2787-2154
Properties
Product manual | Version: 1.0.2
27
Power Supply Pro 2
Table 37: Legend for “Standards: EMC – Immunity to Interference (Tests Performed)”
Category
Description
A
Normal operation within specification limits
B
Temporary degradation of function that is self-recoverable after interference
C
Temporary loss of function that requires operator intervention or system reset
Table 38: Standards: EMC – Emission of Interference (Tests Performed)
Standard
Title
Test
Value
EN 55016-2-1
Part 2-1: Methods of measurement
of disturbances and immunity – Con-
ducted disturbance measurements
(CISPR 16-2-1)
Conducted distur-
bance
AC input
Class B (residential area) at nom-
inal load
Conducted distur-
bance
DC output
Class B (residential area) at nom-
inal load
EN 55016-2-3
Part 2-3: Methods of measurement
of disturbances and immunity – Ra-
diated disturbance measurements
(CISPR 16-2-3)
Housing interference
radiation
Class B (residential area) at nom-
inal load
EN 61000-3-2
Part 3-2: Limits – Limits for harmonic
current emissions (equipment input
current ≤ 16 A per phase)
Upper harmonic in-
put currents
Class A fulfilled at nominal load
3.10.4 Special Requirements
Observe the following:
• Perform installation according to the local conditions, applicable regulations (e.g., VDE
0100), national accident prevention specifications (e.g., UVV-VBG4 or DGUV Regula-
tion 2) and accepted technical regulations.
• This product is intended for installation in electrical systems or machines and fulfills the
requirements of the Low Voltage Directive.
When installing in machines, the following also applies:
• When installing in machines, normal operation must not commence until it is deter-
mined that the machine complies with the requirements of the Machinery Directive, EN
60204.
• Commencement of normal operation is allowed only on the condition of compliance
with the EMC Directive.
• The manufacturer of the system or machine is responsible for ensuring compliance
with the limit values required by EMC legislation.