Table 23: Process Image at Configuration for Ni120
Temperature
°C
Numerical value
1)
Status
byte
hex.
LED
Error
AI 1, AI 2
binary
hex.
dec.
<
−
80.0
'1000.0000.0000.0001' 0x8001
−
32767
0x41
On
−
80.0
'1111.1100.1110.0000' 0xFCE0
−
800
0x00
Off
−
50.0
'1111.1110.0000.1100' 0xFE0C
−
500
0x00
Off
0.0
'0000.0000.0000.0000' 0x0000
0
0x00
Off
50.0
'0000.0001.1111.0100' 0x01F4
500
0x00
Off
100.0
'0000.0011.1110.1000' 0x03E8
1000
0x00
Off
150.0
'0000.0101.1101.1100' 0x05DC
1500
0x00
Off
200.0
'0000.0111.1101.0000' 0x07D0
2000
0x00
Off
250.0
'0000.1001.1100.0100' 0x09C4
2500
0x00
Off
300.0
'0000.1011.1011.1000' 0x0BB8
3000
0x00
Off
320.0
'0000.1100.1000.0000' 0x0C80
3200
0x00
Off
> 320.0
'0010.0001.0011.0100' 0x2134
8500
0x42
On
Broken wire
against RL
'0010.0001.0011.0100' 0x2134
8500
0x42
On
1)
Temperature values below 0 °C are represented in two’s complement binary form.
The measured value can exceed the range from –800 to +3200 until the limitation
applies.