PWM SERIES - User Manual

Page 

VSi-PWM-2018-06

22

http://www.VSi.

UK

.com

3.

Switch CB 1 (Input Breaker) to the ‘OFF’ position.

Stabiliser should now be safely powered down.

5.6 Manual Bypass Operation

Only available on models PCM-3.5H-S25 to PCM-14H-S25

Incorrect switching may seriously damage the
Stabiliser /and or connected Load Equipment - 

Invalidate any Warranty

5.6.1 Turning On

Please ensue all load equipment is switched off before commencing 

any of these procedures.

1.

Switch 

CB 2

 (Output Breaker) to the ‘OFF’ position.

2.

Switch 

CB 1

 (Input Breaker) to the ‘OFF’ position.

3.

Remove the 

CB 3

 (Bypass Switch) Cover Plate.

4.

Switch 

CB 3

 (Bypass Switch) to the ON position.

The load is now supplied by the unregulated utility mains supply.

5.6.2 Turning Off

1.

Switch CB 3 (Bypass Switch) to the OFF position.

2.

Reattach the CB 3 (Bypass Switch) Cover Plate.

Stabiliser should now be ready for Power Up.

Содержание PWM 10.5H-S25

Страница 1: ...PWM SERIES STATIC DIGITAL AC AUTOMATIC VOLTAGE STABILISER USER MANUAL Thank you for purchasing a VSi PWM Series Static Digital AC Automatic Voltage Stabiliser...

Страница 2: ...nt If any problems are encountered with the procedures contained within this Manual then seek assistance from VSi or the distributor from whom you purchased the equipment Whilst every precaution has b...

Страница 3: ...2 7 Certi cation Compliance 6 2 8 Warranty 7 3 Safety Instructions 8 9 3 1 Introduction 8 3 2 General Installation and Usage 8 4 Visual External Appearance 10 17 4 1 Front View 10 4 2 Rear View 12 4 3...

Страница 4: ...virtually maintenance free and offer an exceptional fast speed of correction making them ideal for the most sensitive of electrical and electronic loads 1 2 Basic Principle of Operation PWM SERIES AC...

Страница 5: ...IEC 320 16 Amp Hardwire Operating Frequency 50 60 Hz 2 2 Output Model No PWM 2 1H S25 PWM 3 5H S25 PWM 5 25H S25 PWM 7H S25 PWM 10 5H S25 PWM 14H S25 Max Output Rating 2 1 kVA kW 3 5 kVA kW 5 5 kVA kW...

Страница 6: ...Indicators Line Normal Bypass Fault Audible Alarms Fault Over Voltage Comms RS 232 2 4 Protection Model No PWM 2 1H S25 PWM 3 5H S25 PWM 5 25H S25 PWM 7H S25 PWM 10 5H S25 PWM 14H S25 Over Current In...

Страница 7: ...S25 PWM 10 5H S25 PWM 14H S25 Construction Freestanding Enclosures to IP20 NEMA 1 Style BS EN 60529 Colour RAL 7047 Telegray 4 Physical Size 258 W x 333 H x 422 D mm 258 W x 546 H x 532 D mm Weight 2...

Страница 8: ...PWM SERIES User Manual Page VSi PWM 2018 06 7 http www VSi UK com 2 8 Warranty Model No PWM 2 1H S25 PWM 3 5H S25 PWM 5 25H S25 PWM 7H S25 PWM 10 5H S25 PWM 14H S25 Standard Warranty 24 Months 2 Years...

Страница 9: ...be connected to the output of stabiliser If on delivery there is evidence of visible damage do not attempt to install or start the Stabiliser Advise the transport delivery company and inform VSi or th...

Страница 10: ...t sources Do not allow liquids or foreign object to enter the unit The installation and use of this product must comply with all relevant current electrical installations that are in force in the terr...

Страница 11: ...PWM SERIES User Manual Page VSi PWM 2018 06 10 http www VSi UK com 4 Visual External Appearance 4 1 Front View 4 1 1 Model PWM 2 1H S25 to PWM 7H S25...

Страница 12: ...PWM SERIES User Manual Page VSi PWM 2018 06 11 http www VSi UK com 4 1 2 Model PWM 10 5H S25 to PWM 14H S25...

Страница 13: ...PWM SERIES User Manual Page VSi PWM 2018 06 12 http www VSi UK com 4 2 Rear View 4 2 1 Model PWM 2 1H S25...

Страница 14: ...PWM SERIES User Manual Page VSi PWM 2018 06 13 http www VSi UK com 4 2 2 Model PWM 3 5H S25 PWM 7H S25...

Страница 15: ...PWM SERIES User Manual Page VSi PWM 2018 06 14 http www VSi UK com 4 2 3 Model PWM 10 5H S25 PWM 14H S25 on Castors...

Страница 16: ...ww VSi UK com 4 3 Front Display Panel In normal running mode both the LINE and INV Status Indicators should be illuminated 4 3 1 Status Indicators All Okay in line mode In Bypass Mode Stable Output Vo...

Страница 17: ...are Input Voltage I P Vac Voltage level of the incoming utility mains supply Output Voltage O P Vac Output Voltage delivered by the system Input Frequency I P Hz Frequency of the incoming utility mai...

Страница 18: ...al Page VSi PWM 2018 06 17 http www VSi UK com 4 3 3 Load Level Indication In addition to load current readings the display panel also shows below the digital metering in the form of a bar graph perce...

Страница 19: ...etain the packing carton and packaging material to return the PWM SERIES Stabiliser in the unlikely event of its operational failure 5 2 Positioning Although the Stabiliser does not produce excessive...

Страница 20: ...e Input Cable to the terminal block as indicated and take to mains supply via cable entry access hole in the enclosure Connect the Output Cable to the terminal block as indicated and take to the load...

Страница 21: ...BLUE must be connected to the terminal marked N for Neutral The wire coloured YELLOW and GREEN must be connected to the terminal marked G for Earth Ground 5 4 Plug N Play Installation Model PCM 2 1H S...

Страница 22: ...rational able to support have load connected It is recommended that you check the output voltage with a True RMS Voltmeter to ensure that the correct output voltage is displayed If the correct voltage...

Страница 23: ...alidate any Warranty 5 6 1 Turning On Please ensue all load equipment is switched o before commencing any of these procedures 1 Switch CB 2 Output Breaker to the OFF position 2 Switch CB 1 Input Break...

Страница 24: ...ure If the LINE indicator still does not illuminate please seek advice from the dealer from whom the stabiliser was purchased or get in touch with your local VSi Support Centre Display FAULT indicator...

Страница 25: ...and within the permissible input voltage tolerance window shut down the Stabiliser as per the instructions in Section 5 5 2 of this Manual Wait 10 seconds then restart following closely the instructi...

Страница 26: ...Bypass following the instructions given in Section 5 6 If the unstable output voltage condition still exists please seek advice from the dealer from whom the Stabiliser was purchased or get in touch...

Страница 27: ...tional 1 Incoming utility mains supply is not present and or CB 1 is not in the ON position Check to ensure mains supply is present and CB 1 is switched ON If the display is still not operational plea...

Страница 28: ...tability and tness for a particular purpose Some counties do not permit limitation or exclusions of implied warranties therefore the aforesaid limitation s or exclusions s may not apply to the purchas...

Страница 29: ...Your Name Company Names Address Telephone No Email Address Date of Purchase Where From Whom it was Purchased Serial No Model No Local Voltage Type of Load Connected A Description of the Fault Once yo...

Страница 30: ...PWM SERIES User Manual Page VSi PWM 2018 06 29 http www VSi UK com Notes...

Страница 31: ...PWM SERIES User Manual Page VSi PWM 2018 06 30 http www VSi UK com Notes...

Страница 32: ...WWW VSi UK COM...

Отзывы: