background image

7

2.1 SAFETY PRECAUTIONS

Do not attempt to operate the machine until the safety 
precautions and operating instructions in this manual are 
read completely and are thoroughly understood.
Take notice of all warning labels on the machine. The la-
bels have been put there to help maintain a safe working 
environment. The labels have been designed to withstand 
washing and cleaning. All labels must remain legible for 
the life of the machine. Labels should be checked periodi-
cally to be sure they can be recognized as warning labels.
If danger, warning or caution labels are needed, indicate 
the part number, type of label, location of label, and quantity 
required along with your address and mail to:

STOELTING

ATTENTION:  Customer Service

502 Hwy. 67

Kiel, Wisconsin  53042

2.2 SHIPMENT AND TRANSIT

The machine has been assembled, operated and inspected 
at the factory. Upon arrival at the 

fi

 nal destination, the 

entire machine must be checked for any damage which 
may have occurred during transit.
With the method of packaging used, the machine should 
arrive in excellent condition. THE CARRIER IS RESPON-
SIBLE FOR ALL DAMAGE IN TRANSIT, WHETHER 
VISIBLE OR CONCEALED. Do not pay the freight bill 
until the machine has been checked for damage. Have 
the carrier note any visible damage on the freight bill. If 
concealed damage and/or shortage is found later, advise 
the carrier within 10 days and request inspection. The 
customer must place a claim for damages and/or short-
ages in shipment with the carrier. Stoelting cannot make 
any claims against the carrier.

2.3 MACHINE INSTALLATION

WARNING

Installation must be completed by a qualifi ed 
electrician/refrigeration specialist.

Incorrect installation may cause personal injury, 
severe damage to the machine and will void fac-
tory warranty.

Installation of the machine involves moving the machine 
close to its permanent location, removing all crating, set-
ting in place, assembling parts, and cleaning.
A. 

Uncrate the machine.

SECTION 2

INSTALLATION INSTRUCTIONS

B. 

Install the four casters. Turn the threaded end 
into the machine until no threads are showing. To 
level, turn out casters no more than 1/4” maximum, 
then tighten all jam nuts.

C. 

The machine must be placed in a solid level 
position.

NOTE

Accurate leveling is necessary for correct drainage 
of freezing cylinder and to insure correct overrun.

D. 

Machines with air cooled condensers require a 
minimum of 3” (7,5cm) clearance at the sides and 
6” at the back for proper circulation. (Fig. 2-1)

E. 

Machines that have a water cooled condenser 
require 1/2” NPT supply and drain 

fi

 ttings.

F. 

In air-cooled machines, use a voltmeter to measure 
incoming voltage. If the supply voltage is 215 or 
less, remove the right side panel and move the 
voltage selector toggle switch to the 208V position.

NOTE

Supply voltage must be checked to make sure the 
fan motor operates properly.

2.4 INSTALLING PERMANENT WIRING

If permanent wiring is required by local codes, the follow-
ing procedure must be performed:
A. 

Refer to the nameplate on the side panel of the 
machine for speci

fi

 c electrical requirements. Make 

sure the power source in the building matches 
the nameplate requirements.

B. 

Remove the back panel and the junction box 
cover located at the back of the machine.

C. 

Remove the installed cord and install permanent 
wiring according to local code.

Figure 2-1 Space and Ventilation Requirements

Содержание Stoelting O431

Страница 1: ...Model O431 SERVICE MANUAL Manual No 513641 Rev 1...

Страница 2: ......

Страница 3: ...built prior to date of change DO NOT ATTEMPT to operate the machine until instructions and safety precautions in this manual are read completely and are thoroughly understood If problems develop or q...

Страница 4: ...ecific safety information the following safety defini tions are provided to assist the reader The purpose of safety symbols is to attract your at tention to possible dangers The safety symbols and the...

Страница 5: ...Motor Profile Cutout Compensation 5 2 Installation Instructions 2 1 Safety Precautions 7 2 2 Shipment and Transit 7 2 3 Machine Installation 7 2 4 Installing Permanent Wiring 7 2 5 Mix Pump 8 A Mix Pu...

Страница 6: ...4 Obtaining Readings and Modifying Settings Service Personnel Only 21 4 5 Readings Service Personnel Only 22 4 6 Adjustments Service Personnel Only 23 4 7 Other Settings Service Personnel Only 23 4 8...

Страница 7: ...42 6 8 Switches 43 A Spigot Switch 43 B Pump Pressure Switch 44 C Cab Door Magnetic Reed Switch 44 6 9 Temperature Control Sensor 45 7 Troubleshooting 7 1 Error Codes 47 7 2 Troubleshooting Error Code...

