3-3. Audible Alarm   

Battery Mode 

Sounding every 4 seconds 

Low Battery 

Sounding every second 

Overload 

Sounding twice every second 

Fault 

Continuously sounding 

Bypass Mode 

Sounding every 10 seconds 

 
3-4. LCD display wordings index 

Abbreviation 

Display content 

Meaning 

ENA 

 

Enable 

DIS 

   

Disable 

ESC 

 

Escape 

HLS 

 

High loss 

LLS 

 

Low loss 

BAT 

 

Battery 

CF 

 

Converter 

TP 

 

Temperature 

CH 

 

Charger 

FU 

 

Bypass frequency unstable 

EE 

 

EEPROM error 

 
3-5. UPS Setting 

 

There are three parameters to set up the 

UPS.   

Parameter 1: It’s for program 
alternatives. Refer to below table. 
Parameter 2 and parameter 3 are the 

setting options or values for each 
program.

 

 

01: Output voltage setting 

Interface 

Setting 

 

Parameter 3: Output voltage 

For 200/208/220/230/240 VAC models, you may choose 
the following output voltage: 

200:

 presents output voltage is 200Vac 

208:

 presents output voltage is 208Vac 

220:

 presents output voltage is 220Vac 

 

 

 

 

 

Parameter 1 

Parameter 2 

Parameter 3 

Содержание Winner series

Страница 1: ...1K 2K 3K Online UPS Uninterruptible Power Supply System Version 1 2 User Manual...

Страница 2: ...2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 5 3 Operations 7 3 1 Button operation 7 3 2 LCD Panel 7 3 3 Audible Alarm 9 3 4 LCD display wordings index 9 3 5 UPS Setting 9 3 6...

Страница 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...inal package in a safe place for future use NOTE There are two different types of online UPS standard and long run models Please refer to the following model table Model Type Model Type 1K Standard mo...

Страница 6: ...4 1K L Schuko 2K L Schuko 3K L Schuko 1K L Universal 2K L Universal 3K L Universal Rack Unit 1KR L Chinese 1KR L IEC 2KRL Chinese 2KRL IEC...

Страница 7: ...er of the terminal block b Suggest using AWG14 or 2 1mm2 power cords c Upon completion of the wiring configuration please check whether the wires are securely affixed d Put the small cover back to the...

Страница 8: ...ided CD into CD ROM to install the monitoring software If not please follow steps below to download and install monitoring software from the internet 1 Go to the website http www power software downlo...

Страница 9: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Страница 10: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UPS...

Страница 11: ...re CH Charger FU Bypass frequency unstable EE EEPROM error 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and p...

Страница 12: ...t frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Int...

Страница 13: ...in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 120 140 setting the high voltage point in parameter 3 from 120Vac to 140Vac Default 132Vac LLS Bypass low voltage...

Страница 14: ...When the input voltage is beyond the acceptable range or power failure and alarm is sounding every 4 second UPS will backup power from battery Bypass mode When input voltage is within acceptable range...

Страница 15: ...attery is not connected Sounding every second Over Charge Sounding every second Over temperature Sounding every second Charger failure Sounding every second Battery fault Sounding every second Out of...

Страница 16: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...

Страница 17: ...ity If the problem still persists consult your dealer Batteries defect Contact your dealer to replace the battery Fault code is shown as 05 on LCD display At the same time alarm is continuously soundi...

Страница 18: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Страница 19: ...ypical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 87 90 Battery Mode 83 87 89 BATTERY Standard Model Battery Type 12 V 9 AH 12 V 7 AH 12 V 7 AH 12 V 9 AH Numbers 2 3 6 8 6 8 Recharge Time 4 h...

Отзывы: