ELECTRIC ACTUATOR SPECIFICATIONS 

3 way valve: SHUT / Position , OPEN / Position

Actuator type ( :Voltage code)  ECR-120-  

ECR-360-

Voltage 

100 / 110 AC V ±5 %  50/60 Hz  (Code: 1) 
200 / 220 AC V ±5 %  50/60 Hz  (Code: 2) 

Rated torque 

[N m]  12 

36 

Operation time 

[s]  3 to 6 

7 to 14 

When power is turned on, operation starts about 30 seconds after capacitor is   
charged. 

Charging Time 

[s]  30 

90 

 

When the power is just turned on. 

Power consumption 

[VA] 

In motion: 30 max. Charging: 50 max. Stop: 2.5

Motor 

DC motor 

Overload protection 

Timer 

Method of operation 

a-contact input type, with built-in relay 

Operation *¹ 

[Mode A] SW is OFF    SHUT , SW is ON     OPEN. (Standard) 
[Mode B] SW is ON     SHUT , SW is OFF    OPEN. (Option: Q) 

Power failure   

[Mode A] SHUT    
[Mode B] OPEN   

Built-in power supply 

Electric double layer capacitor 

Input signal current 

6 mA  (O-terminal)  Leakage current in SW: less than 1 mA. 

Output signal rating   

Resistance load: 0.5 A 125 V AC  / 1 A 24 V DC. 

Alarm signal 

Output when the motor protection circuit operates by the overload.   
(it returns by power supply OFF or reverse operating signal) 

Duty cycle 

20 % 15 min.   

Ambient temperature 

-20 to 50 ºC   

Space heater 

Built in to the control board   

Manual operation 

Manual shaft   

Enclosure 

Equivalent to IP65 (IEC 60529) 

Housing material 

Aluminum alloy diecast (acrylic resin baking finish) 

Terminal block 

For bare wire 0.2 to 1.5 mm² (AWG 26 to 16)  Ground terminal: M3 

Conduct port 

2-G1/2 Attachments: Cable gland (for  6 to 12 mm cable), plug. 

*¹  Change by DIP switch.  (Standard      Mode B) 

WIRING 

Setting with DIP SW 

Mode A (Standard) 

Mode B 

Output signal (Common in mode A / B) 

Closed the valve    SHUT  signal 
Open the valve     OPEN  signal 
Overtorque 

   ALARM signal 

Note)  Do not use control switch with current leakage (more than 1 mA) such as TRIAC or relay with CR. 

com.

S.LS

O.LS

Voltage

100/110V AC
200/220V AC

SHUT signal

OPEN signal

Alarm signal

R core
transformer

Backup
capacitor

Ground terminal(M3)