Страница 8: ......

Страница 9: ...tic controls to provide a uniform product The machine is designed to operate with almost any type of commercial soft serve or non dairy mixes available including ice milk ice cream yogurt and frozen d...

Страница 10: ...Two 3 4 hp Air Flow Air cooled units require 3 7 6 cm air space on both sides and back Plumbing Fittings Water cooled units require 1 2 N P T water and drain fittings Hopper Volume Two 5 5 gallons 20...

Страница 11: ...erature increases to a preset amount Cut In T a 3 second drive motor pre stir analyzes product consistency The pre stir check is also performed each time the spigot handle is opened This check prevent...

Страница 12: ...2CutIn and Sl2CtOut During the Sleep 2 Mode the stir cycle runs This cycle is based on preset timed intervals Stir On and Stir Off and prevents product separation The Sleep 2 Mode is often referred to...

Страница 13: ...50 F for more than two hours the machine will go into Sleep Mode and a clean message will be shown on the display 1 6 OPERATION DURING SENSOR FAILURE The IntelliTec control is designed to allow the m...

Страница 14: ...20 sec Sleep 1 Drive motor on timer Sl1DrOff 180 sec Sleep 1 Drive motor off timer Sl2CutIn 32 F Sleep 2 Cut in temperature Sl2CtOut 28 F Sleep 2 Cut out temperature DftOffTm 600 sec No Sensor Default...

Страница 15: ...ING Installation must be completed by a qualified electrician refrigeration specialist Incorrect installation may cause personal injury severe damage to the machine and will void fac tory warranty Ins...

Страница 16: ...clamp Be careful not to twist the mix hose 7 Turn the pump on 8 Allow the remaining 6 15cm of tubing to feed through pump until the hose adapter prevents further feeding 9 Turn the pump off CAUTION R...

Страница 17: ...ontainer is important The bag that is connected nearest the outlet of the manifold will drain last and should be placed at the back of the mix container The mix low level indicator relies on proper ba...

Страница 18: ...manifold adapter Securewithalargehose clamp 3 Push the manifold adapter with spring and valve into the left port nearest the manifold outlet of the mix inlet manifold and secure with retaining clip S...

Страница 19: ...ion of the operating controls on the machine For the information regarding error codes displayedonthecontrolpanel refertothetroubleshooting section of this manual A MAIN FREEZER POWER SWITCH The Main...

Страница 20: ...ng Cylinder OFF ON switch to the OFF position or press the CLEAN button again If the machine is left in CLEAN for more than 20 minutes an error code E4 will be displayed on the display panel Place the...

Страница 21: ...3 Remove the front door by pulling it off the studs 4 Remove the air bleed valve by unscrewing the knob while holding the valve stem from behind Remove the compression spring and push the air bleed va...

Страница 22: ...wipe with the grain of the steel A Clean the rear seal surface from inside of the freezing cylinder B Using sanitizing solution and the large barrel brush provided sanitize the freezing cylinder by di...

Страница 23: ...processing equipment be certified for this use When sanitizing the machine refer to local sanitary regu lations for applicable codes and recommended sanitizing products and procedures The frequency o...

Страница 24: ...DISPLAY 9 Press the left arrow button once The display will read BASIC 10 Press the up arrow button once The display will read CutOut amps 11 Press the SET button A cursor will start blinking under t...

Страница 25: ...mix pump switch in the ON position F Place a container under the spigot and open the spigot to allow the mix to flush out about 8 ounces 0 23 liters of sanitizing solution and liquid mix G Open the a...

Страница 26: ...on the piston downstroke The air is discharged through a second check valve on the piston upstroke The air and mix join at the tee and then travel to the machine C The overrun adjustment is preset at...

Страница 27: ...if applicable as an assembly from the mix container C Completely disassemble the hose assembly and the check valve Fig 3 10 Place hoses tee checkvalveassembly andpickuphoseadapterin 90 to 110 F 32 C...

Страница 28: ...20...

Страница 29: ...low to lock the control panel A Press and hold the PUSH TO FREEZE button for at least 5 seconds B While still holding the PUSH TO FREEZE button press the CLEAN button once C Release both buttons An as...

Страница 30: ...he Cycles setting on the IntelliTec control F and amps Suction line temperature on the freezing cylinder and drive motor amps are available on the same screen to assist with setup and troubleshooting...

Страница 31: ...ure of the refrigerant gas in the evaporator at the front of the freezing cylinder Changingthissettingchangesthetemperatureat which the freezing cycle starts This value along with the CutOut value det...

Страница 32: ...g Cab Off will not be shown on the IntelliTec menu Cab On If the Refriger value is set to Cabinet and the temperaturesensorinthecabinetfails thissetting determines the length of the refrigeration cycl...

Страница 33: ...rough pump B Turn the pump off and relieve any pressure by opening the spigot C Grasp the pickup hose end of the mix pump hose with one hand and turn the pump on Pull down on the pickup hose end until...

Страница 34: ...n for 8 seconds While still holding the SEL button press the up arrow button The LCD Screen will read Display B Release both buttons C Press the left arrow button three 3 times to navigate to the Stor...

Страница 35: ...ise or condition and repair immediately B Monthly checks 1 Check drive belts for wear and tighten belts if necessary Refer to section 4 12 2 Check the condenser filter for dirt Refer to section 4 13 4...

Страница 36: ...28...

Страница 37: ...TE For qualified service personnel only Anybody work ing with refrigerants must be certified as a Techni cian TYPE I as required by 40 CFR 82 Subpart F and hold all State and or local refrigerant hand...

Страница 38: ...e solenoid valves open 11 If the system will not maintain a standing vacuum test with the vacuum pump off gauge increases towards atmosphere find the leak fix it and evacuate again 5 3 REFRIGERANT CHA...

Страница 39: ...ch as any copper line leading to or from the compressor and check terminals C R and S NOTE The compressor is equipped with an internal over load protector If the compressor is warm and ohm meter readi...

Страница 40: ...OR The O431 has two freezing cylinder evaporators and a cab evaporator EVAPORATOR TESTING The evaporator can be checked for leaks using the bubble test or using a leak detector NOTE Foam insulation in...

Страница 41: ...sink from the TXV D Install bulb on suction line exiting the evaporator using existing clamp The bulb has an indent that must be placed against the tubing NOTE Good contact between the bulb and the su...

Страница 42: ...s the only part of the system requiring refrigerant the bypass valve will allow discharge gas to bypass into the suction line to prevent liquid refrigerant from entering the compressor HOT GAS BYPASS...

Страница 43: ...the opening point pressure should be increased to slow the water flow Turn the adjustment screw counterclockwise F If the water temperature and high side pressure are too high the opening point pressu...

Страница 44: ...AGNETIC COIL REMOVAL A Remove the side panel B Disconnect the electrical wires C Remove the retaining screw from the top of the solenoid and pull the magnetic coil off SOLENOID MAGNETIC COIL INSTALLAT...

Страница 45: ...ing appropriate brazing material D Evacuate the system per instructions in Section 5 2 E Recharge the system per instructions in Section 5 3 5 10 CAB UNIT TheIntelliTeccontrolisprogrammedtohandlerefri...

Страница 46: ...38...

Страница 47: ...ntrol board is connected to the machine through an 8 pin connector a 7 pin con nector and a 6 pin connector Theleftsidemembraneswitch touchpad controlstheleft side of the freezer and the right side me...

Страница 48: ...contactor When the spigot is opened or the Push To Freeze button is pressed the DRV LED on the control board will light up After three seconds the CMP LED will light up Refer to Figure 6 4 If the LED...

Страница 49: ...sening the set screws B DRIVE MOTOR INSTALLATION 1 Place the drive motor in position and install the four mounting bolts 2 Place the pulley and key on the motor shaft NOTE Do not tighten the pulley sc...

Страница 50: ...gearbox to the rear of the barrel 2 Fastenthegearboxtothemountingbracketusing the two bolts 3 Mount the pulley on the gearbox shaft and align with the motor pulley then tighten the allen head screws...

Страница 51: ...o the spigot switch should be done after the product is at consistency in Serve Mode or when the machine is empty 1 Open the spigot slowly and listen for a click when the spigot switch closes 2 The cl...

Страница 52: ...UMP PRESSURE SWITCH TEST 1 Turn off the pump motor 2 Open the spigot to relieve air pressure in the system 3 Connect a gauge between the 1 4 ID tubing and the air line into the cab The air line is at...

Страница 53: ...disconnected from electrical supply before removing any access panel Failure to disconnect power before servicing could result in death or serious injury 6 9 TEMPERATURE CONTROL SENSOR The temperature...

Страница 54: ...46...

Страница 55: ...themixisbrokendown cleanandsanitizethe machine and replace the mix with fresh product Icecrystalsintheliquidmixcontainercanclogthe mix inlet system and prevent mix from entering the freezing cylinder...

Страница 56: ...panel still displays the error condition code refer to the wiring diagram and the temperature sensor value table Check each lead of the sensor to ground for continuity If continuity is found replace...

Страница 57: ...IntelliTec control will display an E11 COMMO TIMEOUT Error A COMMO TIMEOUT Error indicates a communication interruption between the display and the control board This error can be caused by a poor co...

Страница 58: ...5 Check system Call distributor for service Product does not dispense 1 No mix in hopper 1 Add mix to the hopper 2 Drive motor overload tripped 2 Wait for automatic reset If condition continues call d...

Страница 59: ...f Draw 2 3 pints to reduce system pressure to zero Turn pump on Purge remaining air in mix bag and pick up hose Important before connecting the pick up hose to the mix bag remove as much air from the...

Страница 60: ...clean pump 1 Mix pump hose service life is exceeded 1 Remove mix pump hose Disconnect pump from power source Remove mix pump cover clamp Clean the rollers a small amount of soapy water Clean mix from...

Страница 61: ...ing Instructions 1 324566 Decal Wired According To 1 324584 Decal Adequate Ventilation 3 2 324686 Decal Danger Automatic Start 2 324799 Decal Pump Off On 2 324803 Decal Domed Stoelting Logo Large Head...

Страница 62: ...ot Black 5 Pack 2 624664 5 O Ring Middle Center Spigot Black 5 Pack 1 624678 5 O Ring Rear Seal Rear Seal Adapter Black 5 Pack 4 625133 O Ring Front Door Red 2 667868 Seal Rear Auger Orange 2 694200 S...

Страница 63: ...lve 2 696152 Clip Lock Check Valve 2 756067 Tubing 1 4 ID Clear Air Line 25 Increments Per Inch 13 2 756079 Tubing 3 8 ID Clear Mix Line 25 Increments Per Inch 24 2 756088 Tubing 1 2 ID Clear Mix Line...

Страница 64: ...Cam 4 2158082 Glide Spigot Socket 3 2158260 Handle Spigot Metal Only 3 8 6 STAINLESS STEEL PANELS Part Number Description Quantity 647653 Screw Panel Header Top Cab Door Handle 647899 Screw Panel Sid...

Страница 65: ...ssor 1 PH 60 Hz Scroll No Capacitors 1 282076 Compressor 1 PH 50 Hz No Capacitors 284085 Condenser Air Cooled 357102 Motor Fan w Blade Guard Air Cooled Condenser 1 558004 Condensate Pan 1 598031 Pulle...

Страница 66: ...wer 1 368325 Filter Air Condenser 1 522858 SV Motor Drive 60 Hz 2 522859 Motor Drive 50 Hz 614233 Speed Reducer 2 718539 Switch Toggle 208 230 1 762275 Valve Magna Check Cab 2 763423 Valve Solenoid 1...

Страница 67: ...58010 Indicator Liquid Line 1 493042 Flasher Indicator Light Cab On Off 1 762481 Valve Expansion Has 2 2 762457 SV Valve Expansion w Orifice Cab 1 763422 Valve Solenoid 1 4 Liquid Line Has 3 3 763482...

Страница 68: ...Display Module Display Only 2 493041 Indicator Light Cab On Off 1 521686 230 Program Board IntelliTec 208V 230V 2 618180 Relay 282062 282076 Compressor 1 718532 Switch Toggle Freezing Cylinder On Off...

Страница 69: ...522307 SV Motor Fan Evaporator Assembly Cab 1 647674 Screw Door Hinge Cab 672724 Sensor Capacitive Cab 2 719123 SV Switch Only Cab Door Hamlin Reed Switch Cab 1 736084 Thermometer Cab 1 2187296 Guard...

Страница 70: ...1871 Spring Piston 2 1171872 Piston Spring Seat 2 1171873 Piston 2 1171874 Ball Bearing Single Pump Rocker Arm 2 1171955 Set Screw Eccentric 2 1171956 Washer Crank Arm Nylon 2 1171958 Filter Air 2 117...

Страница 71: ...37 717928 432003 SV 1171868 1171867 1171870 1171986 1171985 1171988 2177812 3171952 653042 1171987 1171986 644065 1177681 1171874 1171955 1171981 1171983 1171866 1171982 1171956 1171978 1171979 117197...

Страница 72: ...Check Valve Body Black 6 624614 O Ring Top Bottom Center Spigot Black 4 624664 O Ring Middle Center Spigot Black 3 624677 O Ring Spigot Extension Black 4 624678 O Ring Rear Seal Black 5 625133 O Ring...

Страница 73: ...65 0 0 0 8 14 REFRIGERATION DIAGRAM AND WIRING DIAGRAM...

Страница 74: ...66...

Страница 75: ...ons remedies are subject to the conditions that Buyer a signs and returns to Stoelting upon installation the Start Up and Training Checklist for the affected equipment b gives Stoelting prompt written...

Отзывы: