OIMM – VENTUS PRO

Bearings have to be controlled and cleaned regularly; have to be lubricated adequately to prevent direct metallic 

contact between rolling elements, to prevent wear and to project bearing surfaces against corrosion.
The fans with low shaft power are equipped with bearings in a rubber housing which absorbs a part of vibration. 

When you change the bearing it is very important to change the rubber housing too. These bearings don’t need 

to be lubricated.
The fans with higher shaft power are equipped with bearings with cast iron support. The lubricant filled in a bearing 

gradually loses its lubricating properties during operation. Therefore, it is necessary for grease to be replenished 

or renewed from time to time. The grease used is always lithium soap type suitable for all temperatures within 

the operating range.
Excess grease will cause the operating temperature to rise rapidly, particularly when running at high speeds. 

Therefore, only the bearing should be completely filled, whilst the free space in the housing should be partly filled 

(between 30% and 50 %) Where bearings are to operate at very low speeds and must be well protected against 

corrosion, it is advisable to completely fill the housing.

Relubrication interval depends on the fan speed and bearing internal diameter and is calculated by the following 

formula:

t = 10 x {14x106 / (n x 

d ) – 4 x d }

where:

t = relubrication interval ( h ),
n = fan speed ( rpm ),
d = bearing inner diameter ( mm )

If the fan works in particular conditions, relubrication intervals have to be corrected concerning the temperature 

and surrounding factors, according to the following formula:

tc = t x kT x kS

where,

tc = corrected relubrication interval,
kT = temperature correction factor,
kS = surrounding correction factor

Temperature correction factor kT takes into account the reduction of relubrication interval when bearing 

temperature raised over 70

º

C.

LUBRICATION OF BEARINGS

3.10.8

FAN SPEED

(rpm)

BEARING INNER DIAMETER (mm)

20

25

30

35

40

45

50

60

250

124 420

111 000

101 040

93 250

86 940

81 680

77 190

69 890

500

61 810

55 000

49 920

45 920

42 670

39 940

37 600

33 740

750

40 940

36 330

32 880

30 150

27 910

26 020

24 400

21 700

1000

30 500

27 000

24 360

22 260

20 530

19 070

17 800

15 670

1250

24 240

21 400

19 250

17 530

16 100

14 890

13 840

12 060

1500

20 070

17 660

15 840

14 370

13 150

12 110

11 200

9 650

1750

17 080

15 000

13 400

12 120

11 040

10 120

9 310

7 920

2000

14 850

13 000

11 580

10 430

9 460

8 630

7 900

6 630

3000

9 630

8 330

7 320

6 480

5 770

5 150

4 600

3 620

4000

7 020

6 000

5 190

4 510

3 930

3 410

2 950

2 110

5000

5 460

4 600

3 910

3 330

2 820

2 370

1 960

1 210

Содержание ventus PRO 2022

Страница 1: ...VENTUS PRO AIR HANDLING UNITS OPERATION INSTALLATION AND MAINTENANCE MANUAL PRO 2022 OIMM VENTUS PRO Ver 1 0 0 31 05 2022...

Страница 2: ...FOR AHU ASSEMBLY CARRIED OUT BY VTS AUTHORIZED SERVICE 6 INSTALLATION 7 CONNECTIONS 9 DUCTED OUTLE CONNECTIONS 10 PIPING CONNECTIONS 11 CONDENSATE DRAIN LINES 13 ELECTRIC CONNECTIONS 13 SETTING UP OF...

Страница 3: ...so as to prevent the device from being started accidentally Before connecting the electric power supply check the compliance of the mains voltage and frequency with the data on the name plate of the d...

Страница 4: ...th AHU subassemblies transport of the packages to the assembly location and transport of AHU blocks and elements to the assembly location should be carried out using special equipment and qualified st...

Страница 5: ...e from 5 to 35 C In case of outdoor assembly the procedure can be carried out in precipitation free conditions It is acceptable to start the assembly provided that all safety and security requirements...

Страница 6: ...safe environment for the installation crew The following should be provided availability of individual AHU elements or pallets including packages on the assembly place of a particular AHU Ensured tran...

Страница 7: ...ure that access routes are adequate for both size and weight of the unit sections Air handling unit installation areas should also be checked There should be sufficient space around the unit for servi...

Страница 8: ...installed in the AHU sections where negative pressure occurs Drain siphons or siphon parts are not supplied as standard delivery There is no need to apply drain siphons in section with overpressure I...

Страница 9: ...ted to the AHU with the flexible connections optional accessory which suppress vibrations of the unit and level the coaxial deflection of the duct and the AHU outlets Flexible connections are equipped...

