WAGO-I/O-SYSTEM 750 XTR
Appendix 291
750-495/040-00x 3-Phase Power Measurement Module 690 V
Manual
Version 1.2.0
Table 71: Register 36
Register 36 – Undervoltage Limit Phase 1
Function
Data Type Access
Factory Setting
Undervoltage limit, phase 1,
Resolution: 0.1 V
UINT
R/W
0x0000 (0 V)
0:
The undervoltage limit check is deactivated.
≥
1:
Value of the undervoltage limit.
Table 72: Register 37
Register 37 – Undervoltage Limit Phase 2
Function
Data Type Access
Factory Setting
Undervoltage limit, phase 2,
Resolution: 0.1 V
UINT
R/W
0x0000 (0 V)
0:
The undervoltage limit check is deactivated.
≥
1:
Value of the undervoltage limit.
Table 73: Register 38
Register 38 – Undervoltage Limit Phase 3
Function
Data Type Access
Factory Setting
Undervoltage limit, phase 3,
Resolution: 0.1 V
UINT
R/W
0x0000 (0 V)
0:
The undervoltage limit check is deactivated.
≥
1:
Value of the undervoltage limit.
Table 74: Register 39
Register 39 – Current Transformer Ratio Phase 1
Function
Data Type Access
Factory Setting
Divisor for the current transformer ratio, phase 1,
Activation via register 32, bit 12 required
UINT
R/W
0x0001
0:
-not permitted-
≥
1:
Value for the current transformer ratio divisor.
Table 75: Register 40
Register 40 – Current Transformer Ratio Phase 2
Function
Data Type Access
Factory Setting
Divisor for the current transformer ratio, phase 2,
Activation via register 32, bit 13 required
UINT
R/W
0x0001
0:
-not permitted-
≥
1:
Value for the current transformer ratio divisor.