WAGO-I/O-SYSTEM 750 XTR
Use in Hazardous Environments 63
750-563/040-000 2AO 0/4-20mA/ 6-18V DC/ 16Bit /XTR
Manual
Version 1.3.0
Figure 28: Text Detail – Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Table 44: Description of Marking Example for Approved Ex i I/O Modules According to CEC 18
attachment J
Marking
Description
Dust
Ex
Explosion protection mark
nA
Type of protection
[ia IIIC]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 20
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use
Gases
Ex
Explosion protection mark
nA
Type of protection
[ia Ga]
Type of protection and equipment protection
level (EPL): Associated apparatus with intrinsic
safety circuits for use in Zone 0
IIC
Group
T4
Temperature class
Gc
Equipment protection level (EPL)
X
Symbol used to denote specific conditions of use