WAGO-I/O-SYSTEM 750
Device Description
13
750-515 4DO 250V AC 2.0A/ Relais 4NO/ Potential Free
Manual
Version 1.0.1
Pos: 17 /All e Seri en (Allgemei ne Module)/Ü berschriften/N eue Ü berschriften/Ebene 1Ger ätebeschrei bung - Ü berschrift 1 @ 3\mod_1233756084656_21.docx @ 27096 @ 1 @ 1
3
Device Description
Pos: 18.1.1 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/Anwendung/D O/Anwendung 750- 05xx DO Rel ais @ 5\mod_1246611276875_21.docx @ 36561 @ @ 1
The 750-515 Digital Output Module transmits binary control signals from the
automation device to the connected actuators (e.g., solenoid valves, contactors,
transmitters, relays or other electrical loads).
Pos: 18.1.2 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/DO/I/O-Beschrei bung 750-0515 4 D O-Rel ais @ 24\mod_1448445391669_21.docx @ 196247 @ @ 1
The I/O module has 4 output channels, providing for direct connection of
actuators equipment with protection classes II and III.
The actuators can be wired to the CAGE CLAMP
®
connectors directly. An
external potential of 250 VAC can be applied to relay contacts 13, 23, 33 and 43.
Pos: 18.1.3 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/Allgemein/Ver weis auf Kapi tel " Anschlüsse" @ 8\mod_1276775378035_21.docx @ 57956 @ @ 1
The assignment of the connections is described in the “Connectors” section.
Pos: 18.1.4 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/Allgemein/Ver weis auf Kapi tel " Geräte anschli eß en" > "Anschlussbeispi el(e)" @ 5\mod_1246015203281_21.docx @ 36298 @ @ 1
Connection examples are shown in section “Connecting Devices” > … >
“Connection Example(s)”.
Pos: 18.1.5 /Serie 750 (WAGO-I/O-SYST EM)/Wichtige Erläuterungen/Sicherheits- und sonstige Hinweise/Achtung/Achtung: D O Induktionsspannungsbegrenzung R elais @ 5\mod_1247031985231_21.docx @ 36766 @ @ 1
Inductive loads must be dampened!
For the protection of relay coils and contacts, inductive loads must be dampened
with an effective protection circuit!
Examples of protection circuits can be seen in the section “Protective Circuits for
Contacts of Relay Modules”.
Pos: 18.1.6 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/DO/I/O-Beschrei bung 750-0515 @ 24\mod_1448445577335_21.docx @ 196250 @ @ 1
The I/O module contains 1 contact relay per channel. The contact relays are
potential free, i.e., only the connection points for the relay contacts are available
at the field side so that different voltages can be applied independently to all 4
make contacts.
The floating contacts also enable, for example, series connection of all 4 relays or
series connection of several relays when the I/O modules are set up in blocks.
Pos: 18.1.7 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/I/O-Beschrei bung/DO/I/O-Beschrei bung 750-05xx Ansteuerung der R el ais (Interne Systemspannung) @ 5\mod_1246861676649_21.docx @ 36599 @ @ 1
The internal system voltage is used to trigger the relays.
Pos: 18.1.8 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/LED-Anzeige/LED Zustand R elais @ 5\mod_1246862048946_21.docx @ 36603 @ @ 1
The switching status of the two relays is indicated via green status LEDs.
Pos: 18.1.9 /Serie 750 (WAGO-I/O-SYST EM)/Gerätebeschrei bung/Ei nlei tung/LED-Anzeige/Ver weis auf Kapitel "Anzeigeelemente" @ 5\mod_1246010525000_21.docx @ 36194 @ @ 1
The meaning of the LEDs is described in the “Display Elements” section.
Pos: 18.1.10 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Versorgung/Anordnung unter Ber ücksichtigung der Leistungskontakte beliebig @ 3\mod_1233756233468_21.docx @ 27099 @ @ 1
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node. An arrangement
in groups within the group of potentials is not necessary.
Pos: 18.1.11 /Serie 750 ( WAGO-I/O- SYST EM)/Wichtig e Erl äuter ung en/Sicher hei ts- und sonstige Hi nweise/Hinweis/Hi nweis: Potential einspeiseklemme für Erde einsetzen! (keine LK für Er de) @ 3\mod_1226499037468_21.docx @ 25023 @ @ 1
Use supply modules for ground (earth)!
The I/O module has no power jumper contacts for receiving and transmitting the
earth potential. Use a supply module when an earth potential is needed for the
subsequent I/O modules.
Pos: 18.1.12 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Einsatzbereich/Einsatzbereich 750- xxxx alle Koppler/C ontroll er ohne Ei nschränkung @ 3\mod_1232541691906_21.docx @ 26522 @ @ 1