Страница 10: ...d prior to the reducing section To achieve ideal conditions the length of parallel ducting in both cases should be equal to 8 impeller diameters However parallel ducting of considerably shorter length...

Страница 11: ...ves any air in the system into the upper part of the coil where a manual air release valve should be fitted PIPING CONNECTIONS 3 6 2 The diameter of the connection and the type of connection of the ex...

Страница 12: ...12 OIMM VENTUS PRO COIL CONNECTION RULES COIL INSTALLATION HYDRONIC COILS COIL INSTALLATION STEAM COILS Hydronic Steam...

Страница 13: ...d together with ahu diagrams Before starting connecting power supply check conformity of the voltage and frequency of a supply network with the data shown on the device s rating plate Permissible fluc...

Страница 14: ...efault motors with their own cooling system and with fans built into a shaft Supply cabling must be led to the fan s motor via rubber passes located in the back panel of the AHU casing One should conn...

Страница 15: ...s in accordance with guidelines outlined in the operation and maintenance manual of the frequency converter Before putting into service and after long time of storage or standstill the resistance of i...

Страница 16: ...e marked U V W and the neutral terminal N please check data on the rating plate The voltage marked on the rating plate must be in agreement with the mains voltage the terminal board is normally equipp...

Страница 17: ...h water heat exchangers heaters coolers glycol recovery air damper s actuators of supply units should be equipped with a return spring ensuring its spontaneous closure in case of power cut SETTING UP...

Страница 18: ...d be taken in to account System layout should take into consideration of possible coil withdrawal It is recommended that the water flow is shut off when the fan is switched off To avoid the overheatin...

Страница 19: ...tarters controls overload protecting devices interlocks etc should be provided as required See page 34 After the start up check that direction of rotation of the fan is correct The electric heater sho...

Страница 20: ...nits must not be used for handling of flammable gases Spark proof versions of rotating parts fans motors etc must be selected for this kind of applications so air handling unit manufacturer should be...

Страница 21: ...represent a danger suitable guards can be installed drive guards Safety guards should be used when drive systems are accessible by the personnel limit switch Cuts off the power supply of the fan moto...

Страница 22: ...ensure all panels if removed during installation are in position and all service doors are closed ensure that minimum water level is maintained in the humidifier On the downstream or pressure side of...

Страница 23: ...rical supply secure fan impeller if there is a possibility of windmilling Check carefully for the cause of the problem and correct as necessary After ensuring that there is not any problem no leaks be...

Страница 24: ...less electric supply has been locked out and the impeller has been secured Before the maintenance operation the safety precautions should be taken by locking out the main and maintenance switch and pr...

Страница 25: ...AR Check the filter frame for proper sealing Replace synthetic filter media in panel filters Check the controls and operation of automatic roll filters Check the coils and fins Wash with water spray i...

Страница 26: ...cracks on the copper tubes by oxyacetylene welding Check with water if the welding is successful or not After cleaning the coil drain should be checked and the siphon should be cleaned Condition of th...

Страница 27: ...the filters can be taken out by pulling aside Synthetic bag filter can be cleaned by vacuumed or compressed air besides can be washed with the sensitive detergent and warm water Humidifier should be c...

Страница 28: ...quate It goes without question however that like all Rules of thumb some judgement is necessary on the part of person doing the adjusting A belt should be just tight enough to avoid slippage Before lo...

Страница 29: ...the housing Relubrication interval depends on the fan speed and bearing internal diameter and is calculated by the following formula t 10 x 14x106 n x d 4 x d where t relubrication interval h n fan sp...

Страница 30: ...se be removed from the bearing arrangement and replaced by fresh grease The 6 months limit represents a very rough guideline recommendation and may be adapted to particular applications By adding smal...

Страница 31: ...s recommended to contact the unit manufacturer System checklist A systematic check of items listed below may identify the problem See that a impeller rotation is correct b pulley are aligned c belts a...

Страница 32: ...ings Noise from bearings Loose on support Tighten bearings Loose on shaft Tighten shaft Bearings worn or damaged Change bearings Bearings need lubrication Lubricate bearings Foreign material inside be...

Страница 33: ...tlet duct system is not completed Check access doors and duct joints Seal leaks Complete duct system HIGH AIR FLOW Ducts are oversized or duct resistance overestimated Close balancing dampers or slow...

Страница 34: ...w Oversized coil or compressor ELECTRONIC STEAM HUMIDIFIER No humidifying Electronic power failure Power is not reaching elements or control valve Thermostatic gear fault Heater elements faulty Safety...

Отзывы: