wc_tx003579gb_FM10.fm
63
Mobile Generator
Operation (Basler Controller)
Continued from the previous page.
6. Connect the load to the lugs and/or to the convenience receptacles.
7. Check the operation of the genset controller.
a. Set the engine start switch to REMOTE START. The LCD panel momentarily
displays
INITIALIZING
followed by
READY
.
Engine information is also
displayed. Check the fuel level and battery voltage. Add fuel and/or charge
the battery if needed. If the LCD display does not power up, check battery
voltage and connections.
b. With the READY screen showing, press the emergency stop button
(f)
. The
LCD panel displays
EMERGENCY STOP
, and the pre-alarm/alarm LED
illuminates. If the LCD does not display
EMERGENCY STOP
, do not
continue. Contact a Wacker Neuson dealer for assistance. Pull out the
emergency stop button after verifying the display.
c. Set the engine start switch to OFF.
Starting
8. Start the engine by setting the engine start switch to the START/RUN position.
After displaying
INITIALIZING
and
NOT IN AUTO
, the LCD panel will display
START DELAY
followed by
CRANKING
as the engine begins its crank cycle. The
crank cycle calls for the engine to crank for 10 seconds, then rest for 10 seconds.
This cycle will repeat three times in an attempt to start the engine.
If the engine does not start within three attempts, the genset controller stops the
crank cycle and
OVERCRANK
is displayed on the LCD panel.
9. To repeat the crank cycle, set the start switch to OFF, then back to START/RUN.
Upon startup
Upon engine startup, the LCD displays the monitoring screen. Run the engine for a
few minutes to allow it to warm before turning on (closing) any circuit breakers.
Note: Leave the engine start switch (a) in the START/RUN position while the
generator is operating.
10.Check the voltage on the monitoring screen and adjust it as needed using the
voltage adjustment rheostat. See topic
Selecting the Voltage.
11.Turn on (close) the appropriate circuit breakers for your load.
wc_gr010195
Содержание G 25
Страница 1: ...5200015081 04 0215 5 2 0 0 0 1 5 0 8 1 Operator s Manual Mobile Generator G 25 T4i G 25 T4f EN...
Страница 6: ...Foreword 6 wc_tx003565gb_FM10 fm Notes...
Страница 24: ...wc_si000835gb_FM10 fm 24 Label Locations G 25 2 Label Locations G G GG JJ C H F VV EE K E W D X wc_gr011688...
Страница 165: ...wc_tx003641gb_FM10 fm 165 G 25 Maintenance Tier 4i Engines Isuzu 770012...
Страница 168: ...wc_tx003642gb_FM10 fm 168 Maintenance Tier 4f Engines Isuzu 770006...
Страница 169: ...wc_tx003642gb_FM10 fm 169 Maintenance Tier 4f Engines Isuzu 770007...
Страница 170: ...wc_tx003642gb_FM10 fm 170 Maintenance Tier 4f Engines Isuzu 770008 770009...
Страница 171: ...wc_tx003642gb_FM10 fm 171 Maintenance Tier 4f Engines Isuzu 770010...
Страница 191: ...wc_tx003111gb_FM10 fm 191 User s Information for Transport Canada Fuel Tank...
Страница 192: ...wc_tx003111gb_FM10 fm 192 User s Information for Transport Canada Fuel Tank...
Страница 212: ...Schematics Machines with Deep Sea Controller G 25 212 Notes...
Страница 213: ......