5.3.6 RA (Ramp function)
Command
Parameters
Unit
Group
RA:I
X
i= 1… 4
x= 1… 120000
-
ms
STD
Four quadrants ramp function.
The first quadrant means the acceleration ramp for solenoid A and the second one stands for the deceleration
ramp of solenoid A. According to this the third quadrant represents the acceleration ramp for solenoid B so
that the fourth quadrant remains for the deceleration ramp for solenoid B.
ATTENTION:
Because of internal calculations rounding errors may be occur on the display.
5.4
Power limitation function
5.4.1 PL:V (Power limitation factor)
5.4.2 PL:T1 (Dynamic of the power limitation function)
Command
Parameters
Unit
Group
PLV:I
X
PLT1:I
X
I = A|B
x= 2000… 10000
x= 10… 1000
0,01 %
0,1 ms
STD
The power limitation function is parameterized by these parameters.
PL:V
defines the power factor according to the possible maximum power for each direction. The possible
maximum is calculated by the maximum pressure and the displacement. It should be payed attention
to the power loss.
PL:T1
defines the dynamic, means the speed of the power limitation function. Typical used values are in
the range of
5… 50ms.
Attention:
Because of internal calculations the value is parameterizable only stepwise. Always the next possi-
ble higher step is chosen.
t
A
u
sg
a
n
g
/O
u
tp
u
t A
A
u
sg
a
n
g
/O
u
tp
u
t
B
RA:1
RA:2
RA:3
RA:4