background image

2787-2144

Notes on Operation

Product manual | Version: 1.0.0

57

Power Supply Pro 2

10.5.4 “Electronic Circuit Breaker” Mode

In this mode, a specified trip current and trip delay can be set via the 

8

 

WAGO Interface

Configuration software [

}

 42]

 or a connected 

8

 

communication module [

}

 62]

. If the

output current exceeds the trip current setting, a specified amount of time elapses. If the
output current is still higher than the trip current setting after the trip delay corresponding
to the setting, the output is switched off. To switch the output back on, manual interven-
tion is necessary. The following options are available for this:
• Communication interface
• Buttons
• Digital input

t

I

ECB

t

ECB

t

0

t

1

<100ms

I

OUT

/ I

N

Figure 39: “Electronic Circuit Breaker” Mode

10.5.5 “Latching Shutdown on Thermal Overload” Mode

In this mode, the output voltage is switched off in the event of excessive internal device
temperature. A corresponding “High Device Temperature” warning can, for example, be
transmitted via the 

8

 

WAGO Interface Configuration software [

}

 42]

 or passed to a

higher-level controller via a connected 

8

 

communication module [

}

 62]

. To switch the

output back on, manual intervention is necessary. The following options are available for
this:
• Communication interface
• Buttons
• Digital input

10.5.6 “Power Boost” mode

This mode can be used in combination with the following modes:

8

 

“Constant Current” Mode [

}

 55]

8

 

“Constant Current with Latching Shutdown” Mode [

}

 56]

8

 

“Electronic Circuit Breaker” Mode [

}

 57]

In this mode, output current equal to 150 % of the nominal output current is permitted for
5 seconds. The output is then switched off. To switch the output back on, manual inter-
vention is necessary. The following options are available for this:
• Communication interface

Содержание 2787-2144

Страница 1: ...Product manual Version 1 0 0 Power Supplies Power Supply Pro 2 2787 2144...

Страница 2: ...has been taken to ensure the accuracy and completeness of this documentation However as errors can never be fully excluded we always appreci ate any information or suggestions for improving the docum...

Страница 3: ...pe label 13 3 4 Label 14 3 5 Connections 14 3 5 1 Connectors 14 3 5 2 Input 15 3 5 3 Output 15 3 5 4 Signal 16 3 6 Indicators 16 3 7 Control elements 17 3 7 1 Buttons 17 3 8 Communication interface 17...

Страница 4: ...Menu Bar 42 9 3 1 1 Backstage Tab 42 9 3 1 2 Device Tab 42 9 3 1 2 1 Dialog Settings 42 9 3 2 Main Menu 49 9 3 3 Display Section 49 9 3 3 1 Display Section Measurements 49 9 3 3 2 Display Section Meas...

Страница 5: ...oduct manual Version 1 0 0 v Power Supply Pro 2 10 6 Maintenance 59 11 Decommissioning 60 11 1 Disposal and Recycling 60 12 Appendix 61 12 1 Application Notes 61 12 1 1 AC Operation 61 12 2 Accessorie...

Страница 6: ...uct is an open system and is designed for installation in a additional enclosure This product fulfills the requirements of protection type IP20 and is designed for use in dry indoor spaces Operation o...

Страница 7: ...cal regulations and accepted technology standards and practices applicable at the time of installation and the instruc tions in the products Instructions for use must be complied with 1 2 Typographica...

Страница 8: ...st slight injury Action step to reduce risk NOTICE Type and source of malfunction property damage only Possible malfunctions that may restrict the product s scope of functions or ergonomics but do not...

Страница 9: ...state of the art at the time the documentation was created and are not subject to updating service The installer and operator bear sole responsibility to ensure they are complied with in their current...

Страница 10: ...d practices applicable at the time of installation 2 2 Electrical Safety High voltage can cause electric shock or burns Disconnect all power sources from the product before performing any installation...

Страница 11: ...opened with tools Ensure the required pollution degree in the vicinity of the system Offer adequate protection against direct or indirect contact Offer adequate protection against UV irradiation Prev...

