Axpert MKS-4000/KS-5000 Service manual
18
55
Over DC voltage on output of inverter
56
Battery connection is open
57
Current sensor failed
6.2 Warning Indicator
Warning
Code
Warning Event
Audible Alarm
Icon flashing
01
Fan is locked
Beep three times every
second
03
Battery is over charged
Beep once every
1second
04
Low battery
Beep once every 1
second
07
Overload
Beep once every 0.5
second
10
Power limitation
Beep twice every 3
seconds
6.3 Trouble shooting according to fault indication
Problem
LCD/LED/Buzzer
Explanation / Possible cause
What to do
Unit shuts down
automatically
during startup
process.
LCD/LEDs and
buzzer will be active
for 3 seconds and
then complete off.
The battery voltage is too low
(<1.91V/Cell)
1. Re-charge battery.
2. Replace battery.
No response after
power on.
No indication.
1. The battery voltage is far too
low. (<1.4V/Cell)
2. Battery polarity is connected
reversed.
1. Check if batteries and the
wiring are connected well.
2. Re-charge battery.
3. Replace battery.
Mains exist but the
unit works in
battery mode.
Input voltage is
displayed as 0 on
the LCD and green
LED is flashing.
Input protector is tripped
Check if AC breaker is
tripped and AC wiring is
connected well.
Green LED is
flashing.
Insufficient quality of AC power
(Shore or Generator)
1. Check if AC wires are too
thin and/or too long.
2. Check if generator (if
applied) is working well, or
check if input voltage range