WAGO-I/O-SYSTEM 750 XTR
Device Description 19
750-1405/040-000 16DI 24VDC 3ms XTR
Manual
Version 1.3.0
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos: 18.14 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1
Pos: 18.15 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung (alte Struktur)/Anschl üsse/Push-in CAGE CLAMP®-Anschlüsse - Ü berschrift 3 @ 15\mod_1370519905692_21.docx @ 122018 @ 3 @ 1
3.2.3
Push-in CAGE CLAMP
®
Connectors
Pos: 18.16 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung (alte Struktur)/Anschl üsse/D I/Anschl üsse 750-140x 16 D I Push-in CAGE CLAMP @ 3\mod_1232518694593_21.docx @ 26470 @ @ 1
Figure 4: Push-in CAGE CLAMP
®
Connectors
Table 5: Legend for Figure “Push-in CAGE CLAMP
®
Connectors”
Channel Designation Connector Function
1
DI 1
1
Input DI 1: Signal voltage
2
DI 2
2
Input DI 2: Signal voltage
.
.
.
15
DI 15
15
Input DI 15: Signal voltage
16
DI 16
16
Input DI 16: Signal voltage