Manual 

WAGO I/O SYSTEM 750 XTR 

 

 

 

750-481/040-000  

2AI RTD Ex i XTR 

2-Channel Analog Input; Resistance Measurement; 

Intrinsically Safe; Extreme 

Version 1.1.0  

 

 

 

Содержание 2AI RTD Ex i XTR

Страница 1: ...Manual WAGO I O SYSTEM 750 XTR 750 481 040 000 2AI RTD Ex i XTR 2 Channel Analog Input Resistance Measurement Intrinsically Safe Extreme Version 1 1 0 ...

Страница 2: ... 45 55 E Mail support wago com Every conceivable measure has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreciate any information or suggestions for improving the documentation E Mail documentation wago com We wish to point out that the software and hardware terms as well as the trademarks of companies used and ...

Страница 3: ... 3 Device Description 14 3 1 View 16 3 2 Connectors 17 3 2 1 Data Contacts Local Bus 17 3 2 2 Power Jumper Contacts Field Supply 18 3 2 3 CAGE CLAMP Connectors 19 3 3 Display Elements 20 3 4 Operating Elements 20 3 5 Schematic Diagram 21 3 6 Technical Data 22 3 6 1 Device Data 22 3 6 2 Power Supply 22 3 6 3 Inputs 22 3 6 4 Explosion Protection 23 3 6 5 Communication 23 3 6 6 Connection Type 24 3 6...

Страница 4: ...the United States of America NEC and Canada CEC 57 7 2 Installation Regulations 60 7 2 1 Special Notes including Explosion Protection 60 7 2 2 Special Notes Regarding ANSI ISA Ex 62 8 Appendix 63 8 1 Configuration and Parameterization using a GSD File with PROFIBUS DP and PROFINET IO 63 8 1 1 2AI RTD Ex i Configuration 63 8 1 1 1 PROFIBUS DP Fieldbus Couplers Controllers 750 333 0xx 000 750 833 0x...

Страница 5: ... manual for the used fieldbus coupler controller Consider power layout of the WAGO I O SYSTEM 750 XTR In addition to these operating instructions you will also need the system description Design Notes XTR Guidelines and Recommendations for Increasing Operational Safety and the manual for the used fieldbus coupler controller which can be downloaded at www wago com There you can obtain important inf...

Страница 6: ...ates a moderate risk potentially hazardous situation which if not avoided could result in death or serious injury Personal Injury Indicates a low risk potentially hazardous situation which if not avoided may result in minor or moderate injury Damage to Property Indicates a potentially hazardous situation which if not avoided may result in damage to property Damage to Property Caused by Electrostat...

Страница 7: ...t Conventions Font Type Indicates italic Names of paths and data files are marked in italic type e g C Program Files WAGO Software Menu Menu items are marked in bold letters e g Save A greater than sign between two names means the selection of a menu item from a menu e g File New Input Designation of input or optional fields are marked in bold letters e g Start of measurement range Value Input or ...

Страница 8: ...l changes to the coupler or controller should always be carried out by qualified personnel with sufficient skills in PLC programming 2 1 3 Use of the 750 Series in Compliance with Underlying Provisions Fieldbus couplers controllers and I O modules found in the modular WAGO I O SYSTEM 750 receive digital and analog signals from sensors and transmit them to actuators or higher level control systems ...

Страница 9: ...ser The following actions will result in the exclusion of liability on the part of WAGO Kontakttechnik GmbH Co KG Repairs Changes to the hardware or software that are not described in the operating instructions Improper use of the components Further details are given in the contractual agreements Please send your request for modified and new hardware or software configurations directly to WAGO Kon...

Страница 10: ...rical and electronic equipment can be harmful to the environment and human health 2 1 4 1 2 Packaging Packaging contains materials that can be reused PPWD 94 62 EU and 2004 12 EU packaging guidelines apply throughout Europe Directives and laws may vary nationally Environmentally friendly disposal of the packaging protects the environment and allows sustainable and efficient use of resources Observ...

Страница 11: ...protection against UV irradiation Guarantee mechanical stability Restrict access to authorized personnel and may only be opened with tools Ensure disconnect and overcurrent protection The device is intended for installation in automation technology systems Disconnect protection is not integrated Connected systems must be protected by a fuse Provide suitable disconnect and overcurrent protection on...

Страница 12: ...s having seeping and insulating properties The components are not resistant to materials having seeping and insulating properties such as aerosols silicones and triglycerides found in some hand creams If you cannot exclude that such materials will appear in the component environment then install the components in an enclosure being resistant to the above mentioned materials Clean tools and materia...

Страница 13: ...se ensure that environmental factors personnel work space and packaging are properly grounded Use only direct current DC for insulation testing Both the system voltage and field voltage side are capacitively coupled to the DIN rail If an I O module is mounted on the DIN rail application of an AC voltage between the DIN rail and at least one of these two potentials can lead to the destruction of th...

Страница 14: ...YSTEM 750 fieldbus couplers controllers and I O modules is only to be done in zone 2 or in non hazardous environments To fulfill Ex i regulations only passive transducers that means without their own voltage supply like adjustable resistances pressure flow and level meters may be connected to the input module The transducers are directly supplied from the I O module The module has two input channe...

Страница 15: ...wered by SELV PELV power supplies The operating status of the channels is indicated by a green status LED per channel A red error LED per channel indicates a wire break a short circuit or that the signal is outside the measuring range The meaning of the LEDs is described in the Display Elements section Any configuration of the I O module is possible within an intrinsically safe segment when config...

Страница 16: ... Figure View Pos Description Details See Section 1 Marking possibility with Mini WSB 2 Status LEDs Device Description Display Elements 3 Data contacts Device Description Connectors 4 CAGE CLAMP connectors Device Description Connectors 5 Power jumper contacts Device Description Connectors 6 Release tab Mounting Inserting and Removing Devices ...

Страница 17: ... are available as self cleaning gold spring contacts Figure 2 Data Contacts Do not place the I O modules on the gold spring contacts Do not place the I O modules on the gold spring contacts in order to avoid soiling or scratching Pay attention to potential equalization from the environment The devices are equipped with electronic components that may be destroyed by electrostatic discharge When han...

Страница 18: ...esigned as blade contacts and those on the right side as spring contacts Figure 3 Power Jumper Contacts Table 4 Legend for Figure Power Jumper Contacts Contact Type Function 1 Spring contact Potential transmission Uv for field supply 2 Spring contact Potential transmission 0 V for field supply 3 Blade contact Potential feed in 0 V for field supply 4 Blade contact Potential feed in Uv for field sup...

Страница 19: ...nsor RL R1 4 left Input AI 1 Sensor R 2 R2 5 left Input AI 2 Sensor R RL2 7 left Input AI 2 Sensor RL R2 8 left Input AI 2 Sensor R S 4 right Common shield connection of input S 8 right Use shielded signal lines Only use shielded signal lines for analog signals and I O modules which are equipped with shield clamps Only then can you ensure that the accuracy and interference immunity specified for t...

Страница 20: ...tional readiness and trouble free local bus communication Error AI 1 B Off Normal operation Red Overrange underflow of the admissible measuring range broken wire short circuit 2 Status AI 2 E Off No operational readiness or the local bus communication is interrupted Green Operational readiness and trouble free local bus communication Error AI 2 F Off Normal operation Red Overrange underflow of the...

Страница 21: ...WAGO I O SYSTEM 750 XTR Device Description 21 750 481 040 000 2AI RTD Ex i XTR Manual Version 1 1 0 3 5 Schematic Diagram Figure 6 Schematic Diagram ...

Страница 22: ...supply 25 mA Power consumption Pmax 0 45 W Power loss Pl 0 45 W Isolation 300 VAC system supply Current via power jumper contacts max 1000 mA 3 6 3 Inputs Table 9 Technical Data Inputs Number of inputs 2 Signal type Resistance thermometer Pt100 Pt200 Pt500 Pt1000 Ni100 Ni120 Ni1000 Resistances 1 2 kΩ 5 kΩ Potentiometer setting 0 100 1 2 kΩ 5 kΩ Sensor connection 2 conductors 3 conductors Temperatu...

