User’s Manual
16
3.4.6. PARAMETERS
RECOVERY
Recovery mode
- selecting the operation mode for the recirculation
chamber
•
MECH
– Maximum Energy Changeover – control from the PID
controller, recirculation plays the role of the
fi
rst heating / cooling
section in order to take full advantage of energy recovery, the scope
of possible changes concerning recirculation is de
fi
ned by
fi
xed
setting of minimum fresh air.
•
Manual
-
fi
xed manual recirculation settings
•
Univ.AI
– control from the universal analog input; the range of
possible changes is limited by the setting of minimum fresh air
Recovery rate
– indicates current recovery capacity, gives a link
to output detail screen (password protected link – see Advanced
Manual)
0% – no recovery, 100% – full recovery
Note!
The controller signal can differ from the actual recovery rate
due to protective functions that could affect it.
Frost prot. rate
– indicates the rate of frost protection, that is
subtracted from controller signal in order to protect the recovery unit
from freezing
Note
!
Frost protection can be managed in two stages - first step
can be reduction of supply fan speed, second step is reducing the
recovery rate
Glycol pump
– indicates current state of the pump, gives a link to
pump detail screen (see Advanced manual)
Status
- combined information for communication problems and for
motor alarms
OK
- no malfunctions
Comm
- communication to the frequency converter not stable or lost
Alarm
- communication OK, but frequency converter reported an
error, e.g. overload
CO2 value
- value of CO2 concentration
HMI ADVANCED
RECOVERY
Recov. mode
MECH
Recovery rate
50%
Frost prot.rate
o%
Glycol pump
On
Alarm status
OK
CO2 value
500 ppm
3.4.7. PARAMETERS
COOLING
Main temp
– current readout from the main temperature sensor
Setpoint
– current setpoint for the regulator, read only
Cooling rate
– indicates current cooling capacity
0% – no cooling, 100%
– full cooling
Pump status
– indicates the current state of the pump or chiller
Alarm status
– indicates the state of the cooling device
OK
– no malfunctions
Fault
– alarm input has been activated
HMI ADVANCED
COOLING
Main temp
27,0°C
Setpoint
21,0°C
Cooling rate
65%
Pump status
On
Alarm status
OK