Device Description 25
750-506 2DO 24V DC 0.5A/ diagnostics
Manual
Version 1.2.1
Public
Pos: 45.1 /All e Seri en ( Allgemei ne Module)/Ü berschriften/Ebene 3/Anschlusstechni k - Ü berschrift 3 @ 17\mod_1380123271324_21.docx @ 132788 @ 3 @ 1
3.5.5
Connection Type
Pos: 45.2 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/Technische Daten/Anschl usstechni k/T echnische D aten Verdrahtungsebene CC - 0,08 bis 2,5mm2 @ 17\mod_1380121238809_21.docx @ 132780 @ @ 1
Table 12: Technical Data – Field Wiring
Connection technology
CAGE CLAMP
®
Conductor cross-section
0.08 mm² … 2.5 mm², AWG 28 … 14
Strip length
8 mm … 9 mm / 0.33 in
Pos: 45.3 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/Technische Daten/Anschl usstechni k/T echnische D aten Leistungskontakte (Messer/F eder) @ 19\mod_1400241643293_21.docx @ 153921 @ @ 1
Table 13: Technical Data – Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning
Pos: 45.4 /Serie 750 (WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/Technische Daten/Anschl usstechni k/T echnische D aten D atenkontakte @ 17\mod_1380123495844_21.docx @ 132794 @ @ 1
Table 14: Technical Data – Data Contacts
Data contacts
Slide contact, hard gold plated, self-
cleaning
Pos: 46 /Serie 750 ( WAGO I/O SYSTEM)/Ger ätebeschrei bung (al te Str uktur)/T echnische Daten/Klimatische U mgebungsbedi ngung en/Technische Daten Klimat. U mgebungsbed. ohne er w. T emp. 0...55°C /-25...+85°C (>2000m auf Anfr age) @ 5\mod_1247657968368_21.docx @ 37603 @ 3 @ 1
3.5.6
Climatic Environmental Conditions
Table 15: Technical Data – Climatic Environmental Conditions
Surrounding air temperature, operation 0 °C … 55 °C
Surrounding air temperature, storage
−25
°C … +85 °C
Operating altitude
0 … 2000 m;
(> 2000 m upon request)
Relative humidity
Max. 5 % … 95 % without condensation
Pollution degree
2
Protection type
IP20
Resistance to harmful substances
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
Maximum pollutant concentration at
relative humidity < 75 %
SO
2
≤
25 ppm
H
2
S
≤
10 ppm
Special conditions
Ensure that additional measures for
components are taken, which are used
in an environment involving:
– dust, caustic vapors or gases
– ionizing radiation
Pos: 47 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1