Страница 23: ...out taking into account the concurrence LO CO Ex ia IIC 100 mH 13 5 µF Ex ia IIB 100 mH 240 µF Ex ia IIA 100 mH 1000 µF Ex ia I 100 mH 1000 µF Reactances with taking into account the concurrence LO CO Ex ia IIC 100 mH 1 µF 20 mH 1 2 µF 1 mH 1 9 µF 0 1 mH 3 4 µF 0 001 mH 13 5 µF Ex ia IIB 100 mH 4 9 µF 20 mH 6 µF 1 mH 11 µF 0 1 mH 20 µF 0 001 mH 240 µF Ex ia IIA 100 mH 7 2 µF 20 mH 8 6 µF 1 mH 15 µ...

Страница 24: ...l Data Climatic Environmental Conditions Surrounding air temperature operation 40 C 70 C Surrounding air temperature storage 40 C 85 C Relative humidity 95 Elevation above sea level without temperature derating with temperature derating max 0 m 2000 m 2000 m 5000 m 0 5 K per 100 m 5000 m Resistance to harmful substances Acc to IEC 60068 2 42 and IEC 60068 2 43 Maximum pollutant concentration at re...

Страница 25: ... 750 481 040 000 Conformity marking CULUS UL61010 2 201 Korea Certification The following Ex approvals have been granted for the I O module 750 481 040 000 TÜV 17 ATEX 196484 X I M1 Ex ia Ma I II 3 1 G Ex ec ia Ga IIC T4 Gc II 1 D Ex ia Da IIIC IECEx TUN 17 0005X Ex ia Ma I Ex ec IIC T4 Gc Ex ec ia Ga IIC T4 Gc Ex ia Da IIIC CULUS UL 12 12 01 for Use in Hazardous Locations ...

Страница 26: ... following shipbuilding approvals are pending for the I O module 750 481 040 000 ABS American Bureau of Shipping DNV GL Temperature D cold testing at 40 C 16 h Relative humidity B Vibration B vibration testing at acceleration 5 0g EMC B Housing A LR Lloyd s Register Env 1 2 3 4 PRS Polski Rejestr Statków ...

Страница 27: ...2012 A11 2013 Group II electrical equipment Equipment requirements in the types of protection EN 60079 7 2015 Electrical equipment in e type of protection with ec level of protection EN 60079 11 2012 Equipment protection by intrinsic safety i IECEx Certificates of Conformity General Requirements IEC 60079 0 ed 6 Group II electrical equipment Equipment requirements in the types of protection EC 600...

Страница 28: ...s 1000 shocks per axis and direction half sine 25g 6 ms 1000 shocks per axis and direction half sine Environmental Requirements EN 61850 3 Achieved EN 60721 3 1 1K5 except precipitation and ice formation EN 60721 3 3 3K7 except wind driven precipitation water and ice formation EN 60870 2 2 C3 except wind driven precipitation and ice formation Shipbuilding Mechanical Climatic Environmental Conditio...

Страница 29: ...5 EN 60255 26 1 kV conductor conductor 2 kV conductor ground Conducted Disturbances Induced by High frequency Fields EN 61000 4 6 EN 60255 26 10 V 150 kHz 80 MHz Magnetic Fields With Electrical Frequencies EN 61000 4 8 EN 60255 26 300 A m continuous 1000 A m for 1 s Damped Oscillatory Magnetic Fields EN 61000 4 10 100 A m Voltage Dips Short term Interruptions and Voltage Fluctuations EN 61000 4 11...

Страница 30: ...Oscillatory Waves EN 61000 4 18 EN 60255 26 IEEE C37 90 1 1 25 kV conductor conductor 2 5 kV conductor ground Voltage Dips Short term Interruptions and Voltage Fluctuations to DC Supply Inputs EN 61000 4 29 EN 60255 26 Standard not applicable Harmonics Shipbuilding Standard not applicable The list of ship certifications issued is available in the section Approvals ...

Страница 31: ...dB µV m AV 3 GHz 6 GHz Shipbuilding Class B 80 dB µV m 50 dB µV m QP 150 kHz 300 kHz 50 dB µV m 34 dB µV m QP 0 3 MHz 30 MHz 54 dB µV m QP 30 MHz 2 GHz 24 dB µV m QP 156 MHz 165 MHz Shipbuilding Class A 80 dB µV m 50 dB µV m QP 150 kHz 30 MHz 60 dB µV m 54 dB µV m QP 30 MHz 100 MHz 54 dB µV m QP 100 MHz 2 GHz 24 dB µV m QP 156 MHz 165 MHz Conducted Emission of Interference Line Connection AC Volta...

Страница 32: ...Conducted Emission of Interference Line Connection DC Voltage EN 61000 6 3 EN 60255 26 EN 55032 Class A 79 dB µV QP 0 15 MHz 0 5 MHz 66 dB µV AV 0 15 MHz 0 5 MHz 73 dB µV QP 0 5 MHz 30 MHz 60 dB µV AV 0 5 MHz 30 MHz QP Quasi Peak Detector AV Average Detector If necessary please find different data in the section Approval regarding approval for EMC A or EMC B ...

Страница 33: ...he fieldbus coupler controller is optional which means that accessing or parsing the status information depends on the fieldbus system The input module 750 481 040 000 transmits 16 bit measured values and 8 optional status bits per channel 4 1 Configuration for Pt Resistance Sensors To evaluate the platinum resistance sensors the measured values of the resistance are converted and sent as temperat...

Страница 34: ...0000 0000 0000 0000 0x0000 0 0x00 Off 100 0 0000 0011 1110 1000 0x03E8 1000 0x00 Off 200 0 0000 0111 1101 0000 0x07D0 2000 0x00 Off 500 0 0001 0011 1000 1000 0x1388 5000 0x00 Off 750 0 0001 1101 0100 1100 0x1D4C 7500 0x00 Off 800 0 0001 1111 0100 0000 0x1F40 8000 0x00 Off 850 0 0010 0001 0011 0100 0x2134 8500 0x00 Off 850 0 0010 0001 0011 0100 0x2134 8500 0x42 On Broken wire against RL 0010 0001 0...

Страница 35: ...mperature values below 0 C are represented in two s complement binary form Table 22 Process Image at Configuration for Ni100 and Ni1000 Temperature C Numerical value 1 Status byte hex LED Error AI 1 AI 2 binary hex dec 60 0 1000 0000 0000 0001 0x8001 32767 0x41 On 60 0 1111 1101 1010 1000 0xFDA8 600 0x00 Off 50 0 1111 1110 0000 1100 0xFE0C 500 0x00 Off 0 0 0000 0000 0000 0000 0x0000 0 0x00 Off 50 ...

Страница 36: ...Off 50 0 0000 0001 1111 0100 0x01F4 500 0x00 Off 100 0 0000 0011 1110 1000 0x03E8 1000 0x00 Off 150 0 0000 0101 1101 1100 0x05DC 1500 0x00 Off 200 0 0000 0111 1101 0000 0x07D0 2000 0x00 Off 250 0 0000 1001 1100 0100 0x09C4 2500 0x00 Off 300 0 0000 1011 1011 1000 0x0BB8 3000 0x00 Off 320 0 0000 1100 1000 0000 0x0C80 3200 0x00 Off 320 0 0010 0001 0011 0100 0x2134 8500 0x42 On Broken wire against RL ...

Страница 37: ...ff 750 0001 1101 0100 1100 0x1D4C 7500 0x00 Off 1000 0010 0111 0001 0000 0x2710 10000 0x00 Off 1200 0010 1110 1110 0000 0x2EE0 12000 0x00 Off approx 1200 0010 0001 0011 0100 0x2134 8500 0x42 On Values marked with approx are not calibrated In the measuring range from 10 Ω to 5 0 kΩ the resolution is 1 digit per 0 5 Ω Table 25 Process Image Configuration for Measuring Range 10 Ω 5 kΩ Resistance Ω Nu...

Страница 38: ...nt is determined by the total resistance RG of the potentiometer If RG is measured with 16 bit resolution using RG 200 Ω in the measuring range of 5 0 kΩ the increment is given by 04 0 200 65536 0 5 100 Ω Ω k d Table 26 Process Image at Configuration for Potentiometer Measuring Percentage Numerical value Status byte hex LED Error AI 1 AI2 binary hex dec 0 0 0000 0000 0000 0000 0x0000 0 0x00 Off 20...

Страница 39: ...cts The blade contacts are sharp edged Handle the I O module carefully to prevent injury Do not touch the blade contacts Requirements for Clearances and Creepage Distances For all sections of a node that contain I O modules for Ex i use stricter require ments with regard to clearances and creepage distances apply Before such a node section the respective Power supply 24 VDC Diagn for Ex i XTR Modu...

Страница 40: ...s end module at all fieldbus nodes with the WAGO I O SYSTEM 750 XTR fieldbus couplers controllers to guarantee proper data transfer For vibration loads 4g observe the following installation instructions Use pan head screws or blind rivets at least every 60 mm 12 mm pin spacing to secure the DIN rail Make the open conductor length between strain relief and wire connection as short as possible Use t...

Страница 41: ...en devices are energized High voltage can cause electric shock or burns Switch off all power to the device prior to performing any installation repair or maintenance work Temperature range applies to normal operation XTR I O modules may be operated below 20 C but not wired and or reconnected 5 2 1 Inserting the I O Module 1 Position the I O module so that the tongue and groove joints to the fieldb...

Страница 42: ...e snapped in place the electrical connections for the data contacts and power jumper contacts if any to the fieldbus coupler controller or to the previous or possibly subsequent I O module are established 5 2 2 Removing the I O Module 1 Remove the I O module from the assembly by pulling the release tab Figure 9 Removing the I O Module Example Electrical connections for data or power jumper contact...

Страница 43: ...ch CAGE CLAMP Do not connect more than one conductor at one single connection If more than one conductor must be routed to one connection these must be connected in an up circuit wiring assembly for example using WAGO feed through terminals 1 For opening the CAGE CLAMP insert the actuating tool into the opening above the connection 2 Insert the conductor into the corresponding connection opening 3...

Страница 44: ...quired Do not exceed maximum current via power contacts The maximum current available from the Power Supply 24 VDC Diagn for Ex i XTR Modules 750 606 040 000 is 1 A When configuring the system ensure that this current is not exceeded If exceeded an additional 750 606 040 000 must be used Keep the air and creep distances between intrinsically safe segments The maximum current available from the 750...

Страница 45: ...nt I O modules via the power contacts designed as spring contacts Figure 11 Ex i XTR Power Supply Concept Table 27 Legend for Figure Ex i XTR Power Supply Concept Pos Explanation 1 XTR fieldbus coupler controller 2 XTR I O modules 3 XTR supply Power Supply 24 VDC Diagn for Ex i XTR Modules 750 606 040 000 4 I O modules Ex i XTR 5 XTR end module 750 600 040 000 UF1 Field supply 1 24 VDC US System s...

Страница 46: ... Categories Table 28 Legend for Figure Overvoltage Categories Pos Explanation 1 XTR fieldbus coupler controller 2 XTR filter module 3 XTR supply module Power Supply 24 VDC Diagn for Ex i XTR Modules 750 606 040 000 4 I O modules Ex i XTR 5 XTR end module Overvoltage categories and rated surge voltage see EN 61010 2 201 ...

Страница 47: ...ation field side power supply filters 750 624 040 001 Field Supply Filter 24 VDC HI NC XTR or power supply filters 750 626 040 000 Supply Filter 24 VDC HI XTR are generally to be used for XTR I O module groups Table 29 Filter Modules for 24V Power Supply Item No Designation Description 750 626 040 000 Power supply filter System and field supply with filtering 24 V 0 V 750 624 040 001 Field side po...

Страница 48: ...igure 13 Power Supply Concept Example 1 Table 30 Legend for Figure Power Supply Concept Example 1 Pos Explanation 1 XTR fieldbus coupler controller 2 XTR filter module 750 626 040 000 3 XTR supply Power Supply 24 VDC Diagn for Ex i XTR Modules 750 606 040 000 4 I O modules Ex i XTR 5 XTR end module ...

Страница 49: ...pt Example 2 Table 31 Legend for Figure Power Supply Concept Example 2 Pos Explanation 1 XTR fieldbus coupler controller 2 XTR filter module 750 626 040 000 3 XTR filter module 750 626 040 000 or 750 624 040 001 4 XTR supply 750 606 040 000 Power Supply 24 VDC Diagn for Ex i XTR Modules 5 I O modules Ex i XTR 6 XTR end module ...

