User’s Manual—Read before using this equipment

10

100

90
80

70

60
50
40
30
20

10

0

0

180 200

20 40 60 80 100 120 140 160

The curve can be applied to any lead acid battery under load providing that it has an AH rating 

at the 20 hour rate.
Continuing with the previous example, the 150 amp load will need to run for 10 hours, so we 

begin configuration with a 1,500 AH battery. If the vertical is 1,500 and the horizontal is 150 

amps, the percentage of load on the battery is 10%. The curve shows that the 1,500 AH is 

derated to 90% of maximum. This means that the battery will have to be 1,650 AH for the full 10 

hour run time. It is important to add some extra battery capacity, because as the batteries age 

they will lose AH capacity.

CONFIGURING THE BATTERY BANK

Twelve-volt, 220 AH batteries were selected for these illustrations because they are generally 

readily available and relatively inexpensive. They are deep-cycle type and with regular 

recharging they have a relatively long life. These batteries are “flooded” type; they freely vent 

hydrogen and oxygen while under charging and heavy discharge. They must be vented to 

outside air to prevent accumulation of explosive gases. If the batteries are to be kept in close 

proximity to the inverter or in a living space, use deep-cycle sealed lead acid (SLA) batteries.

Fusing Requirements

NOTE: It is important that this 5,000 watt inverter has the correct main battery fuse added to the 

Positive (+) battery cable as close as possible to the battery bank’s positive terminal. ANL fuse 

must be located within one foot of positive battery terminal, marine installations within 8 inches. 

Refer to this chart for correct size:

#3744 (12V DC INPUT) 

#3744-4 (24V DC INPUT)

#3744-8 (48V DC INPUT)

ANL 500 amp fuse

ANL 250 amp fuse

ANL 125 amp fuse

The fuse amperage rating must be sized to allow simultaneous operation of all the AC appliances 

to be powered, allowing for the momentary high startup current requirements of inductive loads. 

Use the recommended fuse block (fuse holder) and fuse, or an electrical equivalent. ANL type 

fuses and fuse holders are readily available from marine supply dealers.
The fuses are very important to protect equipment, batteries and personnel. The fuses protect 
against battery explosion if the cables that connect to the inverter accidentally short.

Содержание Proline-5000 3744

Страница 1: ...Item No 3744 12V DC Input 3744 4 24V DC Input 3744 8 48V DC Input Proline 5000 AC to DC Inverter User s Manual Please visit our website for the latest information on this product RoHS compliant...

Страница 2: ...Output AC Terminals 6 Remote ON OFF Switch Connection 6 Power Inverter Output Waveform 6 Inverter Output Characteristics 7 Rear Panel 7 High Speed Cooling Fan 7 Negative DC Input and Positive DC Input...

Страница 3: ...onnecting an Inverter 12 General information 12 Ground Terminal Wire Requirements 12 Cable Preparation 12 Inverter to Battery Connection Procedure 13 Charging the Battery Bank 14 Regular Loss of Comme...

Страница 4: ...ing fumes from flooded lead acid batteries Keep well ventilated this device generates heat Do not continuously operate your inverter at more than its rated output wattage Incorrect battery polarity wi...

Страница 5: ...e equipment All Modified Sine Wave MSW inverters may not properly operate some appliances with either speed control features or dimmer controls Some appliance GFCI power cords will not operate properl...

Страница 6: ...verter These are used to help diagnose problems if they occur Volts Display The volts display is the measurement of the voltage at the DC terminals of the inverter not actual battery voltage During hi...

Страница 7: ...nnection to distributed wiring that has multiple AC outlets Any wiring that is directly connected must be 10 gauge or larger Facing the front panel the terminals are Top Middle Bottom Live Black Neutr...

Страница 8: ...gh Speed Cooling Fan Positive DC Input Terminal High Speed Cooling Fan Fans operate automatically when the internal temperature of the inverter requires cooling Always allow free air flow Do not block...

Страница 9: ...otorized appliances will cause Do not exceed the surge rating of this inverter 5 000 watts this can cause immediate overload shut down At 5 000 watts continuous output this inverter requires a DC powe...

Страница 10: ...ged at a 1 amp rate is will take 20 hours to discharge that battery The terms charged and discharged relate to actual battery voltage This means that the output voltage of a nominal 12 volt battery st...

Страница 11: ...ries are flooded type they freely vent hydrogen and oxygen while under charging and heavy discharge They must be vented to outside air to prevent accumulation of explosive gases If the batteries are t...

Страница 12: ...protection Safety Ground 12V 220Ah 12V 220Ah 12V 220Ah INVERTER 12V DC Input Safety Ground 12V 220Ah 12V 220Ah 12V 220Ah 12V 220Ah 12V 220Ah 12V 220Ah INVERTER 24V DC Input Safety Ground 48V DC Input...

Страница 13: ...to the positive terminal of the battery bank Use a length of string and follow the route the cables will follow Measure the length of string and then determine the correct gauge cable required for the...

Страница 14: ...erminals on the rear of the inverter 4 Tighten the retaining nuts 5 Connect all fuses end positive cable ring terminals to the positive battery bank terminal 6 Carefully tighten the retaining nuts DO...

Страница 15: ...charger manual s s WARNING THERE IS DANGER OF EXPLOSION DO NOT CONNECT OR DISCONNECT CHARGER CABLES DIRECTLY AFTER BATTERY DISCHARGE OR RECHARGE MAKE SURE THAT THE BATTERY BANK AREA IS WELL VENTED BE...

Страница 16: ...ed value Recharge or replace battery Equipment being operated draws too much power Cable gauge may be inadequate use heavier cables Inverter is too hot thermal shut down mode Allow inverter to cool Ch...

Страница 17: ...DC 0 2A DC Battery low alarm 3744 10 5V 0 5V DC 3744 4 21 0V 1 0V DC 3744 8 42 0V 2 0V DC Battery low shutdown 3744 9 5V 0 5V DC 3744 4 20 0V 1 0V DC 3744 8 40 0V 2 0V DC AC output sockets 3 US standa...

Страница 18: ...battery negative to inverter negative Use this Total Cable Length to determine the correct cable gauge in table in Appendix A Fuse Battery Bank INVERTER Positive Cable Positive Cable Negative Cable To...

Страница 19: ...warranty is in lieu of all warranties expressed or implied and no representative or person is authorized to assume any other liability in connection with the sale of our products There shall be no cl...

Страница 20: ...CA 94544 U S A Tel 1 510 471 9221 U S Canada Toll Free 1 800 231 5806 customerservice wagan com www wagan com 2016 Wagan Corporation All Rights Reserved Wagan Tech and wagan com are trademarks used b...

Отзывы: