Installation Clearances
The diagram below shows the minimum recommended clearances to meet safety isolation requirements.
Class II equipment
For Class II equipment, the end equipment must also provide a supplementary insulation barrier to the baseplate. This can be achieved in a variety of ways such as a
plastic enclosure, insulating sheet or insulating mounting pillars.
Plastic enclosure
Insulator
Insulating Spacers
Must meet safety agency requirements.
No accessible conductive parts.
Must meet safety agency requirements.
Recommend 5mm creepage from all edges.
M4 thread, Male-Male or Male-Female, Nylon 6/6
Mount baseplate directly to Enclosure or Heatsink
Enclosure or Heatsink
≥5mm Clearance or insulator with thickness > 0.4mm
Enclosure
Enclosure
≥5mm Clearance or insulator with thickness > 0.4mm on all sides
Plastic Enclosure
VCCS300 PSU
Metal Enclosure
VCCS300 PSU
≥5mm
≥5mm
VCCS300 PSU
≥5mm
≥5mm
Metal Enclosure