3.8
Generator Derating
All generators are subject to derating for altitude and temperature.
Internal combustion engines, unless modified, run less efficiently at
higher altitudes due to the reduction of air pressure. This translates
into a lack of power and thus reduction in generator output.
Temperature affects both engine and generator performance. As
temperature increases, an engine will run less efficiently and more
resistance will be found in electrical components. Therefore, as the
temperature increases, the output of the generator decreases. Altitude
also affects the cooling capacity of air—the higher the altitude the less
dense the air is and thus the lower its ability to transfer heat.
For every increase in altitude of 500 m (1650 ft.) above 1000 m (3300
ft.), the output of the generator will be reduced by 3%. For every
increase of 5° C (9° F) in ambient temperature above 40° C (104° F),
the output of the generator will be reduced by 3%. Use the tables
shown for altitude and temperature deration factors. It may be
necessary to consider both altitude and ambient temperature deration
factors to determine true generator output.
Ambient Temp.
°C (°F)
Derate
Factor
45 (113)
3 %
0.97
50 (122)
6 %
0.94
55 (131)
9 %
0.91
60 (140)
12 %
0.88
Altitude
m (ft.)
Derate
Factor
1500 (4900)
3 %
0.97
2000 (6600)
6 %
0.94
2500 (8200)
9 %
0.91
3000 (9900)
12 %
0.88
3500 (11500)
15 %
0.85
4000 (13100)
18 %
0.82
Содержание GP 5600A
Страница 1: ...5000192945 01 0511 5 0 0 0 1 9 2 9 4 5 Operator s Manual Portable Generator GP 5600A GPS 5600A EN...
Страница 15: ...GP GPS 5600A Labels wc_si000558gb fm 15 2 Labels 2 1 Label Locations wc_gr003142 C L G B E F N K J D A M B...
Страница 20: ...Labels GP GPS 5600A 20 wc_si000558gb fm Notes...
Страница 27: ...GP GPS 5600A Operation wc_tx000789gb fm 27...
Страница 47: ...GP GPS 5600A Technical Data wc_td000240gb fm 47 Notes...
Страница 48: ...Technical Data GP GPS 5600A 48 wc_td000240gb fm...
Страница 61: ......