DIAGRAM
Selection of required cross section for extension of cables and power lines
This procedure takes into consideration:
1.
The ohmic and inductive resistance of the line with an admissible loss of voltage of 5% and cos phi =
0,8 as per voltage-frequency-curves.
2.
The admissible warming-up of the lines as per VDE standard (table of required minimum cross section).
☛
ATTENTION!
The larger one of both cross sections has to be chosen.
Example:
Nominal voltage 3 ~ 400 V, 50 Hz
Rated current 15 A
Line length 100 m
15 A x 100 m = 1500 A x m
Cross section as per diagramm: 2,5 mm
2
Cross section as per table: 15 A : 1 mm
2
Chosen cross section: 2,5 mm
2
Voltage - Frequency - Curves
Cross-section area of cable in mm
2
Minimum cross-section
area according to VDE
Max.
Max.
Cable
load
fuse
mm
2
A
A
1
15
10
1,5
18
10/3~16/1~
2,5
26
20
4
34
25
6
44
35
10
61
50
16
82
63
25
108
80
Rated current x length of cable A x m