4. Troubleshooting 

If the UPS system does not operate correctly, please solve the problem by using the table below.   

Symptom 

Possible cause 

Remedy 

No indication and alarm even 
though the mains is normal.   

The AC input power is not 
connected well. 

Check  if  input  power  cord 
firmly  connected  to  the 

mains.   

The  AC  input  is  connected 
to the UPS output. 

Plug AC input power cord to 
AC input correctly.   

The icon 

and 

  flashing on 

LCD display and alarm is sounding 
every second. 

The external or internal 

battery is incorrectly 
connected. 

Check  if  all  batteries  are 

connected well. 

Fault code is shown as 27 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

Battery voltage is too  high 
or the charger is fault. 

Contact your dealer. 

Fault code is shown as 28 and the 

icon 

 

is lighting on LCD 

display and alarm is continuously 

sounding. 

Battery  voltage  is  too  low 
or the charger is fault. 

Contact your dealer. 

The icon 

  and

is 

flashing on LCD display and alarm 

is sounding twice every second. 

UPS is overload   

Remove  excess  loads  from 
UPS output. 

UPS is overloaded. Devices 
connected to the UPS are 

fed directly by the electrical 
network via the Bypass. 

Remove  excess  loads  from 
UPS output. 

After repetitive overloads, 
the UPS is locked in the 

Bypass mode. Connected 
devices are fed directly by 
the mains. 

Remove  excess  loads  from 
UPS output first. Then shut 

down  the  UPS  and  restart 
it. 

Fault code is shown as 43 and The 

icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 

automatically because of 
overload at the UPS output. 

Remove  excess  loads  from 

UPS output and restart it. 

Fault code is shown as 14 and the 
icon 

 

is lighting on LCD 

display and alarm is continuously 
sounding. 

The UPS shut down 
automatically because 
short circuit occurs on the 
UPS output. 

Check  output  wiring  and  if 
connected  devices  are  in 
short circuit status. 

Fault code is shown as 01, 02, 03, 

04, 05, 11, 12, 13 and 41 on LCD 
display and alarm is continuously 
sounding. 

A  UPS  internal  fault  has 

occurred.  There  are  two 
possible results: 
1. The load is still supplied, 

but directly from AC power 
via bypass.   
2.  The  load  is  no  longer 

supplied by power.   

Contact your dealer 

Содержание Winner series

Страница 1: ...1K 2K 3K Online UPS Uninterruptible Power Supply System Version 1 2 User Manual...

Страница 2: ...2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 9 3 6...

Страница 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...inal package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table Model Type Model Type 1K Standard mo...

Страница 6: ...4 1K L Schuko 2K L Schuko 3K L Schuko 1K L Universal 2K L Universal 3K L Universal Rack Unit 1KR L Chinese 1KR L IEC 2KRL Chinese 2KRL IEC...

Страница 7: ...er of the terminal block b Suggest using AWG14 or 2 1mm2 power cords c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the...

Страница 8: ...ided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software downlo...

Страница 9: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Страница 10: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS...

Страница 11: ...re CH Charger FU Bypass frequency unstable EE EEPROM error 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and p...

Страница 12: ...t frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Int...

Страница 13: ...in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 120 140 setting the high voltage point in parameter 3 from 120Vac to 140Vac Default 132Vac LLS Bypass low voltage...

Страница 14: ...When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range...

Страница 15: ...attery is not connected Sounding every second Over Charge Sounding every second Over temperature Sounding every second Charger failure Sounding every second Battery fault Sounding every second Out of...

Страница 16: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...