7
1 = POWER 220 Vac
2 = POWER 220 Vac
3 = Pr2 ... TEMPERATURE PRObE
4 = GND ... TEMPERATURE PRObE
4 = GND ... GROUND ANEMOMETER
5 = Pr1 ... IOUT 4/20 mA ANEMOMETER
6 = +12V ... +Vcc ANEMOMETER
7 = NO ... CONTACT NO ALARM
8 = C ... COMMON ALARM
9 = NC ... CONTATTO NC ALARM
18 = GND- ...-0 fAN SIGNAL OUTPUT
19 = +10V ... +10Vcc fAN SIGNAL OUTPUT
fAN SIGNAL OUTPUT 0-10V
CONT
ACT
NO
CONT
ACT
NO
COMMON
ANEMOMETER PROBE
SONDA
°C
ENGLISH
INSTRUCTIONS FOR START-UP
The unit switches to B mode when it is powered. (See a description of modes A and B below).
The panel is set to automatic mode upon first start-up.
At subsequent start-ups, the panel will be set to the mode last saved before the last shut-down.
Below is a description of the various features found on the unit. All parameters described initially
have factory set values.
Note: If the necessary probes are not present, the unit will operate continuously as a normal fan at
the initially set speed.
POWER
ELECTRIC CONNECTIONS