20 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-1606/040-000 Potential Distribution 16*0V XTR
Manual
Version 1.3.0
3.6
Technical Data
3.6.1
Device Data
Table 6: Technical Data – Device
Width
12 mm
Height (from upper edge of DIN-rail)
62 mm
Depth
100 mm
Weight
39.3 g
Degree of protection
IP20
3.6.2
Supply
Table 7: Technical Data – Supply
Voltage via power jumper contacts
under laboratory conditions
for ambient operating temperature
−
40 °C … +55 °C
for ambient operating temperature
+55 °C … +70 °C
24 VDC (power supply via SELV/PELV
power supply unit)
18 V … 31.2 V (17.4 V … 31.2 V)
1)
18 V … 28.8 V (17.4 V … 28.8 V)
1)
18 V … 26.4 V (17.4 V … 26.4 V)
1)
Current via power jumper contacts
max
10 A
Potential connections
16 x 0 VDC
Rated surge voltage
1 kV
1)
including residual ripple of 15 %
3.6.3
Connection Type
Table 8: Technical Data – Field Wiring
Wire connection
Push-in CAGE CLAMP
®
Cross section
0.25 mm² … 1.5 mm² / AWG 24 … 16
Stripped lengths
8 mm … 9 mm / 0.33 in
Table 9: Technical Data – Power Jumper Contacts
Power jumper contacts
Blade/spring contact, self-cleaning, hard
gold plated
Table 10: Technical Data – Data Contacts
Data contacts
Slide contact, self-cleaning, hard gold
plated