Страница 12: ...ither via the WAGO USB configuration cable or via an attached communication module It is also possible to record and evaluate various output parameters via the WAGO Interface Con figuration software w...

Страница 13: ...pply Unit Pro 2 2787 2144 PS PH 24VDC A U Pro 2 1 5 IN OUT Ambient Temp Derating www wago com 2787 2144 Class I Equipment Indoor Use Only IP20 Technical Data WAGO Kontakttechnik GmbH Co KG Hansastr 27...

Страница 14: ...re Label Position Comment Details 1 2D data matrix code Contains the information from positions 2 5 2 Key number Fixed information 37S 3 ID number per D U N S Fixed information WAGO Minden 4 WAGO item...

Страница 15: ...put voltage 4 Test slot Series 721 Series see section 8 Accessories 62 Connection technology CAGE CLAMP 3 5 3 Output 1 2 3 4 5 6 Figure 5 Output X2 Connection Table 8 Legend for Figure Output X2 Conne...

Страница 16: ...Ds These LEDs indicate operating states and 8 Diagnostics 36 100 75 50 25 DC OK Figure 7 Optical Status Indicator Table 12 Indication of Operating States General Indicator Product is in Standby Mode L...

Страница 17: ...to make settings 3 8 Communication interface The communication interface is covered with a cap Remove this cap to use the commu nication interface NOTICE Avoid destruction of the product by electrosta...

Страница 18: ...ur PC 3 Carefully insert the plug for the communication interface straight into the communi cation interface in such a way that the keying tab fits into the lower recess The plug is seated correctly o...

Страница 19: ...ring time typ 1 110 VAC 37 ms 230 VAC 38 ms Holding time typ 1 110 VAC 41 ms 230 VAC 41 ms 1 At nominal load Table 18 Technical Data Input Connection Property Value Cross section Solid 0 08 2 5 mm 28...

Страница 20: ...ge 90 264 VAC 3 10 90 load step 4 20 MHz bandwidth 5 See section 8 Short Circuit and Overload Behavior 55 6 Can be set via the WAGO Interface Configuration software 7 See figure Turn on Time Overshoot...

Страница 21: ...0 C 140 F Required tools conductor termination Operating tool with a partially insulated shaft type 2 see section 8 Accessories 62 3 9 4 Efficiency Power Loss Table 21 Table Technical Data Efficiency...

Страница 22: ...al Output DO Property Value Switch on threshold typ UOUT USET 0 93 Switch off threshold typ UOUT USET 0 87 Contact load max 50 mA Voltage drop typ 100 mV at 50 mA Contact voltage max 31 2 VDC Polarity...

Страница 23: ...emperature operation 25 70 C Surrounding air temperature restricted operation 1 40 25 C Surrounding air temperature storage 40 85 C Derating Temperature Dependent 2 3 K 55 C and 230 VAC 3 K 60 C and 2...

Страница 24: ...e section 8 Latching Shutdown on Thermal Overload Mode 57 5 The circuit breaker can be used for activation during installation In this case the circuit breaker must meet all the requirements on this s...

Страница 25: ...Climatic Environmental Conditions Standard Test Value Mechanical Environmental Conditions EN 60068 2 6 f 5 150 Hz 1g 3 5 m IEC 60068 2 27 shock 15g 11 ms 6 shocks per axis and direction half sine EN 6...

Страница 26: ...immunity test Contact discharge 6 kV B Air discharge 2 kV 4 kV 8 kV B EN 61000 4 3 Part 4 3 Testing and measurement techniques Radiated radio fre quency electromagnetic field immu nity test 80 MHz 1...

Страница 27: ...2 1 Conducted distur bance AC input Class B residential area at nom inal load Conducted distur bance DC output Class B residential area at nom inal load EN 55016 2 3 Part 2 3 Methods of measurement of...

Страница 28: ...787 2144 Properties 28 Product manual Version 1 0 0 Power Supply Pro 2 The manufacturer of the system or machine is responsible for ensuring compliance with the limit values required by EMC legislatio...

Страница 29: ...ng and displaying time series of measured values For details see section 8 Display Section Measurement Recording 51 Configurable overload behavior For details see section 8 Dialog Settings 42 Configur...

Страница 30: ...ance of at least 50 mm from the ventilation openings to adjacent surfaces The letters shown in parentheses refer to positions in the View figure in section 8 View 12 Mounting Positions Nominal mountin...

Страница 31: ...Rail A B Figure 15 Mounting Install the product as per EN 60715 by snapping it onto the DIN 35 rail see figure Mounting 1 Place the product with its DIN 35 rail guide on the top edge of the DIN 35 ra...

Страница 32: ...manual Version 1 0 0 Power Supply Pro 2 Removing from the DIN 35 Rail D C Figure 16 Removal 1 To remove see figure Removal pull the latch k down C using a screwdriver or an operating tool 2 Pivot the...

Страница 33: ...les see section 8 Technical Data 18 Check the appropriate operating voltage before connecting the equipment see section 8 Type label 13 6 2 Connect Conductor to CAGE CLAMP CAGE CLAMP Connectors are de...

Страница 34: ...tion opening 3 Remove the operating tool to close the CAGE CLAMP The conductor is now securely clamped 6 3 Push In Termination The connections for the output can also be wired directly without using a...

Страница 35: ...output voltage Press once The output voltage increases in steps Press and hold The output voltage increases con tinuously Press once The output voltage is reduced in steps Press and hold The output vo...

Страница 36: ...r Trip ping Current of Electronic Cir cuit Breaker Exceeded 100 Flashing 2 Hz Flashing 2 Hz Flashing 2 Hz 75 Off Flashing 2 Hz Signaling of regular utilization 50 Off Off 25 Off Off DC OK Flashing 2 H...

Страница 37: ...ponents Requirements Operating system Windows 10 64 bit Memory 8 GB Free hard disk space 250 MB Processor 1 GHz or higher 64 bit x64 Screen resolution 1920 1080 pixels 9 1 2 Install WAGO Interface Con...

Страница 38: ...the example of connecting the product to a computer via a WAGO USB Communication Cable 9 2 First Steps The following steps are based on the WAGO Interface Configuration software G2 version 01 00 01 2...

Страница 39: ...enu Item Description Communication Selects the connection between the product and software Language Selects the display language for the software Help Opens the help for the software About Displays in...

Страница 40: ...een manually selected or automatically detected by the software see the following steps The settings you have to make on this tab depend on whether you are configuring your product offline or online O...

Страница 41: ...1 8 Menu Bar 42 The menu bar contains general software settings options You can find more information in section 8 Menu Bar 42 2 8 Main Menu 49 The main menu contains individual tabs that contain dif...

Страница 42: ...ameters and measured values which can be stored as a CSV file Update Performs a firmware update on the product You can get the current firmware update and corre sponding compatibility information from...

Страница 43: ...externally The saved settings can be imported into a product that is configured offline a replacement product or a product used in a similar way for example Factory Settings Resets all settings to th...

Страница 44: ...tronic circuit breaker If this box is checked the Electronic Circuit Breaker overload behavior is enabled In the event of overload the power supply works like an electronic circuit breaker and switche...

Страница 45: ...on off If this box is checked the product can be switched on and off via the digital input Inversion If this box is checked the digital input is inverted Function triggered by low high transition If...

Страница 46: ...off latched 1 If this box is checked the digital output is set if latching shutdown occurs Digital output via process data communication 1 If this box is checked the digital output can be con trolled...

Страница 47: ...l switch on delay is enabled in the event of connection to the grid Switch on delay Here you can enter the switch on delay unit ms Disable reset to factory set tings If this box is checked it is not l...

Страница 48: ...tion active If this box is checked no parameters can be written to the product Write and read protection ac tive If this box is checked no parameters can be written to the product or read from the pro...

Страница 49: ...nce graph for up to three measured values The representation in the Display section is described in section 8 Display Section Measurement Recording 51 Information Shows information about the connected...

Страница 50: ...last minute unit Ws Last hour This indicates the output energy supplied in the last hour unit Wh Operating condition Status DC O K Green indicator Status OK Red indicator There is a message Status of...

Страница 51: ...d values over a specific time period clock should be recorded The corresponding input form changes accordingly Pos 3 input form for chart Pos 4 input form for clock 2 Measured Value Selection Here you...

Страница 52: ...ecorded only for on line display and not saved Start Starts the recording setting at pos 1 chart Stop Stops the recording before the specified number is reached setting at pos 1 chart 5 This shows the...

Страница 53: ...lay The corresponding switch on delay can be parameterized in the 8 Dialog Settings 42 dialog in the System section of the WAGO Interface Configuration soft ware The maximum number of products that ca...

Страница 54: ...Table 61 Derating Location Dependent Temperature Value Derating TU 55 C 16 0 1000 m 55 C 2000 m or higher 0 1 2 3 4 5 0 1000 2000 3000 4000 5000 IOUT A Altitude m Tamb 40 C Tamb 50 C Tamb 55 C Figure...

Страница 55: ...e Configuration software 10 5 Short Circuit and Overload Behavior The product s output is electronically protected against overload and short circuits The following values apply to the description bel...

Страница 56: ...man ual intervention is necessary The following options are available for this Communication interface Buttons Digital input t 110 100 20s IOUT IN Figure 37 Constant Current with Latching Shutdown Mod...

Страница 57: ...down on Thermal Overload Mode In this mode the output voltage is switched off in the event of excessive internal device temperature A corresponding High Device Temperature warning can for example be t...

Страница 58: ...be caused by a short circuit or a large overload in the secondary circuit for example In some cases the current pulse can trip an overcurrent protection device that is present in the connected circuit...

Страница 59: ...tection class against dust accumulation moisture radiation and aggressive chemi cals Permitted repairs are limited to the measures listed in these operating instructions Should a fault occur nonethele...

Страница 60: ...benefits health protects the environ ment from harmful substances in electrical and electronic equipment and enables sus tainable and efficient use of resources Observe national and local regulations...

Страница 61: ...lustrate examples of how a WAGO Power Supply Pro 2 can be connected as a consumer in three different grounding systems TN TT and IT 12 1 1 AC Operation L N PE Load Source AC 1 phase AC DC Figure 42 AC...

Страница 62: ...ication Cable 2 5 m 0750 0923 Accessories Tools Table 64 Accessories Tools Description Designation Item Number Operating tool with partially insulated shaft Type 2 blade 3 5 0 5 mm 0210 0720 Operating...

Страница 63: ...emark of the Digital Illumination Interface Alliance DiiA EtherCAT is a registered trademark and patented technology licensed by Beckhoff Automation GmbH Germany ETHERNET IP is a registered trademark...

Страница 64: ...ent 19 Table 17 Technical Data Mains Failure Buffering Time 19 Table 18 Technical Data Input Connection 19 Table 19 Technical Data Output 19 Table 20 Technical Data Output Connection 20 Table 21 Table...

Страница 65: ...le 48 Legend for the Graphical User Interface Overview 41 Table 49 Device Tab 42 Table 50 Dialog Settings Buttons 43 Table 51 Dialog Settings DC Output 44 Table 52 Dialog Settings Signalization 45 Tab...

Страница 66: ...Removal 32 Figure 17 Connect Conductor to CAGE CLAMP 34 Figure 18 Software Start 38 Figure 19 Start View 38 Figure 20 Start View Tabs 39 Figure 21 Backstage Tab 39 Figure 22 Device Tab Selection Menu...

Страница 67: ...rent with Latching Shutdown Mode 56 Figure 38 Hiccup Mode 56 Figure 39 Electronic Circuit Breaker Mode 57 Figure 40 Power Boost Mode in Combination with Constant Current Mode 58 Figure 41 Loop Impedan...

Страница 68: ...s catalogs videos and other WAGO media are subject to copyright Distribution or modification of the contents of these pages and videos is prohibited Furthermore the content may neither be copied nor m...

Отзывы: