Advanced manual
37
Transducer type
- mounted sensor
• DSC
- sensor from Sentera Controls
• CDD
- sensor from CATIC-I
• OTHER
- manual settings
• HTC
- OEM VTS
(
Holding Register
- Modbus function
0000
- CO2
value index in modbus)
Transducer online
- information about connected
device on Modbus line
HMI ADVANCED
CO2 transducer
Transducer type
DSC
Holding Register
0000
Transducer online
█
4.2. SERVICE MENU
OUTPUTS
Actual output values are available here to check the
hardware functionality.
Digital outputs
▪
Terminal NO1
- water heater pump start
▪
Terminal NO2
- damper open
▪
Terminal NO3
- glycol recovery pump start or
user con
fi
gurable relay 1
▪
Terminal NO4
- cooling start (DX stage 1 or
chiller)
▪
Terminal NO5
- cooling start (DX stage 2)
▪
Terminal NO6
- pre-water heater pump start or
user con
fi
gurable relay 2
▪
Terminal NO7
- alarm signal
Analog outputs
▪
Terminal Y1
- heating rate
▪
Terminal Y2
- cooling rate or pre-heating rate
▪
Terminal Y3
- recovery rate
Note!
The percentage values refer to 0..10V hardware
output.
HMI ADVANCED
OUTPUTS
NO1
NO2
NO3
Off
Off
Off
NO4
NO5
NO6
On
On
On
NO7/NC7
Off
OUTPUTS
Y1
Y2
Y3
25%
0%
100%
FRQ CONVERTERS CONFIGURATION
Device function
– setting for the place in the AHU,
that the actual FC has got.
▪
Supply 1
– 1st supply fan (Modbus address 2)
▪
Supply 2
– 2nd (5)
▪
Supply 3
– 3rd (7)
▪
Supply 4
– 4th (9)
▪
Exhaust 1
– 1st exhaust fan (3)
▪
Exhaust 2
– 2nd (6)
▪
Exhaust 3
– 3rd (8)
▪
Exhaust 4
– 4th (10)
▪
RRG
– rotary regenerator (4)
Note! Bad selection will cause bad parameter setting
and bad addressing in Modbus communication.
HMI ADVANCED
FC CONFIG
Device function
Supply1
Freq.conv.type
LSiC5
Motor power
0,55kW
Motor poles
2p
Selection OK
Yes
FCCon
fi
g state
Ready