VWR Flow Through Скачать руководство пользователя страница 5

 

Section 2 – Operations 

 

 

WARNING 
Do NOT circulate water through any Cooler unit. 
Do NOT use combustible or toxic fluids such as pure methanol. Do NOT use 
fluids corrosive to copper.

 

 

Before proceeding, be sure the Power ON/OFF switch is in the OFF position. 

 

2.1 Power 

Plug the unit into a properly wired, grounded outlet with the same voltage and frequency indicated on 
the identification label on the back of the unit.  Use of an extension cord is not recommended.  If 
necessary, use a cord that is properly grounded and will handle the total wattage of the unit.  The 
extension cord must not cause more than a 10% voltage drop to the Cooler. 

 

2.2 

Safety Overload Warning 

The compressor in these units is equipped with an internal safety overload switch.  If the unit is turned 
off, sufficient time must be allowed for internal pressure and temperatures to stabilize before the unit is 
turned on again.  

The time off before

 

restarting should not be less than 10 minutes.  

If the unit is 

turned on too quickly, the compressor may not start and the unit will not operate.  If this happens, turn 
the unit off again and wait 10 minutes before restarting. 

 

2.3 

Choice of Fluids 

In order to select a fluid for low temperature use, the viscosity of a fluid at low temperatures as well as 
its freezing point must be considered. 
 
The two most frequently used fluids are: a mixture of methanol and water; or a mixture of ethylene or 
propylene glycol and water.  For most applications, the use of a 50:50 mixture of methanol and water is 
preferred.  This mixture has the low freezing point required, is low in viscosity, and is not flammable. 
 

Suitable Fluids

 

Use the chart below in selecting fluid for your application.  It is highly recommended to stay within the 
fluid's normal range for best stability and low vaporization. 
 

Extreme range operation should be avoided.

 

The centistokes (cs) ratings are at 25

°

C. 

 

Fluid Description 

Normal Range 

Extreme Range 

 

Ethylene glycol 30% : water 70% 

0

°

C to 90

°

C -15

°

C to 107

°

 

Ethylene glycol 50% : water 50% 

-25

°

C to 100

°

C -35

°

C to 115

°

 

Propylene glycol 30%     water 70% 

5

°

C to 90

°

C -10

°

C to 107

°

 

Propylene glycol 50%     water 50% 

-20

°

C to 100

°

C -30

°

C, to 115

°

 

Dynalene

 HC50 

-50

°

C to 60

°

C * 

-62

°

C to 60

°

C * 

 

DC200, 5 cs Silicone Oil 

-35

°

C to 60

°

C * 

-62

°

C to 60

°

C * 

 

DC200, 10 cs Silicone Oil 

-20

°

C to 80

°

C -35

°

C to 165

°

C * 

 

*Warning - Fluids flashpoint temperature. 

Dynalene

  is a registered trademark of Advanced Fluid Technologies. 

 

Содержание Flow Through

Страница 1: ...Operator Manual Flow Through Coolers Immersion Coolers 110 064 Rev C 05 03...

Страница 2: ...ng Procedure For Immersion Coolers 2 5 Operating Procedure For Flow Through Coolers 2 6 Application Notes Section 3 Trouble Shooting 3 1 Required Maintenance 3 2 Problem Solution chart Section 4 Servi...

Страница 3: ...r other causes not arising out of defects in material or workmanship There are no warranties expressed or implied including but not limited to those of merchantability or fitness for a particular purp...

Страница 4: ...ith a copper tube within a tube heat exchanger The fluid to be cooled is circulated through the space between the tubes while the refrigerant evaporates to produce cooling inside the inner tube The fl...

Страница 5: ...and wait 10 minutes before restarting 2 3 Choice of Fluids In order to select a fluid for low temperature use the viscosity of a fluid at low temperatures as well as its freezing point must be consid...

Страница 6: ...r pump 5 Set the circulator s temperature control to the desired temperature When the temperature stabilizes the circulator s heater should cycle to maintain the set temp 6 Turn the Cooler s power swi...

Страница 7: ...ltage Avoid extension cords that can cause voltage drops 3 See Sect 3 1 Required Maintenance Check for airflow exiting the back of the unit Air vents should not be closer than 3 in from a wall or unit...

Страница 8: ...ssor valves may produce high pitch buzzing sound 12 Check power Unit s power switch should be illuminated Section 4 Service and Technical Support If you have followed the troubleshooting steps and you...

Отзывы: