![WAGO 750-508/040-000 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/wago/750-508-040-000/750-508-040-000_manual_3215025052.webp)
52
Use in Hazardous Environments
WAGO-I/O-SYSTEM 750 XTR
750-508/040-000 2DO 24 VDC 2A/ Diagn XTR
Manual
Version 1.3.0
Figure 23: Text Detail
– Marking Example for Approved Ex i I/O Module According to NEC 505
Table 29: Description of Marking Example for Approved Ex i I/O Module According to NEC 505
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
Figure 24: Text Detail
– Marking Example for Approved Ex i I/O Module According to NEC 506
Table 30: Description of Marking Example for Approved Ex i I/O Modules According to NEC 506
Marking
Description
CI I,
Explosion protection group
Zn 2
Area of application
AEx
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)