3 Assembly and installation [specialist]
2015/03
EN-XXX_CIRCOtransfer-30E-50E_TI-MA-BA-150401-3PAW0501 - 99609x7WAG0x-mub-en - V06
9
3
Assembly and installation [specialist]
The location of installation must be dry, load-carrying, frost-proof and protected against
ultraviolet radiation. Furthermore, the access to the control and safety equipment must be
guaranteed at all time during operation!
The discharge line of the safety equipment should be guided into a heat-resistant container with
corresponding size. This allows you to avoid uncontrolled discharging into the environment and
to easily refill the circuits!
NOTICE
Material damage due to high temperatures!
Install the fitting group at a sufficient distance from the collector field, since the solar fluid may
be very hot near the collector.
It may be necessary to install an intermediate tank in order to protect the expansion tank.
1.
You can use a drilling template in order to facilitate the
installation, which you can find on the station.
2.
Copy the mounting hole measures to the mounting
surface.
3.
Drill the holes and insert apropriate wall plugs into the
holes.
4.
Screw in the screws and let them stick about 4 cm out
of the wall.
5.
Remove the station from the packaging.
6.
Remove the insulating front shell.
Hang the station onto the screws and tighten
the screws.