Page 32 of 53
POS-123-P-PFN
5.6.5
ACC (Current loop auto adjustment)
Command
Parameter
Unit
Group
ACC
X
x= ON|OFF
-
POWERSTAGE
Operation mode of the closed loop current control.
ON
:
In automatic mode PPWM and IPWM are calculated depending on the PWM-frequency.
OFF
:
Manual adaption by the user is necessary.
5.6.6
PPWM (P gain of the current loop)
5.6.7
IPWM (I gain of the current loop)
Command
Parameter
Unit
Group
PPWM
X
IPWM
X
x= 0… 30
x= 1
… 100
-
-
POWERSTAGE
The PI current controller for the solenoid control is parameterized with these commands.
A higher P-gain increases the dynamic of the closed current loop and so its influence on the dither. The I-gain
should only be changed if having detailed knowledge about the current control.
CAUTION
: These parameters should not be changed without adequate measurement facilities and
experience. Changes are only possible if ACC is set to OFF.
If the PWM frequency is < 250 Hz, the current controller dynamics must be reduced.
Typical values are: PPWM = 1... 3 and IPWM = 40... 80.
If the PWM frequency is > 1000 Hz, the default values of PPWM = 7 and IPWM = 40 should be selected.