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual) 

EMC-Immunity to interference (CE) 

acc. to EN 61000-6-2 (01) 

EMC-Emission of interference (CE) 

acc. to EN 61000-6-3 (01) 

Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual) 

 

C

UL

US

 (UL508) 

 

 

Conformity Marking 

 

 

 

More Information

 

Detailed references to the approvals are listed in the document "Overview 
Approvals WAGO-I/O-SYSTEM 750", which you can find on the CD ROM 
ELECTRONICC Tools and Docs (Item-No.: 0888-0412)  
or in the internet under: 

www.wago.com

 

!

 Documentation 

!

 WAGO-I/O-SYSTEM 750 

!

 

System Description 

 

Содержание 750-532

Страница 1: ...Fieldbus Independent I O Modules 4 DO DC 24 V 0 5 A High Side Switching Diagnostics 750 532 Manual Version 1 0 1 ...

Страница 2: ...0 571 8 87 5 55 Fax 49 0 571 8 87 85 55 E Mail support wago com Every conceivable measure has been taken to ensure the correctness and com pleteness of this documentation However as errors can never be fully ex cluded we would appreciate any information or ideas at any time E Mail documentation wago com We wish to point out that the software and hardware terms as well as the trademarks of companie...

Страница 3: ...n 4 1 1 3 Intended Use 4 1 2 Symbols 5 1 3 Number Notation 5 1 4 Safety Notes 6 1 5 Scope 6 2 I O Modules 7 2 1 Digital Output Modules 7 2 1 1 750 532 4 DO DC 24 V 0 5 A High Side Switching Diagnostics 7 2 1 1 1 View 7 2 1 1 2 Description 7 2 1 1 3 Display Elements 9 2 1 1 4 Schematic Diagram 9 2 1 1 5 Technical Data 10 2 1 1 6 Process Image 11 ...

Страница 4: ...nufacturers are always named without referring to patent rights The existence of such rights can therefore not be ruled out 1 1 2 Personnel Qualification The use of the product detailed in this manual is exclusively geared to specialists having qualifications in PLC programming electrical specialists or persons instructed by electrical specialists who are also familiar with the valid standards WAG...

Страница 5: ...ration ESD Electrostatic Discharge Warning of damage to the components by electrostatic discharge Observe the precautionary measure for handling components at risk Note Routines or advice for efficient use of the device and software optimization More information References on additional literature manuals data sheets and INTERNET pages 1 3 Number Notation Number Code Example Note Decimal 100 norma...

Страница 6: ...s to be regarded Do not use any contact spray The spray may impair the functioning of the contact area The WAGO I O SYSTEM 750 and its components are an open system It must only be assembled in housings cabinets or in electrical operation rooms Access must only be given via a key or tool to authorized qualified personnel The relevant valid and applicable standards and guidelines concerning the ins...

Страница 7: ...t from the control system These output modules can recognize a short circuit to ground a line break and an overload in either channel The module has four output channels Four 2 conductor actuators may be directly connected to the module The actuators can be connected using connection DO 1 or DO 2 DO 3 DO 4 and 0 V The connection of 3 conductor actuators to this module requires a field side connect...

Страница 8: ... LED goes off An optocoupler is used for electrical isolation between the bus and the field side Any configuration of the output modules is possible when designing the fieldbus node Grouping of module types is not necessary The field side supply voltage of 24 V for the output module is derived from adjacent I O modules or from a supply module The supply voltage for the field side is made automatic...

Страница 9: ...on off off on on off green DO 3 on off on off on off on off on off red 3 DIA 3 off off off on on off off on on off green DO 4 on off on off on off on off on off red 4 DIA 4 off off off on on off off on on off 13 14 DO 2 DIA 2 DIA 4 DO 1 DIA 1 DIA 3 DO 3 DO 4 Fig 2 1 1 2 Display Elements g053202x Status from PLC to the module 1 0 1 0 1 0 1 0 1 0 The full diagnostic is only possible provided that th...

Страница 10: ...unique switching off 0 125 J Lmax 2 Wmax I Isolation 500 V System Field Current consumption typ field side 13 mA per module load Internal bit width 4 Bit Out 4 Bit In Diag Dimensions mm W x H x L 12 x 64 x 100 from upper edge of 35 DIN rail Weight ca 50 g Standards and Regulations cf Chapter 2 2 of the Coupler Controller Manual EMC Immunity to interference CE acc to EN 61000 6 2 01 EMC Emission of...

Страница 11: ...controls DO 4 Channel 4 controls DO 3 Channel 3 controls DO 2 Channel 2 controls DO 1 Channel 1 The input bits show the state of the outputs Input bit B3 B2 B1 B0 Meaning Diagnostics DO 4 Channel 4 Diagnostics DO 3 Channel 3 Diagnostics DO 2 Channel 2 Diagnostics DO 1 Channel 1 Diagnostic bit DO 0 Normal operation output DO 1 4 follows the output bit Diagnostic bit DO 1 Open Circuit Short Circuit ...

Страница 12: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 05 71 8 87 0 Fax 05 71 8 87 1 69 E Mail info wago com Internet http www wago com ...

Отзывы: