background image

Fault Indication

LED and Buzzer

Status

Possible Cause

Fan does not spin

Installation & Wiring

Note:

 this is a guide only. It is the responsibility of the installer to ensure correct wiring.

Solution

Short circuit protection

Batteries are aged or broken

If the unit has been tested and found faulty, you must get a RMA number before sending the unit in.

It is highly reccomended that wire connections be as short as possible, and less than 1.5 meters if possible. Long 
DC wires may have Voltage drop and reduce the overall performances of an inverter. Make sure that suitable wires 
are chosen based on the rating of current. Too small of a cross-section may result in low input and high heat. 

Check the DC input source. Make sure the 
voltage is within required range AT 
TERMINALS.
Make sure that the ventilation is not blocked or 
the ambient temperature is not too high. 
Minimize load or reduce heat.
Make sure the load isnt too hihgh for the unit. Or 
the start up current is not too high. (for inductive 
or capacitive loads) Startup can be as high as 7-
10 times cont rating (will overload)

Make sure the output is not overloaded or shout 
circuited.

Get batteries tested. Replace batteries.

Connection. Obstruction. Faulty

Check that the load is not too large for battery 
size.

Check the leads for fan on PC board. Remove 
any obstruction. 

Condition

Buzzer sounds 3 times (LED 
flashes red 3 times)

The inverter should be serviced by a professional technician. Any incorrect usage or modification may damage the 
unit or result in shock hazard or damage to the unit. If you cant clear the fault condition, contact your place of 
purchase. 

Batteries are not lasting

Battery capacity is too small

Overload protection

Abnormal input

Over temperature protection

No AC output voltage

Buzzer sounds 4 times (LED 
flashes red 4 times)

Buzzer sounds 5 times (LED 
flashes red 5 times)

You must contact Electro Parts for a Return Manufacturer Authority (RMA) number

Fault Conditions

Buzzer sounds once and LED 
flashes green once

Buzzer sounds 3 times (LED 
flashes red 3 times)

This indicates normal operation. This occurs when the unit starts up.

Low voltage protection:

 These units have three stages of UVP;

1) WARNING:  Single slow warning beep & LED flash when Input is 
below 11.2V. 
2) AC SHUTOFF: Below 10.5V the Output shuts off & 3 beeps with 3 x 
LED flashes.                                                                                                       
3) INV SHUTDOWN:  It will then repeat this cycle 10 times ( 3 x beeps / 3 
Flashes x 10), unless the input Voltage increases to above 12.6V within 
that time, It will completely shut down so as to not draw any power from 
the battery (The unit will need to be switched back on manually). (all 
figures are double for 24V units)

Over load protection: 

The load is 120% higher than rated power. 

Reduce load and restart. THIS ALSO INCLUDES START UP POWER.

Over voltage protection:

 The battery voltage is too high. Make sure 

input voltage is lower than 15.5V for 12V models and 31V for 24V 
models.

Over temperature protection:

 The internal temperature is too high. 

Reduce temp and make sure there are no vents being obstructed. Make 
sure there is enough ventilation.

NOTE: diagnosing the fault without the unit being tested is not practical. If you cannot get the unit tested, you can 
return/ freight the unit back to Electro Parts Aust Pty Ltd

Отзывы: