5.6.6 PPWM (Solenoid current controller P gain)
5.6.7 IPWM (Solenoid current controller I gain)
Command
Parameters
Unit
Group
PPWM
X
IPWM
X
x= 0… 30
x= 1… 100
-
-
ACC=OFF
The PI current controller for the solenoids is parameterized with these commands.
CAUTION
: These parameters should not be changed without adequate measurement facilities and
experiences.
Attention, if the parameter ACC is set to ON, these adjustments are done automatically.
If the PWM frequency is < 250 Hz, the dynamic of the current controller has to be decreased.
Typical values are: PPWM = 1
… 3 and IPWM = 40… 80.
If the PWM frequency is > 1000 Hz, the default values of PPWM = 7 and IPWM = 40 should be chosen.
5.7
Process data (Monitoring)
Command
Description
Unit
W
C
X
XR
U
Command value after input scaling
Command value after ramp function
Feedback value
Feedback value real unit
Command value to current controller
%
%
%
%
bar
IA
IB
Output current of solenoid A
Output current of solenoid B
mA
mA
The process data are the variable values which can be continuously observed on the monitor or on the oscillo-
scope.