Страница 50: ...O SYSTEM 750 XTR 750 481 040 000 2AI RTD Ex i XTR Manual Version 1 1 0 6 3 Connection Examples 6 3 1 2 RTD 2 Conductors Figure 15 Example Connection 2 RTD 2 Wire 6 3 2 2 RTD 3 Conductors Figure 16 Example Connection 2 RTD 3 Wire ...

Страница 51: ...STEM 750 XTR Connect Devices 51 750 481 040 000 2AI RTD Ex i XTR Manual Version 1 1 0 6 3 3 2 Resistance Figure 17 Example Connection 2 Resistance 6 3 4 2 Potentiometer Figure 18 Example Connection 2 Potentiometer ...

Страница 52: ...rdous areas and shall be used in accordance with the marking and installation regulations The following sections include both the general identification of components devices and the installation regulations to be observed The individual subsections of the Installation Regulations section must be taken into account if the I O module has the required approval or is subject to the range of applicati...

Страница 53: ...50 481 040 000 2AI RTD Ex i XTR Manual Version 1 1 0 7 1 Marking Configuration Examples 7 1 1 Marking for Europe According to ATEX and IECEx Figure 19 Marking Example According to ATEX and IECEx Figure 20 Text Detail Marking Example According to ATEX and IECEx ...

Страница 54: ...osion group of dust T135 C Max surface temperature of the enclosure without a dust layer Dc Equipment protection level EPL Mining I Equipment group Mining M2 Category High level of protection Ex Explosion protection mark d Type of protection Flameproof enclosure I Explosion group for electrical equipment for mines susceptible to firedamp Mb Equipment protection level EPL Gases II Equipment group A...

Страница 55: ...vironments 55 750 481 040 000 2AI RTD Ex i XTR Manual Version 1 1 0 Figure 21 Marking Example for Approved Ex i I O Module According to ATEX and IECEx Figure 22 Text Detail Marking Example for Approved Ex i I O Module According to ATEX and IECEx ...

Страница 56: ...layer Dc Equipment protection level EPL Mining I Equipment Group Mining M2 M1 Category High level of protection with electrical circuits which present a very high level of protection Ex Explosion protection mark d Type of protection Flameproof enclosure ia Ma Type of protection and equipment protection level EPL Associated apparatus with intrinsic safety electrical circuits I Explosion group for e...

Страница 57: ... of America NEC and Canada CEC Figure 23 Marking Example According to NEC Figure 24 Text Detail Marking Example According to NEC 500 Table 34 Description of Marking Example According to NEC 500 Marking Description CL I Explosion protection gas group DIV 2 Area of application Grp A B C D Explosion group gas group op temp code T4 Temperature class ...

Страница 58: ...otection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equipment protection level EPL Figure 26 Text Detail Marking Example for Approved Ex i I O Module According to NEC 506 Table 36 Description of Marking Example for Approved Ex i I O Modules According to NEC 506 Marking Description CI I Explosion protection group Zn 2 Area of a...

Страница 59: ...A Type of protection ia IIIC Type of protection and equipment protection level EPL Associated apparatus with intrinsic safety circuits for use in Zone 20 IIC Group T4 Temperature class Gc Equipment protection level EPL X Symbol used to denote specific conditions of use Gases Ex Explosion protection mark nA Type of protection ia Ga Type of protection and equipment protection level EPL Associated ap...

Страница 60: ...hen replacing components The product is an open system As such the product must only be installed in appropriate enclosures or electrical operation rooms to which the following applies Can only be opened using a tool or key Inside pollution degree 1 or 2 In operation internal air temperature within the range of 0 C Ta 55 C or 20 C Ta 60 C for components with extension number 025 xxx or 40 C Ta 70 ...

Страница 61: ...ticular Operating DIP switches coding switches or potentiometers Replacing fuses Wiring connecting or disconnecting of non intrinsically safe circuits is only permitted in the following cases The circuit is disconnected from the power supply The area is known to be non hazardous Outside the device suitable measures must be taken so that the rated voltage is not exceeded by more than 40 due to tran...

Страница 62: ...one networks or telecommunication cables WARNING The radio receiver module 750 642 may only be used to connect to external antenna 758 910 WARNING Product components with fuses must not be fitted into circuits subject to overloads These include e g motor circuits WARNING When installing I O module 750 538 Control Drawing No 750538 in the manual must be strictly observed Additional Information Proo...

Страница 63: ...rite a parameterization made with the GSD file the I O module operates with the WAGO I O CHECK settings until the 750 333 040 000 Fieldbus Couplers are restarted After restart the I O module is re parameterized via PROFIBUS using the GSD settings 8 1 1 2AI RTD Ex i Configuration 8 1 1 1 PROFIBUS DP Fieldbus Couplers Controllers 750 333 0xx 000 750 833 0xx 000 When using the aforementioned PROFIBUS...

Страница 64: ...ation GSD Entry PI Length Byte Data Type Inst Module Sub Module I O 750 481 0 000 2AI RTD INT16 2 I 4 n a INT16 2 UINT8 INT16 2 I O 6 6 UINT8 INT16 8 1 2 2AI RTD Ex i Parameterization The I O module can be supplied with all operating parameters when selecting the module entry in the GSD file on the PROFIBUS DP and PROFINET IO fieldbus devices Figure 28 Example of a Parameter Assignment Dialog for ...

Страница 65: ...WAGO I O SYSTEM 750 XTR Appendix 65 750 481 040 000 2AI RTD Ex i XTR Manual Version 1 1 0 Figure 29 Example of a Parameter Assignment Dialog for PROFINET IO Fieldbus Couplers ...

Страница 66: ...eter Value WAGO I O CHECK GSD File PB DP PN IO Sensor type RTD Pt100 RTD Ni100 RTD Pt1000 RTD Pt500 RTD Pt200 RTD Ni1000 RTD Ni120 POT 5k POT 1k2 R 5k R 1k2 Connection type 3 conductors 2 conductors PI diagnostics enabled disabled Watchdog enabled disabled Number format Two s complement Amount sign Filter constant 25 Hz 640 ms 50 Hz 320 ms 60 Hz 270 ms 100 Hz 160 ms 200 Hz 80 ms 400 Hz 40 ms 1000 ...

Страница 67: ...e Channel Parameters Parameter Value Explanation Diagnostics Channel x x 0 1 The fieldbus coupler controller signals a diagnosis if one of the following events External error Measurement range underflow Line break are reported by at least one I O module channel 0 lock Diagnostics reported by the I O module do not lead to the signaling of a diagnosis by the fieldbus coupler controller 1 release Dia...

Страница 68: ...y 1 true Provided that the channel diagnostics of the respective signal channel has been activated an external error leads to transmission of a diagnostic alarm and entry in the diagnostics database of the station proxy Diagnostics Measurement range underflow Channel x x 0 1 0 false An Measurement range underflow on the respective signal channel does not lead to transmission of a diagnostic alarm ...

Страница 69: ...2 Resistance 51 Figure 18 Example Connection 2 Potentiometer 51 Figure 19 Marking Example According to ATEX and IECEx 53 Figure 20 Text Detail Marking Example According to ATEX and IECEx 53 Figure 21 Marking Example for Approved Ex i I O Module According to ATEX and IECEx 55 Figure 22 Text Detail Marking Example for Approved Ex i I O Module According to ATEX and IECEx 55 Figure 23 Marking Example ...

Страница 70: ... 34 Table 22 Process Image at Configuration for Ni100 and Ni1000 35 Table 23 Process Image at Configuration for Ni120 36 Table 24 Process Image at Configuration for Measuring Range 10 Ω 1 2 kΩ 37 Table 25 Process Image Configuration for Measuring Range 10 Ω 5 kΩ 37 Table 26 Process Image at Configuration for Potentiometer Measuring 38 Table 27 Legend for Figure Ex i XTR Power Supply Concept 45 Tab...

Страница 71: ...WAGO I O SYSTEM 750 XTR List of Tables 71 750 481 040 000 2AI RTD Ex i XTR Manual Version 1 1 0 Table 41 General Module Channel Parameters 67 Table 42 General Module Channel Parameters 68 ...

Страница 72: ...WAGO Kontakttechnik GmbH Co KG Postfach 2880 D 32385 Minden Hansastraße 27 D 32423 Minden Phone 49 571 887 0 Fax 49 571 887 844169 E Mail info wago com Internet www wago com ...