16
Model
1KTS
1.5KTS
2KTS
3KTS
4KTS
5KTS
6KTS
7KTS
Cable (Cu)
1.5mm
2
2.5mm
2
2.5mm
2
4mm
2
4mm
2
6mm
2
6mm
2
6mm
2
MCB
10A
16A
16A
20A
20A
32A
40A
50A
MCB with rated fault current of 30 mA≤I
fn
≤300 mA should be installed between inverter and grid.
No load should be connected directly with the output of inverter.
Figure 12
Incorrect connections between Load and Inverter
Impedance of the AC connection should be less than 2Ω. To ensure anti-islanding function PV cable
should ensure power loss to be
<
1% of nominal power. Also AC cable between inverter and grid
connection point should be less than 150m. Chart below provides relationship between AC cable
length and cross section with losses
Figure 13
AC Cable Loss for inverter
inverters come with good quality IP66 /IP68 AC connector. Please refer to information
below to make correct AC connection.